Lennox International Inc SL280UH090V48B Equipment in Confined Space ALL AIR from Outside

Page 8

EQUIPMENT IN CONFINED SPACE

ALL AIR FROM OUTSIDE

(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)

CHIMNEY OR

GAS VENT

VENTILATION LOUVERS

(Each end of attic)

 

OUTLET

 

FURNACE

AIR

WATER

 

 

HEATER

VENTILATION

 

INLET

 

AIR

LOUVERS

 

 

 

(For unheated crawl space)

 

 

 

AIR FLOW

 

NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.

FIGURE 3

 

 

 

 

EQUIPMENT IN CONFINED SPACE

 

 

 

 

 

 

 

ALL AIR FROM OUTSIDE

CHIMNEY

 

 

 

 

(All Air Through Ventilated Attic)

OR GAS

 

 

 

 

 

 

 

 

 

 

 

 

VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTILATION LOUVERS

 

 

 

 

 

 

 

 

 

 

 

 

(Each end of attic)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTLET

AIR

FURNACE

INLET AIR

 

 

(Ends 12 in.

 

above bottom)

 

WATER

 

HEATER

 

AIR FLOW

NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equip- ment in the enclosure.

EQUIPMENT IN

CONFINED SPACE

ALL AIR FROM

OUTSIDE

CHIMNEY

OR GAS

VENT WATER

HEATER

OUTLET AIR

FURNACE

INLET AIR

AIR FLOW

NOTE − Each air duct opening shall have a free area of at least one square inch (645 mm2) per 2,000 Btu (.59 kW) per hour of the total input rating of all equipment in the enclosure. If the equipment room is located against an outside wall and the air openings communicate directly with the outdoors, each open- ing shall have a free area of at least one square inch (645 mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all other equipment in the enclosure.

FIGURE 4

FIGURE 5

Page 8

Image 8
Contents Installation Instructions SL280UHV Table of ContentsUnit Dimensions − inches mm Return air from both sidesSide Return Air Opening Either SideSight Glass Access Panel Blower AssemblyParts Arrangement Shipping and Packing List Safety InformationSL280UHV Gas Furnace Use of Furnace as Construction Heater GeneralAir Handler Unit EvaporatorCombustion, Dilution & Ventilation Air Equipment in Confined Space ALL AIR from InsideEquipment Confined Space ALL AIR from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space Blower Motor Rigid LEG Setting EquipmentBottom 20 X 25 X Furnace FrontIndoor AIR Return AIR BaseHorizontal Application Installation Clearances Top Left RightEnd Bottom Typical Horizontal ApplicationFilters Duct SystemVenting Upflow PositionTop Vent Discharge Left Side Vent DischargeSide Vent Discharge Horizontal Left PositionHorizontal Right Position Common Venting Using Metal−Lined Masonry Chimney Disconnected VentSticker Vent PipeVent Connector Through an unused masonry chimney flue is not considered102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Ers or straps. Install a drip leg in vertical pipe runs to − In some localities, codes may require the installationGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangRight−Side Air Discharge Horizontal ApplicationLeft−Side Air Discharge Interior MAKE−UP BOX Installation ElectricalElectrostatic Discharge ESD BOXNon−Communicating CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch NON−COMMUNICATING System Wiring Communicating System Wiring120V Connections ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated ControlRS−BUS Link TB82, future use −10% approx OFF On−Board Links 1045 985940 880SL280UH090V36B Blower Performance less filter 1280 12201155 10951295 12351170 11101360 12301165 11001290 12251160 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Compressor Thermostat energizes Y2For Your Safety Read Before Lighting Unit Start−UpWhite Rodgers GAS Valve Honeywell GAS ValveGas Pressure Adjustment GAS Meter Clocking ChartProper Combustion DialHigh Altitude Other Unit Adjustments Heating Sequence of OperationSEC Heating Operation with TWO−STAGE ThermostatHeating Operation with Single Stage Thermostat Service Electrical SHOCK, Fire Or Explosion HazardSL280UHV BURNER, Combustion AIR Inducer Assembly 13− To clean the combustion air inducer visually inspect11− Back wash using steam. Begin from the burner opening 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Planned Service Repair Parts ListIntegrated Control Diagnostic Modes Integrated Control Diagnostic CodesNormal operation 5 seconds after fault recovered Furnace / air handler. Clears after fault recoveredPower at the thermostat. Alert stops all services Equipment is unable to communicate. IndicatesReconfigure the system. Replace control if heating Missioning and Execute ’Set Factory Default mode’Control will still operate on default parameter set Ate feature will be set as ’installed’ and that couldLow pressure switch failed open Sumes normal operation after fault is clearedFault is cleared Tion after fault is clearedOpen or not within specifications −hour soft lock Out. Clears when flame has been proven stableSoft lockout or reset To flame failurePair/add duct. Cleared after the current service de Is not running. Check power to outdoor unit. ClearsError after current is sensed in both RUN Vice is removed, or after power resetSor run cycle, or after power reset Program Unit Capacity/Size Mode FinishedTroubleshooting Heating Sequence of Operation Call for FIRST−STAGE HeatCall for SECOND−STAGE Heat Call for Heat SatisfiedCall for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE Heat 2ND Stage HeatTroubleshooting Cooling Sequence of Operation Call for CoolingTroubleshooting Continuous Fan Sequence of Operation Call for FAN