High Altitude

The manifold pressure, gas orifice and pressure switch may require adjustment or replacement to ensure proper operation at higher altitudes. Tables 22 through 25 shows

manifold pressure, pressures switch and gas conversion kits at all altitudes.

IMPORTANT

For safety, shut unit off and remove manometer as soon as an accurate reading has been obtained. Take care to replace pressure tap plug.

TABLE 22

Manifold Pressure Settings

 

 

 

 

Manifold

Manifold

Manifold

Supply Line

Unit

 

Orifice Size

Orifice Size

Pressure in.wg.

Pressure in.wg.

Pressure in.wg.

Pressure

Gas

7501 −

0−4500 ft.

4501−7500 ft.

7501 − 10,000 ft.2

in. w.g.

Input

0 − 7500 ft.

10,000 ft.1

 

 

 

 

 

 

 

 

 

Low

High

Low

High

Low

High

Min

Max

 

 

 

 

 

 

 

 

Fire

Fire

Fire

Fire

Fire

Fire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural

.063

.055

1.7

3.5

1.6

3.4

1.7

3.5

4.5

13.0

070

 

 

 

 

 

 

 

 

 

 

 

LP/propane3

.039

.037

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

 

Natural

.063

.055

1.7

3.5

1.5

3.2

1.7

3.5

4.5

13.0

090

 

 

 

 

 

 

 

 

 

 

 

LP/propane3

.039

.037

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

 

Natural

.063

.055

1.7

3.5

1.5

3.2

1.7

3.5

4.5

13.0

110

 

 

 

 

 

 

 

 

 

 

 

LP/propane3

.039

.037

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

 

Natural

.063

.055

1.7

3.5

1.6

2.8

1.7

3.5

4.5

13.0

135

 

 

 

 

 

 

 

 

 

 

 

LP/propane3

.039

.037

4.9

10.0

4.9

10.0

4.9

10.0

11.0

13.0

 

1This is the only permissible derate for these units.

2Natural gas high altitude orifice kit required.

3A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion procedure.

NOTE − Units may be installed at altitudes up to 4500 ft. above sea level without modifications.

TABLE 23

High Altitude Pressure Switch Kits

 

 

High Altitude

 

Unit

 

Pressure Switch Kit

Input

 

 

 

0 − 4500 ft.

4501 − 7500 ft.

7501 − 10,000 ft.

 

 

 

 

 

070

No Change

No Change

73W35

 

 

 

 

090

No Change

69W56

73W35

 

 

 

 

110

No Change

69W56

73W35

 

 

 

 

135

No Change

73W33

73W34

 

 

 

 

TABLE 24

Honeywell Gas Valve Conversion Kits

 

High Altitude

 

 

LP/Propane

 

Natural Gas to

to

 

Natural Gas

 

LP/ Propane Kit

Natural Gas

Unit

Orifice Kit

 

 

Kit

Input

 

 

 

 

 

 

 

 

7501 −

0 − 7500 ft.

7501 −

0 − 7500 ft.

 

10,000 ft.

10,000 ft.

 

 

 

 

 

 

 

 

070

73W37

51W02

73W38

69W79

 

 

 

 

 

090

73W37

51W02

73W38

69W79

 

 

 

 

 

110

73W37

51W02

73W38

69W79

 

 

 

 

 

135

73W37

51W02

73W38

69W79

 

 

 

 

 

TABLE 25

White Rodgers Gas Valve Conversion Kits

 

High Altitude

 

 

LP/Propane

 

Natural Gas to

to

 

Natural Gas

 

LP/ Propane Kit

Natural Gas

Unit

Orifice Kit

 

 

Kit

Input

 

 

 

 

 

 

 

 

7501 −

0 − 7500 ft.

7501 −

0 − 7500 ft.

 

10,000 ft.

10,000 ft.

 

 

 

 

 

 

 

 

070

77W05

77W07

77W11

77W09

 

 

 

 

 

090

77W05

77W07

77W11

77W09

 

 

 

 

 

110

77W05

77W07

77W11

77W09

 

 

 

 

 

135

77W05

77W07

77W11

77W09

 

 

 

 

 

Page 53

Image 53
Contents Table of Contents Installation Instructions SL280UHVReturn air from both sides Unit Dimensions − inches mmSide Return Air Opening Either SideSight Glass Access Panel Blower AssemblyParts Arrangement Shipping and Packing List Safety InformationSL280UHV Gas Furnace General Use of Furnace as Construction HeaterAir Handler Unit EvaporatorCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment Confined Space ALL AIR from Outside Equipment in Confined Space ALL AIR from OutsideEquipment in Confined Space Blower Motor Rigid LEG Setting EquipmentBottom Furnace Front 20 X 25 XIndoor AIR Return AIR BaseRight Horizontal Application Installation Clearances Top LeftEnd Bottom Typical Horizontal ApplicationDuct System FiltersUpflow Position VentingTop Vent Discharge Left Side Vent DischargeSide Vent Discharge Horizontal Left PositionHorizontal Right Position Disconnected Vent Common Venting Using Metal−Lined Masonry ChimneySticker Vent PipeThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard − In some localities, codes may require the installation Ers or straps. Install a drip leg in vertical pipe runs toGas Piping Every 8 to 10 feet 2.44 to 3.01 m with suitable hangRight−Side Air Discharge Horizontal ApplicationLeft−Side Air Discharge Electrical Interior MAKE−UP BOX InstallationElectrostatic Discharge ESD BOXCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Communicating System Wiring NON−COMMUNICATING System Wiring120V Connections ApplicationsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram + = Data High Connection − = Data LOW Connection Integrated ControlRS−BUS Link TB82, future use −10% approx OFF On−Board Links 985 1045940 880SL280UH090V36B Blower Performance less filter 1220 12801155 10951235 12951170 11101230 13601165 11001225 12901160 1380+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorUnit Start−Up For Your Safety Read Before LightingWhite Rodgers GAS Valve Honeywell GAS ValveGAS Meter Clocking Chart Gas Pressure AdjustmentProper Combustion DialHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsSEC Heating Operation with TWO−STAGE ThermostatHeating Operation with Single Stage Thermostat Electrical SHOCK, Fire Or Explosion Hazard Service13− To clean the combustion air inducer visually inspect SL280UHV BURNER, Combustion AIR Inducer Assembly11− Back wash using steam. Begin from the burner opening 17− Reinstall burner box, manifold assembly and burner boxSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesFurnace / air handler. Clears after fault recovered Normal operation 5 seconds after fault recoveredPower at the thermostat. Alert stops all services Equipment is unable to communicate. IndicatesMissioning and Execute ’Set Factory Default mode’ Reconfigure the system. Replace control if heatingControl will still operate on default parameter set Ate feature will be set as ’installed’ and that couldSumes normal operation after fault is cleared Low pressure switch failed openFault is cleared Tion after fault is clearedOut. Clears when flame has been proven stable Open or not within specifications −hour soft lockSoft lockout or reset To flame failureIs not running. Check power to outdoor unit. Clears Pair/add duct. Cleared after the current service deError after current is sensed in both RUN Vice is removed, or after power resetSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation