Bryan Boilers Triple-Flex 150, 250, & 300, 200 service manual Blower, Dhw

Page 52

 

 

 

 

 

 

 

Date:

8-4-2010

 

 

 

 

 

 

 

Revision:

 

0

 

 

 

 

 

 

 

Form:

 

2396

 

 

 

 

 

 

 

 

 

Code

Description

 

 

 

Recommended Troubleshooting of Lockout Codes

 

 

Code

165

Block intake OFF

 

1. Check wiring and correct any errors.

 

 

L

 

 

 

 

 

 

 

2. Inspect the Block Intake Switch to make sure it is working

 

 

 

 

 

 

 

 

 

correctly.

 

 

 

 

 

 

 

 

 

 

3. Reset and sequence the module.

 

 

 

 

 

 

 

 

 

 

4. During Standby and Purge, measure the voltage across the

 

 

 

 

 

 

 

 

 

switch. Supply voltage should be present. If not, the Block Intake

 

 

 

 

 

 

 

 

 

Switch is defective and needs replacing.

 

 

 

 

 

 

 

 

 

 

5. If the fault persists, replace the relay module.

 

 

 

166-

RESERVED

 

 

 

 

 

 

 

171

 

 

 

 

 

 

 

 

 

 

172

Main

 

relay

Internal Fault.

 

 

L

 

feedback incorrect

1. Reset Module.

 

 

 

173

Pilot relay feedback

2. If fault repeats, replace module.

 

 

L

 

incorrect

 

 

 

 

 

 

 

174

Safety

 

relay

 

 

 

L

 

feedback incorrect

 

 

 

 

175

Safety relay open

 

 

 

 

L

176

Main

relay

ON

at

 

 

 

L

 

safe start check

 

 

 

 

 

177

Pilot

relay

ON

at

 

 

 

L

 

safe start check

 

 

 

 

 

178

Safety relay ON at

 

 

 

L

 

safe start check

 

 

 

 

 

179-

RESERVED

 

 

 

 

 

 

 

183

 

 

 

 

 

 

 

 

 

 

184

Invalid

BLOWER

/

1. Return to Configuration mode and recheck selected

 

L

 

HSI output setting

 

parameters, reverify and reset module.

 

 

 

185

Invalid Delta T limit

2. If fault repeats, verify electrical grounding.

 

 

L

 

enable setting

 

 

3. If fault repeats, replace module.

 

 

 

186

Invalid Delta T limit

 

 

 

L

 

response setting

 

 

 

 

 

187

Invalid

DHW

high

 

 

 

L

 

limit enable setting

 

 

 

 

188

Invalid

DHW

high

 

 

 

L

 

limit

 

response

 

 

 

 

 

setting

 

 

 

 

 

 

 

189

Invalid

 

Flame

 

 

 

L

 

sensor type setting

 

 

 

 

190

Invalid

interrupted

 

 

 

L

 

air

switch

enable

 

 

 

 

 

setting

 

 

 

 

 

 

 

191

Invalid

interrupted

 

 

 

L

 

air

switch

 

start

 

 

 

 

 

check

 

enable

 

 

 

 

 

setting

 

 

 

 

 

 

 

192

Invalid

igniter

on

 

 

 

L

 

during setting

 

 

 

 

 

 

193

Invalid ignite failure

 

 

 

L

 

delay setting

 

 

 

 

 

 

 

194

Invalid ignite failure

 

 

 

L

 

response setting

 

 

 

 

 

195

Invalid ignite failure

 

 

 

L

 

retries setting

 

 

 

 

 

 

 

 

 

 

 

 

 

46

 

 

 

Image 52
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Boiler Foundation ClearancesMinimum Clearances to Combustible Surfaces DIMSafety Relief Valves Boiler ConnectionsFlow Connection Expansion Tank ConnectionsVenting of GAS Train Components Electrical RequirementsKW HP Combustion AIR SupplyCombustion AIR Openings LOUVERS, GRILLES, and ScreensDesign & Installation Flue GAS Venting SystemCombustion AIR and Venting Requirements for Canada ScfmMarking of GAS Vents Before Placing Boiler in OperationHydrostatic Test of Boilers and System Test of GAS PipingStart-Up and Operation Triple-Flex High Efficiency Boilers Boiler Assembly TRIPLE-FLEX Front ViewTRIPLE-FLEX Rear View Triple-Flex Rear ViewTRIPLE-FLEX Right Side View TRIPLE-FLEX Left Side ViewTRIPLE-FLEX Behind the Cabinet Door Air Flow Switch Pilot Spark Igniter Assembly TRIPLE-FLEX Left Flue Collector ViewPOWER-UP Validation TRIPLE-FLEX Right Flue Collector ViewHome Sola Hydronic Control SystemNavigation KeyboardConfiguration Configure StatusConfiguration Password Sample ConfigurationChange Parameter Settings Safety Verification Configure VerifyFAULT/ALARM Handling Safety Parameter User ConfirmationInfo BAR Lockouts Clear Lockout Operation Home Page LockoutAnnunciation Operation Modulation Configuration Configure ModulationFiring Rate Control Operation Firing Rate Field System Time Setup Advanced Setup Date & Time Advanced Setup Setup Advanced SetupCalibrate Touch Screen Setup Advanced Setup Diagnostics Advanced Setup Display Reset Reset / Reboot DisplayOutdoor Reset Configure Configure CH Central Heat Configuration Configure Sensor ConfigurationSafety Verification Configure CH Central Heat Configuration Sound Pressure Levels PIDSound Pressure Readings Modbus Communication Alert CodesRPM DHWODR ILK SLO A2DHFS PIIRevision Test Setup PRE Checks and SetupBoiler Commissioning ModulationPilot Adjustment DRY RUNAdjusting Boiler Maximum Input Adjusting Boiler Minimum InputInitial Light OFF IWCCFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clocked GAS Meter ReadingsTroubleshooting PII Or LDate PII OFF LCI OFFILK OFF ILK on Vsnsr WeakFault Codes Are OEM Specific Fault CodesOFF ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Do not Flush the System Through the Boiler Draining the SystemBoiler Water Treatment External FIRE-SIDE Cleaning Suggested Maintenance ScheduleDate Revision Form Lead Lag General Description of the Lead LAG Application Lead LAG LL Master General OperationDrop-stage method Drop-stage detection timing System Wiring Hookup LL / Multi-Boiler Field WiringLEAD-LAG Operation Slave Mode USE FIRST, Equalize RUNTIME, USE Last Slave Operation and SetupSlave Parameters LL Master Operation and Setup Overall ControlPeriodic Data Polling Messages Slave Status ManagerAbnormalFaultCounter Used to tolerate momentary abnormality Invalid Response or no ResponseLL CH Demand Switch DISABLE, STAT, Environcom Remote Stat Master Heat DemandMaster Active Service Master Service StatusModulation Sensor LL Modulation Sensor S5Demand and Rate Integrator Compensation Rate AdjustmentImplementation Base Load Common 0-100% Rate AllocationRate Allocation Method Parallel Commonbase Limited Modulating Stage Overflow and UnderflowStagerstate = Idle Burner DemandStagerstate = Active ADD-STAGE Error Threshold Degrees Error ThresholdADD-STAGE Rate Offset -100% to +100% ADD-STAGE ConditionDROP-STAGE Error Threshold Degrees LL ALL Boilers OFF Threshold Temperature or NoneDROP-STAGE Rate Offset -100% to +100% DROP-STAGE ConditionLAG Selecton Method Sequence ORDER, Measured RUN Time Lead DROP-STAGE on ErrorForce Lead Rotation Time Hhmm or None Date Revision Form Sequencer 1 Minute Event Forced Lead RotationSlave Write Data Slave Read Data