Table 9: Green LED Status Codes

Green LED

 

 

 

 

Flash Code

Indicates

Next System Action

Recommended Service Action

(X + Y)a

 

 

 

 

OFF

No “Call for Heat”

N/A

None

 

Flash Fast

Startup - Flame sense

N/A

None

 

calibration

 

 

 

 

 

Heartbeat

Normal operation

N/A

None

 

 

 

 

If system fails to light on next trial

 

5 minute Retry Delay-

 

for ignition check gas supply, pilot

 

Initiate new trial for ignition after retry

burner, spark and flame sense wir-

2

Pilot flame not detected

delay completed.

ing, flame rod contamination or out

 

during trial for ignition

 

 

of position, burner ground connec-

 

 

 

 

 

 

tion.

 

 

 

 

If system fails to light on next trial

 

Recycle- Flame failed

Initiate new trial for ignition. Flash

for ignition check gas supply, pilot

3

code will remain through the ignition

burner, flame sense wiring, flame

during run

 

trial until flame is proved.

rod contamination, burner ground

 

 

 

 

 

connection.

 

 

 

If situation self corrects within 10

Check for pilot flame. Replace gas

 

 

seconds, control returns to normal

 

Flame sensed out of

valve if pilot flame present. If no

 

4

sequence. If flame out of sequence re-

 

sequence

pilot flame, cycle “Call for Heat.”

If

 

 

mains longer than 10 seconds, control

error repeats, replace control.

 

 

 

goes to Flash code 6+4 (see below)

 

 

 

 

 

 

 

 

Check flame sense lead wire for

 

 

Flame sense leakage to

Control remains in wait mode. When

damage or shorting. Check that

 

7

the fault corrects, control resumes nor-

flame rod is in proper position.

 

ground

 

 

mal operation after a one minute delay.

Check flame rod ceramic for cracks,

 

 

 

 

 

damage or tracking.

 

 

 

Control remains in wait mode. When

Check transformer and AC line for

 

Low secondary voltage

proper input voltage to the control.

8

the fault corrects, control resumes nor-

supply- (below 15.5 Vac)

Check with full system load on the

 

 

mal operation after one minute delay.

transformer.

 

 

 

 

 

 

5 minute Retry Delay-

 

Check gas supply, pilot burner, spark

 

Initiate new trial for ignition after retry

and flame sense wiring, flame rod

6 + 2

On every third retry on

delay completed.

contamination or out of position,

 

 

same “Call for Heat”

 

 

 

burner ground connection.

 

 

 

 

 

 

On every 6th flame

5 minute retry delay, then initiate new

Check gas supply, pilot burner, flame

6 + 3

failure during run on the

sense wiring, contamination of flame

trial for ignition.

 

same “Call for Heat”

rod, burner ground connection.

 

 

 

 

 

Flame sensed out of

Control waits until flame is no longer

Check for pilot flame. Replace gas

 

sensed and then goes to soft lockout.

valve if pilot flame present. If no

 

6 + 4

sequence- longer than

 

Flash code continues. Control auto

pilot flame, cycle “Call for Heat.”

If

 

10 seconds

 

resets from soft lockout after one hour.

error repeats, replace control.

 

 

 

 

 

Soft lockout due to error

Control auto resets from soft lockout

Reset by cycling “Call for Heat.”

If

ON

detected during self

after one hour.

error repeats, replace the control

 

 

check sequences

 

 

 

 

 

aFlash Code Descriptions:

 

 

 

-Flash Fast: rapid blinking

-Heartbeat: Constant ½ second bright, ½ second dim cycles.

-A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats the sequence.

-X + Y flash codes signify that the LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2

Hz, remains off for three seconds, and then repeats the sequence.

56

Image 56
Contents Independence 8141049R26-10/08 Price $5.00Page Page Dimensional Drawing Table of Contents Probe L.W.C.O Float L.W.C.O Tankless Heater Pre-Installation Clearance to Combustible Materials Install assembled cast iron sections on base assembly II. Knocked-Down Boiler AssemblyInstall Base-Burner-Manifold Assembly Install Canopy Canopy Gasket InstallationCombustion Chamber Install Blocked Vent Switch with sheet metal screws Intermittent Ignition EI Install Ignition ModuleIII. Semi-Pak Boiler Assembly Install Trim and ControlsRemove Crate Steam Boiler with Probe Low Water CutoffJunction Box and Mounting Bracket Assembly Water BoilerRemove Jacket Front Panel. See Figure IV. Packaged Boiler AssemblyInstall Jacket Front Panel Piping and Trim Page Recommended Water Piping for Circulator Zoned Heating System Recommended Water Piping for Zone Valve Zoned Heating System Recommended Piping for Indirect Water Heater Page Connect boiler gas valve to gas supply system VI. Gas PipingRated Input Fitting Equivalent Lengths Specific Gravity Correction Factors for Natural GasVII. Venting Boiler Equipped With Vent DamperTypical Vent Installation If an Existing Boiler is RemovedWire Vent Damper if used VIII. ElectricalThermostat Heat Anticipator Settings Alliance Indirect Water Heater if usedVent Damper Harness to Limit This page Left Intentionally Blank Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page IX. System Start-up Fill boiler with waterPrepare to check operation Follow Lighting or Operating InstructionsPage Page Page Page Ignition Module Wiring Ladder Diagram Terminal Designation Ignition Module Terminal Cross-ReferenceGreen LED Status Codes OFFPilot Burner Flame, Honeywell Q350 Adjust gas input rate to boiler. Natural Gas Check low water cutoff steam onlyDo not drain below gauge glass Check LimitAdjust gas input rate to boiler. LP/Propane Input RatePage Page Service Instructions Maintenance of Low Water CutoffBoiler Flueway Cleaning Clean Boiler FluewaysPilot Burner Location Tankless HeaterExcessive Make-Up Water Model No Gallons Per Month YearHoneywell Electronic Ignition Trouble Shooting Guide Honeywell Hot Surface to Pilot Trouble Shooting Guide Avoid Breathing Fiber Particulates and Dust XI. Repair Parts Service RecordSection Assembly Canopy and Draft Hood Canopy/Draft Hood Parts Base Assembly Base TrayBurner Tray 1 Inch Main Burners Manifold and 1 Main Burners Manifold and Main Burners 1 Inch Main Burners Only Manifold and 40mm Main Burners Manifold and Main Burners 40MM Main Burners onlyIntermittent Ignition Only Volt Continuous Ignition Standing Pilot Natural GasLP Gas, High Altitude 2000-5000 Ft. USA Only Natural Gas, High Altitude 5000-9000 Ft. USA OnlyLP Gas, High Altitude 5000-9000 Ft. USA Only Natural Gas, High Altitude 2000-4500 Ft. Canada OnlyPilot Burner, Honeywell Q350A1321 Pilot Burner, Honeywell Q348A1002 Page Jacket Assembly Jacket Assembly Refer to Figure on Front Top PanelSteam Trim Page Water Trim Quantity This page Left Blank Intentionally Page Flame Rollout Switch Blocked Vent SwitchTransformer Steam and Gravity Water Only Ignition Module Intermittent Ignition OnlyLwco Location Wiring of Typical LwcoXII. Low Water Cut Off Lwco Limited Warranty Limited Warranty