Burnham IN10 manual Piping and Trim

Page 16

V. Piping and Trim

WARNING

Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.

A.Design and install boiler and system piping to prevent oxygen contamination of boiler water. Sources of oxygen contamination are system leaks requiring addition of makeup water, fittings, and oxygen permeable materials in distribution system. Eliminate oxygen contamination by repairing system leaks, repairing fittings, using nonpermeable materials in distribution system, and eliminating open tanks in system, or isolating boiler from system with heat exchanger.

B.Install Safety (Relief) Valve in Tapping "E" (¾ NPT). See Figure 23. Use ¾ NPT x 3" nipple and ¾ NPT elbow provided. Safety (Relief) Valve must be installed with spindle in vertical position.

Figure 23: Trim Installation

WARNING

Safety (relief) valve discharge piping must be piped such that the potential of severe burns is eliminated. DO NOT pipe in any area where freezing could occur. DO NOT install any shut-off valves, plugs or caps. Consult Local Codes for proper discharge piping arrangement.

C.Install Drain Valve in Tapping "F" (2 NPT bushed to ¾ NPT). See Figure 23.

D.Connect supply and return piping to heating system. Maintain minimum ½ inch clearance from combustible materials.

1. For STEAM heating see Figure 24. Consult I=B=R Installation and Piping Guides.

2. For HOT WATER heating with Circulator (forced) see Figure 25 and 25A. Consult I=B=R Installation and Piping Guides.

3. If boiler is used in connection with refrigeration systems, boiler must be installed with chilled medium piped in parallel with heating boiler using appropriate valves to prevent the chilled medium from entering the boiler. See Figure 26. Also consult I=B=R Installation and Piping Guides.

4. If  boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with flow control valves to prevent gravity circulation of boiler water during cooling system operation.

NOTICE

Do not use softened water in steam boilers. Accelerated boiler corrosion will result. Tie in fresh water supply to the boiler upstream of a water softener.

Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler failure. Burnham's Standard Warranty does not cover problems caused by oxygen contamination of boiler water or scale (lime) build-up caused by frequent addition of water.

Before using copper for steam piping, consider the following characteristics of copper piping:

1)high coefficient of thermal expansion can induce mechanical stresses and cause expansion/ contraction noises if not accounted for in the piping system design and installation,

2)high heat transfer rate (heat loss) of uninsulated copper piping must be included in the normal piping and pickup factors used to size the boiler,

3)soldering or brazing pastes and fluxes that end up in the system can cause poor heat transfer, surging, an unsteady water line and wet steam if not thoroughly removed during the boil out procedure and,

4)galvanic corrosion of the adjoining metal may occur due to dissimilar metals in certain water chemistries if dielectric unions are not used.

16

Image 16
Contents Independence 8141049R26-10/08 Price $5.00Page Page Dimensional Drawing Table of Contents Probe L.W.C.O Float L.W.C.O Tankless Heater Pre-Installation Clearance to Combustible Materials Install Base-Burner-Manifold Assembly II. Knocked-Down Boiler AssemblyInstall assembled cast iron sections on base assembly Install Canopy Canopy Gasket InstallationCombustion Chamber Install Blocked Vent Switch with sheet metal screws Intermittent Ignition EI Install Ignition ModuleIII. Semi-Pak Boiler Assembly Install Trim and ControlsRemove Crate Steam Boiler with Probe Low Water CutoffJunction Box and Mounting Bracket Assembly Water BoilerInstall Jacket Front Panel IV. Packaged Boiler AssemblyRemove Jacket Front Panel. See Figure Piping and Trim Page Recommended Water Piping for Circulator Zoned Heating System Recommended Water Piping for Zone Valve Zoned Heating System Recommended Piping for Indirect Water Heater Page Rated Input VI. Gas PipingConnect boiler gas valve to gas supply system Fitting Equivalent Lengths Specific Gravity Correction Factors for Natural GasVII. Venting Boiler Equipped With Vent DamperTypical Vent Installation If an Existing Boiler is RemovedWire Vent Damper if used VIII. ElectricalThermostat Heat Anticipator Settings Alliance Indirect Water Heater if usedVent Damper Harness to Limit This page Left Intentionally Blank Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page IX. System Start-up Fill boiler with waterPrepare to check operation Follow Lighting or Operating InstructionsPage Page Page Page Ignition Module Wiring Ladder Diagram Terminal Designation Ignition Module Terminal Cross-ReferenceGreen LED Status Codes OFFPilot Burner Flame, Honeywell Q350 Adjust gas input rate to boiler. Natural Gas Check low water cutoff steam onlyDo not drain below gauge glass Check LimitAdjust gas input rate to boiler. LP/Propane Input RatePage Page Service Instructions Maintenance of Low Water CutoffBoiler Flueway Cleaning Clean Boiler FluewaysPilot Burner Location Tankless HeaterExcessive Make-Up Water Model No Gallons Per Month YearHoneywell Electronic Ignition Trouble Shooting Guide Honeywell Hot Surface to Pilot Trouble Shooting Guide Avoid Breathing Fiber Particulates and Dust XI. Repair Parts Service RecordSection Assembly Canopy and Draft Hood Canopy/Draft Hood Parts Base Assembly Base TrayBurner Tray 1 Inch Main Burners Manifold and 1 Main Burners Manifold and Main Burners 1 Inch Main Burners Only Manifold and 40mm Main Burners Manifold and Main Burners 40MM Main Burners onlyIntermittent Ignition Only Volt Continuous Ignition Standing Pilot Natural GasLP Gas, High Altitude 2000-5000 Ft. USA Only Natural Gas, High Altitude 5000-9000 Ft. USA OnlyLP Gas, High Altitude 5000-9000 Ft. USA Only Natural Gas, High Altitude 2000-4500 Ft. Canada OnlyPilot Burner, Honeywell Q350A1321 Pilot Burner, Honeywell Q348A1002 Page Jacket Assembly Jacket Assembly Refer to Figure on Front Top PanelSteam Trim Page Water Trim Quantity This page Left Blank Intentionally Page Flame Rollout Switch Blocked Vent SwitchTransformer Steam and Gravity Water Only Ignition Module Intermittent Ignition OnlyXII. Low Water Cut Off Lwco Wiring of Typical LwcoLwco Location Limited Warranty Limited Warranty