Burnham IN10 manual III. Semi-Pak Boiler Assembly, Remove Crate, Install Trim and Controls

Page 13

III. Semi-Pak Boiler Assembly

WARNING

Installation of this boiler should be undertaken only by trained and skilled personnel from a qualified service agency.

A.Remove Crate

1.Remove all hold down screws and brackets.

2.Slide boiler to rear of skid and carefully remove from crate skid onto 2 inch thick piece of wood and then onto floor. Do not bump boiler jacket against floor.

3.Do not drop boiler at any time.

B.Move Boiler To Permanent Position. Refer to Section I: Pre-Installation.

C.Identify Trim and Controls

FIRST - Determine controls ordered with boiler and refer to appropriate section(s) following:

There are two ordering methods for trim and controls:

1.EZ–Connect Carton (either steam or water) includes trim, controls, wiring and wiring instructions for installation.

2.Separate Trim Carton (steam or water) and Control Carton (steam or water). Only wiring requiring special connections is provided. For wiring requirements, refer to Section VIII: Electrical and appropriate wiring diagram.

D.Install Trim and Controls

Refer to appropriate paragraphs (following) for trim and controls to be installed.

1.Steam Boiler with Probe Low Water Cutoff

a.Install pressure limit control into Tapping "H" with siphon, ¾" x ¼" hex bushing, ¾" elbow and ¾" x 3" nipple provided. See Figures 1 and 2. DO NOT TWIST control. Use wrench on hex fitting located at bottom of control. See

Figure 18.

b.The L404F pressure limit employs a snap action switch and does not require leveling. See Figure 18.

c.Install pressure gauge into Tapping "B" (½ NPT bushed to ¼ NPT). See Figures 1 and 2. Tighten with wrench applied to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE CASE since this may destroy calibration of gauge.

d.Install Low Water Cutoff Probe into Tapping "K"

(¾ NPT). HANDLE PROBE WITH CARE.

e.Attach Low Water cutoff Control to Probe by following instructions packed with control.

f.Install gauge glass fittings into Tappings "C"

(½ NPT). See Figures 1 and 2. Lower fitting has small drain valve.

g.Install gauge glass and protective rods in fittings.

h.Attach "Lowest Permissible Water Level" Plate with sheet metal screws in location indicated in Figure 9.

i.Attach "Frequent Water Addition" Label above the "Lowest Permissible Water Level" Plate.

2.Steam Boiler with McDonnell & Miller 67 Float Low Water Cutoff

a.Install Low Water Cutoff, see instructions packed with control.

i. Screw brass nipples with union halves into Tappings "C" (½ NPT). See Figure 1 and 2.

ii. Attach Gauge Glass/Low Water Cutoff Assembly to union halves.

iii. Affix Blow-Down Card to Jacket Left Side

Panel adjacent to low water cutoff. iv. Provide blow down discharge piping.

b.Attach street elbow siphon and pressure limit control to low water cutoff. DO NOT TWIST control. Use wrench on hex fitting located at bottom of control.

c.The L404F pressure limit employs a snap action switch and does not require leveling. See Figure 18.

d.Install pressure gauge into Tapping "H" (¾ NPT bushed to ¼ NPT). See Figures 1 and 2. Tighten with wrench applied to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE CASE since this may destroy calibration of gauge.

e.Attach "Lowest Permissible Water Level" Plate with sheet metal screws in location indicated in Figure 9.

f.Attach "Frequent Water Addition" Label above the "Lowest Permissible Water Level" Plate.

Figure 18: L404F Pressure Limit Control

13

Image 13
Contents 8141049R26-10/08 Price $5.00 IndependencePage Page Dimensional Drawing Table of Contents Probe L.W.C.O Float L.W.C.O Tankless Heater Pre-Installation Clearance to Combustible Materials Install Base-Burner-Manifold Assembly II. Knocked-Down Boiler AssemblyInstall assembled cast iron sections on base assembly Canopy Gasket Installation Install CanopyCombustion Chamber Intermittent Ignition EI Install Ignition Module Install Blocked Vent Switch with sheet metal screwsInstall Trim and Controls III. Semi-Pak Boiler AssemblyRemove Crate Steam Boiler with Probe Low Water CutoffWater Boiler Junction Box and Mounting Bracket AssemblyInstall Jacket Front Panel IV. Packaged Boiler AssemblyRemove Jacket Front Panel. See Figure Piping and Trim Page Recommended Water Piping for Circulator Zoned Heating System Recommended Water Piping for Zone Valve Zoned Heating System Recommended Piping for Indirect Water Heater Page Rated Input VI. Gas PipingConnect boiler gas valve to gas supply system Specific Gravity Correction Factors for Natural Gas Fitting Equivalent LengthsBoiler Equipped With Vent Damper VII. VentingIf an Existing Boiler is Removed Typical Vent InstallationVIII. Electrical Wire Vent Damper if usedAlliance Indirect Water Heater if used Thermostat Heat Anticipator SettingsVent Damper Harness to Limit This page Left Intentionally Blank Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Fill boiler with water IX. System Start-upPrepare to check operation Follow Lighting or Operating InstructionsPage Page Page Page Ignition Module Terminal Cross-Reference Ignition Module Wiring Ladder Diagram Terminal DesignationOFF Green LED Status CodesPilot Burner Flame, Honeywell Q350 Check low water cutoff steam only Adjust gas input rate to boiler. Natural GasDo not drain below gauge glass Check LimitInput Rate Adjust gas input rate to boiler. LP/PropanePage Page Maintenance of Low Water Cutoff Service InstructionsClean Boiler Flueways Boiler Flueway CleaningTankless Heater Pilot Burner LocationModel No Gallons Per Month Year Excessive Make-Up WaterHoneywell Electronic Ignition Trouble Shooting Guide Honeywell Hot Surface to Pilot Trouble Shooting Guide Avoid Breathing Fiber Particulates and Dust Service Record XI. Repair PartsSection Assembly Canopy and Draft Hood Canopy/Draft Hood Parts Base Tray Base AssemblyBurner Tray 1 Inch Main Burners Manifold and 1 Main Burners Manifold and Main Burners 1 Inch Main Burners Only Manifold and Main Burners 40MM Main Burners only Manifold and 40mm Main BurnersIntermittent Ignition Only Volt Continuous Ignition Standing Pilot Natural GasNatural Gas, High Altitude 5000-9000 Ft. USA Only LP Gas, High Altitude 2000-5000 Ft. USA OnlyLP Gas, High Altitude 5000-9000 Ft. USA Only Natural Gas, High Altitude 2000-4500 Ft. Canada OnlyPilot Burner, Honeywell Q350A1321 Pilot Burner, Honeywell Q348A1002 Page Jacket Assembly Front Top Panel Jacket Assembly Refer to Figure onSteam Trim Page Water Trim Quantity This page Left Blank Intentionally Page Blocked Vent Switch Flame Rollout SwitchTransformer Steam and Gravity Water Only Ignition Module Intermittent Ignition OnlyXII. Low Water Cut Off Lwco Wiring of Typical LwcoLwco Location Limited Warranty Limited Warranty