X. Service Instructions

DANGER

This boiler uses flammable gas, high voltage electricity, moving parts, and very hot water under high pressure. Assure that all gas and electric power supplies are off and that the water temperature is cool before attempting any disassembly or service.

Assure that all gas valves and electrical disconnect switches are off before attempting any disassembly or service.

Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify, remove or tamper with any control device.

WARNING

This boiler must only be serviced and repaired by skilled and experienced service technicians.

If any controls are replaced, they must be replaced with identical models.

Read, understand and follow all the instructions and warnings contained in all the sections of this manual.

If any electrical wires are disconnected during service, clearly label the wires and assure that the wires are reconnected properly.

Never jump out or bypass any safety or operating control or component of this boiler.

Read, understand and follow all the instructions and warnings contained in ALL of the component instruction manuals.

Assure that all safety and operating controls and components are operating properly before placing the boiler back in service.

A.General. Inspection and service should be conducted annually, except as noted. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Figures 48, 49, 50 or 51.

B.Maintenance of Low Water Cutoff

1.McDonnell & Miller PS-802 or Hydrolevel CycleGard CG400 Probe Style Only.

a.Drain boiler to point below Tapping 'K'. See Figure 2.

b.Disconnect wire(s) connecting control and probe.

c.Remove control from probe.

DANGER

Assure that the boiler is at zero pressure before removing the LWCO probe. Do not rely on the pressure gauge to indicate that the boiler is at zero pressure. Open the safety valve to relieve all internal pressure prior to proceeding. Safety valve discharge piping must be piped such that the potential for burns is eliminated.

d.Unscrew probe from Tapping 'K'. Inspect for scale and sediment buildup.

e.Remove light deposits with damp cloth soaked with vinegar.

f.Remove stubborn deposits using diluted phosphoric acid (H2PO4) solution, 3 parts water to 1 part phosphoric acid. Normal operation will occur with up to 0.2 inch of contamination. If scale or contamination exceeds 0.2 inches, clean probe more frequently.

g.Clean Tapping 'K' to remove old pipe dope and other foreign matter.

h.Apply moderate amount of good quality pipe dope to probe threads, leaving two end threads bare. Install probe in Tapping 'K'. Mount control on probe. Attach wire(s) between control and probe.

i.Fill boiler to normal waterline. Add water treatment as needed.

2.McDonnell & Miller 67 Float Style Only.

a.Weekly (or more frequently if necessary). Open blow-off valve to flush sediment chamber. Follow instructions on Blow-Down Card affixed to Jacket adjacent to low water cutoff.

b.Annually. Dismantle to extent necessary to remove obstructions and insure proper function of working parts.

62

Image 62
Contents Independence 8141049R26-10/08 Price $5.00Page Page Dimensional Drawing Table of Contents Probe L.W.C.O Float L.W.C.O Tankless Heater Pre-Installation Clearance to Combustible Materials Install assembled cast iron sections on base assembly II. Knocked-Down Boiler AssemblyInstall Base-Burner-Manifold Assembly Install Canopy Canopy Gasket InstallationCombustion Chamber Install Blocked Vent Switch with sheet metal screws Intermittent Ignition EI Install Ignition ModuleRemove Crate III. Semi-Pak Boiler AssemblyInstall Trim and Controls Steam Boiler with Probe Low Water CutoffJunction Box and Mounting Bracket Assembly Water BoilerRemove Jacket Front Panel. See Figure IV. Packaged Boiler AssemblyInstall Jacket Front Panel Piping and Trim Page Recommended Water Piping for Circulator Zoned Heating System Recommended Water Piping for Zone Valve Zoned Heating System Recommended Piping for Indirect Water Heater Page Connect boiler gas valve to gas supply system VI. Gas PipingRated Input Fitting Equivalent Lengths Specific Gravity Correction Factors for Natural GasVII. Venting Boiler Equipped With Vent DamperTypical Vent Installation If an Existing Boiler is RemovedWire Vent Damper if used VIII. ElectricalThermostat Heat Anticipator Settings Alliance Indirect Water Heater if usedVent Damper Harness to Limit This page Left Intentionally Blank Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Prepare to check operation IX. System Start-upFill boiler with water Follow Lighting or Operating InstructionsPage Page Page Page Ignition Module Wiring Ladder Diagram Terminal Designation Ignition Module Terminal Cross-ReferenceGreen LED Status Codes OFFPilot Burner Flame, Honeywell Q350 Do not drain below gauge glass Adjust gas input rate to boiler. Natural GasCheck low water cutoff steam only Check LimitAdjust gas input rate to boiler. LP/Propane Input RatePage Page Service Instructions Maintenance of Low Water CutoffBoiler Flueway Cleaning Clean Boiler FluewaysPilot Burner Location Tankless HeaterExcessive Make-Up Water Model No Gallons Per Month YearHoneywell Electronic Ignition Trouble Shooting Guide Honeywell Hot Surface to Pilot Trouble Shooting Guide Avoid Breathing Fiber Particulates and Dust XI. Repair Parts Service RecordSection Assembly Canopy and Draft Hood Canopy/Draft Hood Parts Base Assembly Base TrayBurner Tray 1 Inch Main Burners Manifold and 1 Main Burners Manifold and Main Burners 1 Inch Main Burners Only Intermittent Ignition Only Manifold and 40mm Main BurnersManifold and Main Burners 40MM Main Burners only Volt Continuous Ignition Standing Pilot Natural GasLP Gas, High Altitude 5000-9000 Ft. USA Only LP Gas, High Altitude 2000-5000 Ft. USA OnlyNatural Gas, High Altitude 5000-9000 Ft. USA Only Natural Gas, High Altitude 2000-4500 Ft. Canada OnlyPilot Burner, Honeywell Q350A1321 Pilot Burner, Honeywell Q348A1002 Page Jacket Assembly Jacket Assembly Refer to Figure on Front Top PanelSteam Trim Page Water Trim Quantity This page Left Blank Intentionally Page Transformer Steam and Gravity Water Only Flame Rollout SwitchBlocked Vent Switch Ignition Module Intermittent Ignition OnlyLwco Location Wiring of Typical LwcoXII. Low Water Cut Off Lwco Limited Warranty Limited Warranty