13 Finishing
A. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear- ances as specified. Framing closer than the minimums list- ed must be constructed entirely of noncombustible materi- als (i.e., steel studs, concrete board, etc.) Failure to comply could cause fire.
Combustible Mantels
12 IN. |
MAX. |
10 IN. |
MIN. |
FIREPLACE |
OPENING |
Figure 13.1 Clearances to Mantels or Other Combustibles Above Appliance
Combustible Mantel Legs or Wall Projections
FIREPLACE | 1 IN. MIN. | |
OPENING | ||
| ||
| COMBUSTIBLE | |
| MATERIAL | |
| 6 IN. | |
| MAX. | |
| 7 IN. | |
| 6 IN. MIN. FROM | |
| OPENING | |
| 13 IN. MIN. | |
| FROM OPENING | |
| COMBUSTIBLE WALL OR | |
| MANTEL LEG |
Figure 13.3 Clearances to Combustible Mantel Legs or Wall Projections.
12 IN. MAX.
10 IN.
MIN.
4 IN.
MAX.
FIREPLACE
OPENING
Figure 13.2 Clearances to Mantels or other Non-Combustibles Above Appliance
Non-Combustible Mantel Legs or Wall Projections
FIREPLACE |
|
OPENING | 1 IN. MIN. |
4 IN. MAX. | |
| MANTEL LEG |
| 13 IN. MIN. |
|
Figure 13.4 Clearances to Non-Combustible Mantel Legs or Wall Projections.