TABLE 15

Cooling Mode Blower Speed Ramping

Ramping Option

Switch 9

Switch 10

A (Factory)

Off

Off

B

Off

On

C

On

Off

D

On

On

Ramping Option A (Factory Selection)

DMotor runs at 50% for 30 seconds.

DMotor then runs at 82% for approximately 7−1/2 minu- tes.

DIf demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.

DOnce demand is met, motor runs at 50% for 30 sec- onds then ramps down to stop.

OFF

 

 

 

 

7 1/2 MIN

 

 

100%

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

82% CFM

 

CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2 MIN

 

 

 

1/2 MIN

 

 

50% CFM

 

 

 

50% CFM

COMPRESSOR DEMAND

Ramping Option B

SMotor runs at 82% for approximately 7−1/2 minutes. If demand has not been satisfied after 7−1/2 minutes, motor runs at 100% until demand is satisfied.

SOnce demand is met, motor ramps down to stop.

 

7 1/2 MIN

100% CFM

 

OFF

82%CFM

 

OFF

 

COMPRESSOR DEMAND

 

Ramping Option C

SMotor runs at 100% until demand is satisfied.

SOnce demand is met, motor runs at 100% for 45 sec- onds then ramps down to stop.

100% CFM

100% CFM

OFF

OFF

 

COMPRESSOR

DEMAND 45 SEC.

Ramping Option D

SMotor runs at 100% until demand is satisfied.

SOnce demand is met, motor ramps down to stop.

OFF

100% CFM

OFF

 

COMPRESSOR

 

DEMAND

Switches 11, 12 and 13 −− Heating Mode Blower Speed −− The switches are factory set to the OFF position which pro- vides factory default heat speed. Refer to table 16 for switches 11, 12 and 13 that provided the corresponding in- creases or decrease to both high and low heat demand.

TABLE 16

Heating Mode Blower Speeds

Heat Speed

Switch

Switch

Switch

11

12

13

 

 

 

 

 

Increase 24%

On

On

On

 

 

 

 

Increase 18%

On

On

Off

 

 

 

 

Increase 12%

On

Off

On

 

 

 

 

Increase 6%

On

Off

Off

 

 

 

 

Factory Default

Off

Off

Off

 

 

 

 

Decrease 6%

Off

Off

On

 

 

 

 

Decrease 12%

Off

On

Off

 

 

 

 

Decrease18%

Off

On

On

 

 

 

 

Switches 14 and 15 −− Continuous Blower Speed −− Table 17 provides continuous blower speed adjustments that will result from different switch settings.

TABLE 17

Continuous Blower Speed

Continuous

Switch 14

Switch 15

Blower Speed

 

 

 

 

 

28% of High Cool Speed

Off

On

 

 

 

38% of High Cool Speed

Off

Off

(Factory)

 

 

 

 

 

70% of High Cool Speed

On

Off

 

 

 

100% of High Cool Speed

On

On

 

 

 

Page 37

Image 37
Contents Table of Contents Installation Instructions SL280UHVReturn air from both sides Unit Dimensions − inches mmSide Return Air Opening Either SideParts Arrangement Access Panel Blower AssemblySight Glass SL280UHV Gas Furnace Safety InformationShipping and Packing List General Use of Furnace as Construction HeaterAir Handler Unit EvaporatorCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment in Confined Space Equipment in Confined Space ALL AIR from OutsideEquipment Confined Space ALL AIR from Outside Bottom Setting EquipmentBlower Motor Rigid LEG Furnace Front 20 X 25 XIndoor AIR Return AIR BaseRight Horizontal Application Installation Clearances Top LeftEnd Bottom Typical Horizontal ApplicationDuct System FiltersUpflow Position VentingTop Vent Discharge Left Side Vent DischargeHorizontal Right Position Horizontal Left PositionSide Vent Discharge Disconnected Vent Common Venting Using Metal−Lined Masonry ChimneySticker Vent PipeThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard − In some localities, codes may require the installation Ers or straps. Install a drip leg in vertical pipe runs toGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangLeft−Side Air Discharge Horizontal ApplicationRight−Side Air Discharge Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD BOXCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Communicating System Wiring NON−COMMUNICATING System Wiring120V Connections ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram RS−BUS Link TB82, future use Integrated Control+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 985 1045940 880SL280UH090V36B Blower Performance less filter 1220 12801155 10951235 12951170 11101230 13601165 11001225 12901160 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorUnit Start−Up For Your Safety Read Before LightingWhite Rodgers GAS Valve Honeywell GAS ValveGAS Meter Clocking Chart Gas Pressure AdjustmentProper Combustion DialHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsHeating Operation with Single Stage Thermostat Heating Operation with TWO−STAGE ThermostatSEC Electrical SHOCK, Fire Or Explosion Hazard Service13− To clean the combustion air inducer visually inspect SL280UHV BURNER, Combustion AIR Inducer Assembly11− Back wash using steam. Begin from the burner opening 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesFurnace / air handler. Clears after fault recovered Normal operation 5 seconds after fault recoveredPower at the thermostat. Alert stops all services Equipment is unable to communicate. IndicatesMissioning and Execute ’Set Factory Default mode’ Reconfigure the system. Replace control if heatingControl will still operate on default parameter set Ate feature will be set as ’installed’ and that couldSumes normal operation after fault is cleared Low pressure switch failed openFault is cleared Tion after fault is clearedOut. Clears when flame has been proven stable Open or not within specifications −hour soft lockSoft lockout or reset To flame failureIs not running. Check power to outdoor unit. Clears Pair/add duct. Cleared after the current service deError after current is sensed in both RUN Vice is removed, or after power resetSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation