Burnham IN10 manual Pilot Burner Location, Tankless Heater

Page 64

CAUTION

When necessary to remove burners, be sure to reinstall them in the original manner by engaging the orifice and locating hole in the rear of the burner tray. Burners must be aligned with the burner manifold.

F.Remove Burners for cleaning, changing orifice plugs, or repairs.

1.Turn off electric service to boiler.

2.Turn off gas supply to boiler.

3.Remove jacket front panel.

4.Disconnect pilot tubing at gas valve.

5.Disconnect thermocouple tubing at gas valve (Continuous Ignition only). Disconnect igniter/ sensor cable and ground wire at ignition module

Intermittent Ignition (EI) only. Disconnect flame roll-out switch wires.

6.Remove burner access panel.

7.Mark location of pilot main burner on manifold.

8.Hold burner on throat. Lift slightly to clear orifice.

Pull burner from combustion chamber. See Figure 10. Pilot main burner can only be removed by lifting at 45° angle after adjacent burner to right is removed (1" burners only).

9.Check burners to be sure they do not contain foreign matter or restrictions. Clean burners with a soft bristle brush, blow any dirt out with compressed air or use a vacuum cleaner. See Figure 58.

G.Remove Pilot Assembly for Servicing. Remove machine screw(s) holding pilot burner to pilot bracket, after first removing burner with pilot assembly as described in Step F, number 8 above. To adjust or check spark gap between electrode and hood on Honeywell Q348 intermittent (EI) pilot, see Figure 59.

l. Use a round wire gauge to check spark gap.

2.Spark gap should be 0.125" for optimum performance.

Figure 59: Honeywell Q348 Spark Gap

H.Install Burners by reversing procedures used to remove burner. Main burners must be in slots in rear of burner tray and seated on main burner orifices.

Reconnect pilot gas supply, and thermocouple lead (continuous ignition) or igniter/sensor/ground. See Table 11 for Pilot Burner location.

Table 11: Pilot Burner Location

Boiler Size

Pilot Located Between Burners*

 

 

 

1 inch

40mm

 

 

 

 

 

IN3

1

& 2

1 & 2

 

 

 

 

IN4

2

& 3

2 & 3

 

 

 

 

IN5

3

& 4

2 & 3

 

 

 

 

IN6

4

& 5

3 & 4

 

 

 

 

IN7

6

& 7

3 & 4

 

 

 

 

IN8

7

& 8

4 & 5

 

 

 

 

IN9

8

& 9

4 & 5

 

 

 

IN10

9 & 10

---

 

 

 

IN11

11 & 12

---

 

 

 

 

IN12

12

& 13

---

 

 

 

 

*Burners numbered left to right as viewed from front of boiler.

I.Lubrication. Manufacturers Instruction should be followed on all parts installed on boiler requiring lubrication. This includes:

1.Type of lubricant to be used.

2.Frequency of lubrication.

3.Points to lubricate.

J.Check operation. Follow Steps B through L and Step O from Section IX: System Start-up.

K.Conversion Kits. Follow all instructions provided with kits. Note that Rating Label provided in kit must be used. Apply over or beside original Rating Label allowing the original Serial Number to remain visible.

L.Tankless Heater.

1.Flushing of Heater. All water contains some sediment which settles on inside of coil. Consequently, heater should be periodically backwashed. See Figure 28. Allow water at city pressure to run into hosebib A, through heater, and out hosebib B until discharge is clear. The tees in which the hosebibs are located should be the same size as heater connections to minimize pressure drop.

2.Adjust and maintain mixing valve (tempering valve) in accordance with manufacturer's instructions.

64

Image 64
Contents Independence 8141049R26-10/08 Price $5.00Page Page Dimensional Drawing Table of Contents Probe L.W.C.O Float L.W.C.O Tankless Heater Pre-Installation Clearance to Combustible Materials Install Base-Burner-Manifold Assembly II. Knocked-Down Boiler AssemblyInstall assembled cast iron sections on base assembly Install Canopy Canopy Gasket InstallationCombustion Chamber Install Blocked Vent Switch with sheet metal screws Intermittent Ignition EI Install Ignition ModuleIII. Semi-Pak Boiler Assembly Install Trim and ControlsRemove Crate Steam Boiler with Probe Low Water CutoffJunction Box and Mounting Bracket Assembly Water BoilerInstall Jacket Front Panel IV. Packaged Boiler AssemblyRemove Jacket Front Panel. See Figure Piping and Trim Page Recommended Water Piping for Circulator Zoned Heating System Recommended Water Piping for Zone Valve Zoned Heating System Recommended Piping for Indirect Water Heater Page Rated Input VI. Gas PipingConnect boiler gas valve to gas supply system Fitting Equivalent Lengths Specific Gravity Correction Factors for Natural GasVII. Venting Boiler Equipped With Vent DamperTypical Vent Installation If an Existing Boiler is RemovedWire Vent Damper if used VIII. ElectricalThermostat Heat Anticipator Settings Alliance Indirect Water Heater if usedVent Damper Harness to Limit This page Left Intentionally Blank Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page IX. System Start-up Fill boiler with waterPrepare to check operation Follow Lighting or Operating InstructionsPage Page Page Page Ignition Module Wiring Ladder Diagram Terminal Designation Ignition Module Terminal Cross-ReferenceGreen LED Status Codes OFFPilot Burner Flame, Honeywell Q350 Adjust gas input rate to boiler. Natural Gas Check low water cutoff steam onlyDo not drain below gauge glass Check LimitAdjust gas input rate to boiler. LP/Propane Input RatePage Page Service Instructions Maintenance of Low Water CutoffBoiler Flueway Cleaning Clean Boiler FluewaysPilot Burner Location Tankless HeaterExcessive Make-Up Water Model No Gallons Per Month YearHoneywell Electronic Ignition Trouble Shooting Guide Honeywell Hot Surface to Pilot Trouble Shooting Guide Avoid Breathing Fiber Particulates and Dust XI. Repair Parts Service RecordSection Assembly Canopy and Draft Hood Canopy/Draft Hood Parts Base Assembly Base TrayBurner Tray 1 Inch Main Burners Manifold and 1 Main Burners Manifold and Main Burners 1 Inch Main Burners Only Manifold and 40mm Main Burners Manifold and Main Burners 40MM Main Burners onlyIntermittent Ignition Only Volt Continuous Ignition Standing Pilot Natural GasLP Gas, High Altitude 2000-5000 Ft. USA Only Natural Gas, High Altitude 5000-9000 Ft. USA OnlyLP Gas, High Altitude 5000-9000 Ft. USA Only Natural Gas, High Altitude 2000-4500 Ft. Canada OnlyPilot Burner, Honeywell Q350A1321 Pilot Burner, Honeywell Q348A1002 Page Jacket Assembly Jacket Assembly Refer to Figure on Front Top PanelSteam Trim Page Water Trim Quantity This page Left Blank Intentionally Page Flame Rollout Switch Blocked Vent SwitchTransformer Steam and Gravity Water Only Ignition Module Intermittent Ignition OnlyXII. Low Water Cut Off Lwco Wiring of Typical LwcoLwco Location Limited Warranty Limited Warranty