Lennox International Inc SL280UH090V48B Low pressure switch failed open, Fault is cleared

Page 63

Integrated Control Diagnostic Codes (continued)

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

 

 

 

E 223

Low pressure switch failed open.

Check pressure (inches w.c.) of low pressure switch

 

 

closing on heat call. Measure operating pressure

 

 

(inches w.c.). Inspect vent and combustion air in-

 

 

ducer for correct operation and restriction. Re-

 

 

sumes normal operation after fault is cleared

 

 

 

E 224

Low pressure switch failed closed − Refer to troubleshooting. See

Check operation of low pressure switch to see if it is

 

Page 68.

stuck closed on heat call longer than 150 seconds.

 

 

Measure operating pressure (inches w.c.). Inspect

 

 

vent and combustion air inducer for correct opera-

 

 

tion and restriction. Resumes normal operation after

 

 

fault is cleared.

 

 

 

E 225

High pressure switch failed open − Refer to troubleshooting. See

Check pressure (inches w.c.) of high pressure

 

Page 68.

switch closing on heat call. Measure operating pres-

 

 

sure (inches w.c.). Inspect vent and combustion air

 

 

inducer for correct operation and restriction. Re-

 

 

sumes normal operation after fault is cleared.

 

 

 

E 226

High pressure switch failed closed − Refer to troubleshooting. See

Check operation of high pressure switch closing on

 

Page 68.

heat call. Measure operating pressure (inches w.c.).

 

 

Inspect vent and combustion air inducer for correct

 

 

operation and restriction. Resumes normal opera-

 

 

tion after fault is cleared.

 

 

 

E 227

Low pressure switch open during trial for ignition or run mode. Refer to

Check pressure (inches w.c.) of low pressure switch

 

troubleshooting. See Page 68.

closing on heat call. Measure operating pressure

 

 

(inches w.c.). Inspect vent and combustion air in-

 

 

ducer for correct operation and restriction. Re-

 

 

sumes normal operation after fault is cleared.

 

 

 

E 228

Combustion air inducer calibration failure

Unable to perform pressure switch calibration.

 

 

Check vent system and pressure switch wiring con-

 

 

nections. Resumes normal operation after fault is

 

 

cleared.

 

 

 

E 229

Ignition on high fire

IFC switched to high fire ignition because low fire

 

 

pressure switch did not close in allowed time. No

 

 

action is needed.

 

 

 

E 240

Low flame current − Run mode − Refer to troubleshooting. See Page 68.

Check micro−amperes of flame sensor using control

 

 

diagnostics or field−installed mode. Clean or replace

 

 

sensor. Measure voltage of neutral to ground to en-

 

 

sure good unit ground. Alert clears after current

 

 

heat call has been completed.

 

 

 

E 241

Flame sensed out of sequence − Flame still present.

Shut off gas. Check for gas valve leak. Replace, if

 

 

necessary. Alert clears when fault is recovered.

 

 

 

E 250

Limit switch circuit open − Refer to troubleshooting.

Check for proper firing rate on furnace. Ensure

 

 

there is no blockage in heater. Check for proper air

 

 

flow. If limit not closed within 3 minutes, unit will go

 

 

into 1−hour soft lockout. Resumes normal operation

 

 

after fault is cleared.

 

 

 

E 252

Discharge air temperature too high (gas heat only).

Check temperature rise, air flow and input rate.

 

 

Cleared when heat call is finished.

 

 

 

E 270

Soft lockout − Exceeded maximum number of retries. No flame current

Check for proper gas flow. Ensure that ignitor is

 

sensed.

lighting burner. Check flame sensor current. Clears

 

 

when heat call finishes successfully.

 

 

 

E 271

Soft lockout − Exceeded maximum number of retries. Last retry failed due

Check pressure (inches w.c.) of low pressure switch

 

to the pressure switch opening.

closing on heat call. Measure operating pressure

 

 

(inches w.c.). Inspect vent and combustion air in-

 

 

ducer for correct operation and restriction. Clears

 

 

when heat call finishes successfully.

 

 

 

Page 63

Image 63
Contents Table of Contents Installation Instructions SL280UHVEither Side Unit Dimensions − inches mmReturn air from both sides Side Return Air OpeningAccess Panel Blower Assembly Parts ArrangementSight Glass Safety Information SL280UHV Gas FurnaceShipping and Packing List Evaporator Use of Furnace as Construction HeaterGeneral Air Handler UnitCombustion, Dilution & Ventilation Air Space ALL AIR from Inside Equipment in ConfinedEquipment in Confined Space ALL AIR from Outside Equipment in Confined SpaceEquipment Confined Space ALL AIR from Outside Setting Equipment BottomBlower Motor Rigid LEG Return AIR Base 20 X 25 XFurnace Front Indoor AIRTypical Horizontal Application Horizontal Application Installation Clearances Top LeftRight End BottomDuct System FiltersLeft Side Vent Discharge VentingUpflow Position Top Vent DischargeHorizontal Left Position Horizontal Right PositionSide Vent Discharge Vent Pipe Common Venting Using Metal−Lined Masonry ChimneyDisconnected Vent StickerThrough an unused masonry chimney flue is not considered Vent Connector102 127 −1/2 152 178 10−1/2 MIN MAX Feet FAN + FAN FAN + NAT 130 Carbon Monoxide Poisoning Hazard Every 8 to 10 feet 2.44 to 3.01 m with suitable hang Ers or straps. Install a drip leg in vertical pipe runs to− In some localities, codes may require the installation Gas PipingHorizontal Application Left−Side Air DischargeRight−Side Air Discharge BOX Interior MAKE−UP BOX InstallationElectrical Electrostatic Discharge ESDCommunicating Non−CommunicatingIcomfortt Integrated Control Outdoor Unit Icomfort Touch Applications NON−COMMUNICATING System WiringCommunicating System Wiring 120V ConnectionsDIP Switch Settings and On−Board Links See figure OFF Single Stage Thermostat w Dual fuel capa Bilities SL280UHV Schematic Wiring Diagram Typical SL280UHV Field Wiring Diagram Integrated Control RS−BUS Link TB82, future use+ = Data High Connection − = Data LOW Connection −10% approx OFF On−Board Links 880 1045985 940SL280UH090V36B Blower Performance less filter 1095 12801220 11551110 12951235 11701100 13601230 11651380 12901225 1160+18% 1605 SL280UH110V60C Blower Performance less filter +18% 1785 SL280UH135V60D Blower Performance less filter Operating Sequence Thermostat energizes Y2 CompressorHoneywell GAS Valve For Your Safety Read Before LightingUnit Start−Up White Rodgers GAS ValveDial Gas Pressure AdjustmentGAS Meter Clocking Chart Proper CombustionHigh Altitude Heating Sequence of Operation Other Unit AdjustmentsHeating Operation with TWO−STAGE Thermostat Heating Operation with Single Stage ThermostatSEC Electrical SHOCK, Fire Or Explosion Hazard Service17− Reinstall burner box, manifold assembly and burner box SL280UHV BURNER, Combustion AIR Inducer Assembly13− To clean the combustion air inducer visually inspect 11− Back wash using steam. Begin from the burner openingSL280UHV NOX Inserts Repair Parts List Planned ServiceIntegrated Control Diagnostic Codes Integrated Control Diagnostic ModesEquipment is unable to communicate. Indicates Normal operation 5 seconds after fault recoveredFurnace / air handler. Clears after fault recovered Power at the thermostat. Alert stops all servicesAte feature will be set as ’installed’ and that could Reconfigure the system. Replace control if heatingMissioning and Execute ’Set Factory Default mode’ Control will still operate on default parameter setTion after fault is cleared Low pressure switch failed openSumes normal operation after fault is cleared Fault is clearedTo flame failure Open or not within specifications −hour soft lockOut. Clears when flame has been proven stable Soft lockout or resetVice is removed, or after power reset Pair/add duct. Cleared after the current service deIs not running. Check power to outdoor unit. Clears Error after current is sensed in both RUNSor run cycle, or after power reset Finished Program Unit Capacity/Size ModeCall for FIRST−STAGE Heat Troubleshooting Heating Sequence of OperationCall for Heat Satisfied Call for SECOND−STAGE Heat2ND Stage Heat Call for Heat Satisfied FIRST−STAGE Heat SECOND−STAGE HeatCall for Cooling Troubleshooting Cooling Sequence of OperationCall for FAN Troubleshooting Continuous Fan Sequence of Operation