Integrated Control Diagnostic Codes (continued)
E 272 | Soft lockout − Exceeded maximum number of recycles. Last recycle due | Check operation of low pressure switch to see if it is |
| to the pressure switch opening. | stuck closed on heat call. Check pressure (inches |
|
| w.c.) of high pressure switch closing on heat call. |
|
| Measure operating pressure (inches w.c.). Inspect |
|
| vent and combustion air inducer for correct opera- |
|
| tion and restriction. Clears when heat call finishes |
|
| successfully. |
|
|
|
E 273 | Soft lockout − Exceeded maximum number of recycles. Last recycle due | Check micro−amperes of flame sensor using control |
| to flame failure. | diagnostics or field−installed mode. Clean or replace |
|
| sensor. Measure voltage of neutral to ground to en- |
|
| sure good unit ground. Clears when heat call finish- |
|
| es successfully. |
|
|
|
E 274 | Soft lockout − Exceeded maximum number of recycles. Last recycle | Shut down system. 1−hour soft lockout. Check firing |
| failed due to the limit circuit opening or limit remained open longer than | rate and air flow. Check for blockage. Clears when |
| 3 minutes. | heat call finishes successfully. |
|
|
|
E 275 | Soft lockout − Flame sensed out of sequence. Flame signal is gone. | Shut off gas. Check for gas valve leak. 1−hour soft |
|
| lockout. Clears when flame has been proven stable. |
|
|
|
E 276 | Watchguard calibration failure. | Unable to perform pressure switch calibration. |
|
| Check vent system and pressure switch wiring con- |
|
| nections. 1−hour soft lockout. Clears when calibra- |
|
| tion has finished successfully. |
|
|
|
E 290 | Ignitor circuit fault − Failed ignitor or triggering circuitry. | Measure resistance of hot surface ignitor. Replace if |
|
| open or not within specifications. 1−hour soft lock- |
|
| out. Clears when flame has been proven stable. |
|
|
|
E 291 | Heat air flow restricted below the minimum. | Check for dirty filter and air flow restriction. Check |
|
| blower performance. 1−hour soft lockout. Cleared |
|
| when heat call finishes successfully. |
|
|
|
E 292 | Indoor blower motor unable to start due to obstructed wheel, seized | Indoor blower motor unable to start (seized bear- |
| bearings. | ing, stuck wheel, etc.). Replace motor or wheel if |
|
| assembly does not operate or meet performance |
|
| standards. 1−hour soft lockout. Clears after circula- |
|
| tor successfully starts. |
|
|
|
E 294 | Combustion air inducer over current. | Check combustion blower bearings, wiring and |
|
| amps. Replace if does not operate or does not meet |
|
| performance standards. Clears after inducer current |
|
| is sensed to be in−range after the ignition following |
|
| the soft lockout or reset. |
|
|
|
E 295 | Indoor blower motor temperature is too high. | Indoor blower motor over temperature (motor |
|
| tripped on internal protector). Check motor bearings |
|
| and amps. Replace if necessary. Cleared after |
|
| blower demand is satisfied. |
|
|
|
E 310 | Discharge error temperature sensor failure. Only shown if shorted or | Compare outdoor sensor resistance to temperature/ |
| out of range. | resistance charts in installation instructions. Re- |
|
| place sensor if necessary. Cleared in Communicat- |
|
| ing mode: 30 seconds after fault recovered. In Non− |
|
| Communicating mode: Cleared after the current |
|
| heat call is completed. |
|
|
|
E 311 | Heat rate reduced to match indoor blower air flow. | Warning Only. Furnace blower in cutback mode due |
|
| to restricted airflow. Reduce firing rate every 60 |
|
| seconds to match available CFM. Check filter and |
|
| duct system. To clear, replace filter if needed or re- |
|
| pair/add duct. 2−stage controls will reduce firing rate |
|
| to 1st stage. Clears when heat call finishes success- |
|
| fully. |
|
|
|