Burnham IN10 manual Install Blocked Vent Switch with sheet metal screws

Page 12

I.Install Blocked Vent Switch with sheet metal screws.

1.Models IN3 - IN9. Install on rear flange of canopy.

See Figure 15.

Figure 15: Blocked Vent Switch Installation,

IN3 through IN9

2.Models IN10 - IN12. Install on right side of draft hood. See Figure 16. Reset switch must face away from draft hood relief opening.

3.Attach black 18-2 harness to Blocked Vent Switch terminals. Use end with two fully insulated disconnects.

4.Secure harness to right side jacket panel with clamp.

Figure 16: Blocked Vent Switch Installation,

IN10 through IN12

5.Insert harness through ¾ inch hole in right side jacket panel. Secure with strain relief bushing

J.Intermittent Ignition (EI): Install Ignition Module.

1.Mount ignition module mounting bracket to inside of right side panel using (2) #6 x ¾" sheet metal screws provided.

2.Mount ignition module to bracket using (2) #8 x ½" sheet metal screws provided.

3.Install (3) wire harness from ignition module to gas valve as shown in wiring diagrams.

K.Continue to Section III: Semi-Pak Boiler Assembly, Step C.

12

Image 12
Contents Independence 8141049R26-10/08 Price $5.00Page Page Dimensional Drawing Table of Contents Probe L.W.C.O Float L.W.C.O Tankless Heater Pre-Installation Clearance to Combustible Materials II. Knocked-Down Boiler Assembly Install Base-Burner-Manifold AssemblyInstall assembled cast iron sections on base assembly Install Canopy Canopy Gasket InstallationCombustion Chamber Install Blocked Vent Switch with sheet metal screws Intermittent Ignition EI Install Ignition ModuleIII. Semi-Pak Boiler Assembly Install Trim and ControlsRemove Crate Steam Boiler with Probe Low Water CutoffJunction Box and Mounting Bracket Assembly Water BoilerIV. Packaged Boiler Assembly Install Jacket Front PanelRemove Jacket Front Panel. See Figure Piping and Trim Page Recommended Water Piping for Circulator Zoned Heating System Recommended Water Piping for Zone Valve Zoned Heating System Recommended Piping for Indirect Water Heater Page VI. Gas Piping Rated InputConnect boiler gas valve to gas supply system Fitting Equivalent Lengths Specific Gravity Correction Factors for Natural GasVII. Venting Boiler Equipped With Vent DamperTypical Vent Installation If an Existing Boiler is RemovedWire Vent Damper if used VIII. ElectricalThermostat Heat Anticipator Settings Alliance Indirect Water Heater if usedVent Damper Harness to Limit This page Left Intentionally Blank Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page IX. System Start-up Fill boiler with waterPrepare to check operation Follow Lighting or Operating InstructionsPage Page Page Page Ignition Module Wiring Ladder Diagram Terminal Designation Ignition Module Terminal Cross-ReferenceGreen LED Status Codes OFFPilot Burner Flame, Honeywell Q350 Adjust gas input rate to boiler. Natural Gas Check low water cutoff steam onlyDo not drain below gauge glass Check LimitAdjust gas input rate to boiler. LP/Propane Input RatePage Page Service Instructions Maintenance of Low Water CutoffBoiler Flueway Cleaning Clean Boiler FluewaysPilot Burner Location Tankless HeaterExcessive Make-Up Water Model No Gallons Per Month YearHoneywell Electronic Ignition Trouble Shooting Guide Honeywell Hot Surface to Pilot Trouble Shooting Guide Avoid Breathing Fiber Particulates and Dust XI. Repair Parts Service RecordSection Assembly Canopy and Draft Hood Canopy/Draft Hood Parts Base Assembly Base TrayBurner Tray 1 Inch Main Burners Manifold and 1 Main Burners Manifold and Main Burners 1 Inch Main Burners Only Manifold and 40mm Main Burners Manifold and Main Burners 40MM Main Burners onlyIntermittent Ignition Only Volt Continuous Ignition Standing Pilot Natural GasLP Gas, High Altitude 2000-5000 Ft. USA Only Natural Gas, High Altitude 5000-9000 Ft. USA OnlyLP Gas, High Altitude 5000-9000 Ft. USA Only Natural Gas, High Altitude 2000-4500 Ft. Canada OnlyPilot Burner, Honeywell Q350A1321 Pilot Burner, Honeywell Q348A1002 Page Jacket Assembly Jacket Assembly Refer to Figure on Front Top PanelSteam Trim Page Water Trim Quantity This page Left Blank Intentionally Page Flame Rollout Switch Blocked Vent SwitchTransformer Steam and Gravity Water Only Ignition Module Intermittent Ignition OnlyWiring of Typical Lwco XII. Low Water Cut Off LwcoLwco Location Limited Warranty Limited Warranty