Bryan Boilers 250, Triple-Flex 150, & 300, 200 service manual Sound Pressure Levels, Pid

Page 33

2.2.21CENTRAL HEAT

CONFIGURATION

► CONFIGURE

CH - CENTRAL HEAT CONFIGURATION

 

Date:

8-4-2010

 

Revision:

0

 

Form:

2396

 

 

 

Setpoint source

Local

 

 

S2 (J8-6) 4-20mA

Setpoint

Setpoint for normal

 

Central Heat modulation:

 

50 °F to 190 °F

Time of day setpoint

Setpoint when Time Of

 

Day switch is on. 50 °F to

 

190 °F

 

Off hysteresis

Differential above

 

setpoint when boiler is

 

turned off. 2 °F to 5 °F

On hysteresis

Differential

from setpoint

 

when boiler is turned on.

 

2 °F to 30 °F

4 mA water temperature

50 °F to 190 °F

20 mA water temperature

50 °F to 190 °F

Figure 36 Central Heat Configuration (Central Heat Page)

CH enable

Disable or Enable Central

 

Heating Loop

Demand switch

Sensor for Central Heat

 

demand:

 

Sensor only

 

Sensor & STAT terminal

 

Sensor & Remote Stat

 

LCI & Sensor

Outdoor reset

Enabled

 

Disabled

CH has priority over Lead

Yes, No, Cancel

Lag

 

Figure 38 Central Heat Configuration (Modulation Page)

Modulation sensor

Outlet

sensor,

Inlet

 

 

sensor, S5 (J8-11)

 

Modulation Rate Source

Local

 

 

P-gain Gain

 

applied for the P portion

 

 

of the PID equation 0-400

I-gain Gain

 

applied for the I portion of

 

 

the PID equation 0-400

D-gain

 

Gain applied for the D

 

 

portion

of the

PID

 

 

equation 0-400

 

Hysteresis

step time

Time between hysteresis

(0=Disable

hysteresis

step changes: 0-600

stepping)

 

seconds

 

 

2.2.22SOUND PRESSURE LEVELS

Figure 37 Central Heat Configuration (Setpoint Page)

Sound pressure levels were measured at 4-1/2’ above the floor and 3’ from the boiler at the front, rear and two sides. See Table 6 for decibel readings.

 

 

Decibel Readings

 

Model

Front

Rear

Tube

Right

Side

Side

 

 

 

27

Image 33
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Clearances Boiler FoundationMinimum Clearances to Combustible Surfaces DIMBoiler Connections Safety Relief ValvesFlow Connection Expansion Tank ConnectionsElectrical Requirements Venting of GAS Train ComponentsKW HP Combustion AIR SupplyLOUVERS, GRILLES, and Screens Combustion AIR OpeningsFlue GAS Venting System Design & InstallationScfm Combustion AIR and Venting Requirements for CanadaBefore Placing Boiler in Operation Marking of GAS VentsTest of GAS Piping Hydrostatic Test of Boilers and SystemStart-Up and Operation Triple-Flex High Efficiency Boilers TRIPLE-FLEX Front View Boiler AssemblyTriple-Flex Rear View TRIPLE-FLEX Rear ViewTRIPLE-FLEX Left Side View TRIPLE-FLEX Right Side ViewTRIPLE-FLEX Behind the Cabinet Door Air Flow Switch TRIPLE-FLEX Left Flue Collector View Pilot Spark Igniter AssemblyTRIPLE-FLEX Right Flue Collector View POWER-UP ValidationHome Sola Hydronic Control SystemKeyboard NavigationStatus Configuration ConfigureSample Configuration Configuration PasswordSafety Verification Configure Verify Change Parameter SettingsSafety Parameter User Confirmation FAULT/ALARM HandlingHome Page Lockout Info BAR Lockouts Clear Lockout OperationModulation Configuration Configure Modulation Annunciation OperationFiring Rate Control Operation Firing Rate Field Advanced Setup Setup Advanced Setup System Time Setup Advanced Setup Date & TimeCalibrate Touch Screen Setup Advanced Setup Diagnostics Reset / Reboot Display Advanced Setup Display ResetOutdoor Reset Configure Configure Sensor Configuration Configure CH Central Heat ConfigurationSafety Verification Configure CH Central Heat Configuration PID Sound Pressure LevelsSound Pressure Readings Alert Codes Modbus CommunicationDHW RPMODR ILK A2D SLOHFS PIIRevision PRE Checks and Setup Test SetupBoiler Commissioning ModulationDRY RUN Pilot AdjustmentAdjusting Boiler Minimum Input Adjusting Boiler Maximum InputInitial Light OFF IWCGAS Meter Readings CFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clockedPII Or L TroubleshootingDate LCI OFF PII OFFILK OFF ILK on Weak VsnsrAre OEM Specific Fault Codes Fault CodesOFF ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Draining the System Do not Flush the System Through the BoilerBoiler Water Treatment Suggested Maintenance Schedule External FIRE-SIDE CleaningDate Revision Form Lead Lag Lead LAG LL Master General Operation General Description of the Lead LAG ApplicationDrop-stage method Drop-stage detection timing LL / Multi-Boiler Field Wiring System Wiring HookupLEAD-LAG Operation Slave Operation and Setup Slave Mode USE FIRST, Equalize RUNTIME, USE LastSlave Parameters Overall Control LL Master Operation and SetupSlave Status Manager Periodic Data Polling MessagesInvalid Response or no Response AbnormalFaultCounter Used to tolerate momentary abnormalityMaster Heat Demand LL CH Demand Switch DISABLE, STAT, Environcom Remote StatMaster Service Status Master Active ServiceModulation Sensor LL Modulation Sensor S5Demand and Rate Rate Adjustment Integrator CompensationImplementation Rate Allocation Base Load Common 0-100%Rate Allocation Method Parallel Commonbase Limited Overflow and Underflow Modulating StageBurner Demand Stagerstate = IdleStagerstate = Active Error Threshold ADD-STAGE Error Threshold DegreesADD-STAGE Rate Offset -100% to +100% ADD-STAGE ConditionLL ALL Boilers OFF Threshold Temperature or None DROP-STAGE Error Threshold DegreesDROP-STAGE Rate Offset -100% to +100% DROP-STAGE ConditionLead DROP-STAGE on Error LAG Selecton Method Sequence ORDER, Measured RUN TimeForce Lead Rotation Time Hhmm or None Date Revision Form Forced Lead Rotation Sequencer 1 Minute EventSlave Write Data Slave Read Data