Burnham IN10 manual IX. System Start-up, Fill boiler with water, Prepare to check operation

Page 50

IX. System Start-up

WARNING

Completely read, understand and follow all instructions in this manual before attempting start up.

A.Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on boiler when boiler underwent tests specified in

American National Standard for Gas-Fired Low- Pressure Steam and Hot Water Boilers, ANSI Z21.13.

B.Check Main Burners. Main burners must be in slots in rear of burner tray and seated on main burner orifices.

C.Fill boiler with water:

1.Steam: fill to normal water line. See Figure 1.

2.Water: fill heating system to approximately 12 PSI.

Vent air from system.

D.Prepare to check operation.

1.Obtain gas heating value (in Btu per cubic foot) from gas supplier.

2.Adjust limit:

a.Steam: With an L404A1354 - set cut-out pressure (MAIN scale) on the pressure limit for

(2) PSI and differential pressure (DIFF. scale) below (2) PSI.

With an L404A1651 or an L404F1367 - set cut- out pressure (MAIN scale) on the pressure limit for (1) PSI and differential pressure (DIFF.) for

.5 PSI. These pressures may be varied to suit individual requirements of the system. See Figure 18.

b.Water without tankless heater: set at 200°F.

c.Water with tankless heater: set limit at 220°F and operating control to 200°F.

3.Remove front removable panel. See Figure 45.

Figure 46: Gas Valve Pressure Tap,

Honeywell Gas Valves

Figure 47: Gas Valve Pressure Tap,

Robertshaw Gas Valve

4.Connect manometer to gas valve pressure tapping (for IN12 connect to gas valve with pilot control). See Figure 46 or 47.

5.For natural gas fired boiler, temporarily turn off all other gas-fired appliances.

E.Follow Lighting or Operating Instructions.

1.To place boiler in operation. See Figure 48, 49, 50 or 51. Sequence of Operation is outlined with wiring diagrams in Section VIII: Electrical.

2.Electronic Ignition Modules with LED indicators. Table 7 cross-references the ignition module terminal designations to the ignition terminal numbers in the wiring ladder diagrams. The yellow

LED indicates the status of the flame, see Table 8.

The green LED indicates the status of the system, see Table 9. See Figure 52 for LED locations.

Figure 45: Front Door Removal

50

Image 50
Contents Independence 8141049R26-10/08 Price $5.00Page Page Dimensional Drawing Table of Contents Probe L.W.C.O Float L.W.C.O Tankless Heater Pre-Installation Clearance to Combustible Materials Install assembled cast iron sections on base assembly II. Knocked-Down Boiler AssemblyInstall Base-Burner-Manifold Assembly Install Canopy Canopy Gasket InstallationCombustion Chamber Install Blocked Vent Switch with sheet metal screws Intermittent Ignition EI Install Ignition ModuleRemove Crate III. Semi-Pak Boiler AssemblyInstall Trim and Controls Steam Boiler with Probe Low Water CutoffJunction Box and Mounting Bracket Assembly Water BoilerRemove Jacket Front Panel. See Figure IV. Packaged Boiler AssemblyInstall Jacket Front Panel Piping and Trim Page Recommended Water Piping for Circulator Zoned Heating System Recommended Water Piping for Zone Valve Zoned Heating System Recommended Piping for Indirect Water Heater Page Connect boiler gas valve to gas supply system VI. Gas PipingRated Input Fitting Equivalent Lengths Specific Gravity Correction Factors for Natural GasVII. Venting Boiler Equipped With Vent DamperTypical Vent Installation If an Existing Boiler is RemovedWire Vent Damper if used VIII. ElectricalThermostat Heat Anticipator Settings Alliance Indirect Water Heater if usedVent Damper Harness to Limit This page Left Intentionally Blank Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Prepare to check operation IX. System Start-upFill boiler with water Follow Lighting or Operating InstructionsPage Page Page Page Ignition Module Wiring Ladder Diagram Terminal Designation Ignition Module Terminal Cross-ReferenceGreen LED Status Codes OFFPilot Burner Flame, Honeywell Q350 Do not drain below gauge glass Adjust gas input rate to boiler. Natural GasCheck low water cutoff steam only Check LimitAdjust gas input rate to boiler. LP/Propane Input RatePage Page Service Instructions Maintenance of Low Water CutoffBoiler Flueway Cleaning Clean Boiler FluewaysPilot Burner Location Tankless HeaterExcessive Make-Up Water Model No Gallons Per Month YearHoneywell Electronic Ignition Trouble Shooting Guide Honeywell Hot Surface to Pilot Trouble Shooting Guide Avoid Breathing Fiber Particulates and Dust XI. Repair Parts Service RecordSection Assembly Canopy and Draft Hood Canopy/Draft Hood Parts Base Assembly Base TrayBurner Tray 1 Inch Main Burners Manifold and 1 Main Burners Manifold and Main Burners 1 Inch Main Burners Only Intermittent Ignition Only Manifold and 40mm Main BurnersManifold and Main Burners 40MM Main Burners only Volt Continuous Ignition Standing Pilot Natural GasLP Gas, High Altitude 5000-9000 Ft. USA Only LP Gas, High Altitude 2000-5000 Ft. USA OnlyNatural Gas, High Altitude 5000-9000 Ft. USA Only Natural Gas, High Altitude 2000-4500 Ft. Canada OnlyPilot Burner, Honeywell Q350A1321 Pilot Burner, Honeywell Q348A1002 Page Jacket Assembly Jacket Assembly Refer to Figure on Front Top PanelSteam Trim Page Water Trim Quantity This page Left Blank Intentionally Page Transformer Steam and Gravity Water Only Flame Rollout SwitchBlocked Vent Switch Ignition Module Intermittent Ignition OnlyLwco Location Wiring of Typical LwcoXII. Low Water Cut Off Lwco Limited Warranty Limited Warranty