Bryan Boilers Triple-Flex 150, 250, & 300 CFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clocked

Page 44

Gas

 

 

 

 

Manifold

4.4

3.6

4.0

2.0

Pressure

 

 

 

 

(IWC)

 

 

 

 

Max RPM

6000-

5100-

3550-

2700-

7000

5500

4200

2850

 

Low Fire

 

 

 

 

Gas

 

 

 

 

Manifold

.3

.3

.2

.2

Pressure

 

 

 

 

(IWC)

 

 

 

 

Min RPM

1200-

1200-

800-

800-

1600

1600

950

950

 

Table 9 Approximate Boiler Settings

2.3.9GAS METER READINGS

Burner input rate can be checked by taking readings from the gas meter. Please note checking the rate with a meter is the only way to be sure of input. Manifold readings are only an approximate value and may vary from unit to unit.

In order to obtain accurate data, there must be no other appliances using gas from the same meter while the burner input rate is being checked.

A stopwatch or a watch with a second hand is required to obtain a meter reading. Clock the amount of time it takes for the smallest dial to complete one revolution in seconds. Use the following formula to obtain the cubic feet per hour throughput of the unit.

CFH = 3600Vc gc

CFH = ft 3 hr −1 of gas Vc = ft clocked

gc = time in seconds

To obtain the Btu per hour throughput of the unit use the following formula.

Q = CFH (hv )

hv = heating value of fuel in Btu ft -3

Date: 8-4-2010

Revision: 0

Form: 2396

cubic feet per hour). Consult the National Fuel Gas Code (ANSI Z223.1, NFPA 54) or the local gas utility for further information. Refer to Table 10 for correction factors for the gas pressure at the meter. Refer to Table 11 for the gas temperature correction factors.

Gas Pressure at Meter

Corr. Factor

14" w.c.

1.034

21" w.c.

1.051

1 psig

1.061

2 psig

1.136

5 psig

1.340

Table 10 Gas Pressure Correction

 

 

Gas Temp. at Meter

Corr. Factor

40 °F

1.04

50 °F

1.02

60 °F

1.0

70 °F

.981

80 °F

.963

90 °F

.945

Table 11 Gas Temperature Correction

To correct for pressure and temperature use the following formula.

Qc = Qt p tt

t p = pressure correction table 2.2A

tt = temperature correction table 2.2B

If the meter is not calibrated for gas temperature and pressure, correction factors must be applied to determine correct rate in SCFH (standard

38

Image 44
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Boiler Foundation ClearancesMinimum Clearances to Combustible Surfaces DIMSafety Relief Valves Boiler ConnectionsFlow Connection Expansion Tank ConnectionsVenting of GAS Train Components Electrical RequirementsKW HP Combustion AIR SupplyCombustion AIR Openings LOUVERS, GRILLES, and ScreensDesign & Installation Flue GAS Venting SystemCombustion AIR and Venting Requirements for Canada ScfmMarking of GAS Vents Before Placing Boiler in OperationHydrostatic Test of Boilers and System Test of GAS PipingStart-Up and Operation Triple-Flex High Efficiency Boilers Boiler Assembly TRIPLE-FLEX Front ViewTRIPLE-FLEX Rear View Triple-Flex Rear ViewTRIPLE-FLEX Behind the Cabinet Door TRIPLE-FLEX Left Side ViewTRIPLE-FLEX Right Side View Air Flow Switch Pilot Spark Igniter Assembly TRIPLE-FLEX Left Flue Collector ViewPOWER-UP Validation TRIPLE-FLEX Right Flue Collector ViewHome Sola Hydronic Control SystemNavigation KeyboardConfiguration Configure StatusConfiguration Password Sample ConfigurationChange Parameter Settings Safety Verification Configure VerifyFAULT/ALARM Handling Safety Parameter User ConfirmationInfo BAR Lockouts Clear Lockout Operation Home Page LockoutFiring Rate Control Operation Firing Rate Field Modulation Configuration Configure ModulationAnnunciation Operation Calibrate Touch Screen Setup Advanced Setup Diagnostics Advanced Setup Setup Advanced SetupSystem Time Setup Advanced Setup Date & Time Outdoor Reset Configure Reset / Reboot DisplayAdvanced Setup Display Reset Safety Verification Configure CH Central Heat Configuration Configure Sensor ConfigurationConfigure CH Central Heat Configuration Sound Pressure Levels PIDSound Pressure Readings Modbus Communication Alert CodesRPM DHWODR ILK SLO A2DHFS PIIRevision Test Setup PRE Checks and SetupBoiler Commissioning ModulationPilot Adjustment DRY RUNAdjusting Boiler Maximum Input Adjusting Boiler Minimum InputInitial Light OFF IWCCFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clocked GAS Meter ReadingsTroubleshooting PII Or LDate ILK OFF LCI OFFPII OFF ILK on Vsnsr WeakFault Codes Are OEM Specific Fault CodesOFF ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Boiler Water Treatment Draining the SystemDo not Flush the System Through the Boiler External FIRE-SIDE Cleaning Suggested Maintenance ScheduleDate Revision Form Lead Lag General Description of the Lead LAG Application Lead LAG LL Master General OperationDrop-stage method Drop-stage detection timing System Wiring Hookup LL / Multi-Boiler Field WiringLEAD-LAG Operation Slave Parameters Slave Operation and SetupSlave Mode USE FIRST, Equalize RUNTIME, USE Last LL Master Operation and Setup Overall ControlPeriodic Data Polling Messages Slave Status ManagerAbnormalFaultCounter Used to tolerate momentary abnormality Invalid Response or no ResponseLL CH Demand Switch DISABLE, STAT, Environcom Remote Stat Master Heat DemandMaster Active Service Master Service StatusModulation Sensor LL Modulation Sensor S5Demand and Rate Implementation Rate AdjustmentIntegrator Compensation Rate Allocation Method Parallel Commonbase Limited Rate AllocationBase Load Common 0-100% Modulating Stage Overflow and UnderflowStagerstate = Active Burner DemandStagerstate = Idle ADD-STAGE Error Threshold Degrees Error ThresholdADD-STAGE Rate Offset -100% to +100% ADD-STAGE ConditionDROP-STAGE Error Threshold Degrees LL ALL Boilers OFF Threshold Temperature or NoneDROP-STAGE Rate Offset -100% to +100% DROP-STAGE ConditionForce Lead Rotation Time Hhmm or None Lead DROP-STAGE on ErrorLAG Selecton Method Sequence ORDER, Measured RUN Time Date Revision Form Sequencer 1 Minute Event Forced Lead RotationSlave Write Data Slave Read Data