Bryan Boilers 200, Triple-Flex 150, 250 Combustion AIR Openings, LOUVERS, GRILLES, and Screens

Page 11

interlocked with the boiler to prevent boiler operation if the dampers are closed.

Combustion air openings must never be blocked or obstructed in any manner.

The boiler room must be at a positive or neutral pressure relative to the outdoors. A negative in the boiler room will result in downdraft problems and incomplete combustion due to the lack of air.

WARNING!

Failure to provide an adequate air supply will result in boiler damage and hazardous conditions in the building (fire and asphyxiation hazard as well as equipment damage).

1.6.1COMBUSTION AIR OPENINGS:

The design of combustion air openings MUST comply with local and/or State codes or the authority having jurisdiction. As a minimum, combustion air openings to the boiler room shall be provided as follows:

Note:

Combustion air provided solely from an indoor source is discouraged. No dimension for a round or rectangular opening shall be less than 3”.

Two Permanent Opening Method

One opening starting within 12” of the top of the boiler room and one starting within 12” of the bottom of the boiler room shall be provided. The openings shall be open directly to the outside or ducted directly to the outside.

When directly open to the outside or ducted to the outside by vertical ducts, each opening or duct shall have a minimum fee open area of 1 in2 per 4000 BTU total input rating of the boiler(s) in the room.

If ducted to the outside through horizontal ducts, each opening or duct shall have a minimum free area of 1 in2 per 2000 BTU total input rating of the boiler(s) in the room.

5

Date: 8-4-2010

Revision: 0

Form: 2396

One Permanent Opening Method

One opening commencing within 12” of the top of the room shall be provided. The opening shall be directly to the outside or shall be ducted to the outside with a horizontal or vertical duct.

The opening or duct shall have a minimum free area of:

1 in2 / 3000 BTU /hour of the total input ratting of all appliances (boilers) in the room.

Not less than the sum of the areas of all vent connectors in the room. A “vent connector” is defined as the pipe or duct that connects a fuel burning appliance to a vent or chimney.

Additional area must be provided for other air consuming equipment in the room.

Mechanical Air Supply Systems

The combustion air supply may be provided by a mechanical air supply system. If utilized, the combustion air must be provided from the outside at a minimum rate of 0.35 ft3/min. for every 1000 Btu/hr. input for all appliances located in the space.

If exhaust fans are utilized, additional air shall be provided to replace the exhausted air.

Each boiler and other appliance must be interlocked to prevent operation when the mechanical air supply system is not in operation.

If the combustion air is provided by a buildings mechanical ventilation system, the system shall be sized to provide the specified combustion air in addition to the ventilation air requirements.

1.6.2LOUVERS, GRILLES, AND SCREENS

Louvers and Grilles:

The required size of openings for combustion, ventilation, and dilution air shall e based on the net free area of each opening. Where the free area through a design of louver, grille, or screen is know, it shall be used in calculating the size opening required to provide the free area

Image 11
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form DIM Boiler Foundation Clearances Minimum Clearances to Combustible SurfacesExpansion Tank Connections Safety Relief ValvesBoiler Connections Flow ConnectionCombustion AIR Supply Venting of GAS Train ComponentsElectrical Requirements KW HPLOUVERS, GRILLES, and Screens Combustion AIR OpeningsFlue GAS Venting System Design & InstallationScfm Combustion AIR and Venting Requirements for CanadaBefore Placing Boiler in Operation Marking of GAS VentsTest of GAS Piping Hydrostatic Test of Boilers and SystemStart-Up and Operation Triple-Flex High Efficiency Boilers TRIPLE-FLEX Front View Boiler AssemblyTriple-Flex Rear View TRIPLE-FLEX Rear ViewTRIPLE-FLEX Behind the Cabinet Door TRIPLE-FLEX Left Side ViewTRIPLE-FLEX Right Side View Air Flow Switch TRIPLE-FLEX Left Flue Collector View Pilot Spark Igniter AssemblySola Hydronic Control System POWER-UP ValidationTRIPLE-FLEX Right Flue Collector View HomeKeyboard NavigationStatus Configuration ConfigureSample Configuration Configuration PasswordSafety Verification Configure Verify Change Parameter SettingsSafety Parameter User Confirmation FAULT/ALARM HandlingHome Page Lockout Info BAR Lockouts Clear Lockout OperationFiring Rate Control Operation Firing Rate Field Modulation Configuration Configure ModulationAnnunciation Operation Calibrate Touch Screen Setup Advanced Setup Diagnostics Advanced Setup Setup Advanced SetupSystem Time Setup Advanced Setup Date & Time Outdoor Reset Configure Reset / Reboot DisplayAdvanced Setup Display Reset Safety Verification Configure CH Central Heat Configuration Configure Sensor ConfigurationConfigure CH Central Heat Configuration PID Sound Pressure LevelsSound Pressure Readings Alert Codes Modbus CommunicationDHW RPMODR ILK PII SLOA2D HFSRevision Modulation Test SetupPRE Checks and Setup Boiler CommissioningDRY RUN Pilot AdjustmentIWC Adjusting Boiler Maximum InputAdjusting Boiler Minimum Input Initial Light OFFGAS Meter Readings CFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clockedPII Or L TroubleshootingDate ILK OFF LCI OFFPII OFF ILK on Weak VsnsrThrough Fault CodesAre OEM Specific Fault Codes OFFOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Boiler Water Treatment Draining the SystemDo not Flush the System Through the Boiler Suggested Maintenance Schedule External FIRE-SIDE CleaningDate Revision Form Lead Lag Lead LAG LL Master General Operation General Description of the Lead LAG ApplicationDrop-stage method Drop-stage detection timing LL / Multi-Boiler Field Wiring System Wiring HookupLEAD-LAG Operation Slave Parameters Slave Operation and SetupSlave Mode USE FIRST, Equalize RUNTIME, USE Last Overall Control LL Master Operation and SetupSlave Status Manager Periodic Data Polling MessagesInvalid Response or no Response AbnormalFaultCounter Used to tolerate momentary abnormalityMaster Heat Demand LL CH Demand Switch DISABLE, STAT, Environcom Remote StatLL Modulation Sensor S5 Master Active ServiceMaster Service Status Modulation SensorDemand and Rate Implementation Rate AdjustmentIntegrator Compensation Rate Allocation Method Parallel Commonbase Limited Rate AllocationBase Load Common 0-100% Overflow and Underflow Modulating StageStagerstate = Active Burner DemandStagerstate = Idle ADD-STAGE Condition ADD-STAGE Error Threshold DegreesError Threshold ADD-STAGE Rate Offset -100% to +100%DROP-STAGE Condition DROP-STAGE Error Threshold DegreesLL ALL Boilers OFF Threshold Temperature or None DROP-STAGE Rate Offset -100% to +100%Force Lead Rotation Time Hhmm or None Lead DROP-STAGE on ErrorLAG Selecton Method Sequence ORDER, Measured RUN Time Date Revision Form Slave Read Data Sequencer 1 Minute EventForced Lead Rotation Slave Write Data