Code | Description |
|
|
| Recommended Troubleshooting of Lockout Codes |
|
| Code | ||
165 | Block intake OFF |
| 1. Check wiring and correct any errors. |
|
| L | ||||
|
|
|
|
|
|
| 2. Inspect the Block Intake Switch to make sure it is working |
|
| |
|
|
|
|
|
|
| correctly. |
|
|
|
|
|
|
|
|
|
| 3. Reset and sequence the module. |
|
|
|
|
|
|
|
|
|
| 4. During Standby and Purge, measure the voltage across the |
|
| |
|
|
|
|
|
|
| switch. Supply voltage should be present. If not, the Block Intake |
|
| |
|
|
|
|
|
|
| Switch is defective and needs replacing. |
|
|
|
|
|
|
|
|
|
| 5. If the fault persists, replace the relay module. |
|
|
|
166- | RESERVED |
|
|
|
|
|
|
| ||
171 |
|
|
|
|
|
|
|
|
|
|
172 | Main |
| relay | Internal Fault. |
|
| L | |||
| feedback incorrect | 1. Reset Module. |
|
|
| |||||
173 | Pilot relay feedback | 2. If fault repeats, replace module. |
|
| L | |||||
| incorrect |
|
|
|
|
|
|
| ||
174 | Safety |
| relay |
|
|
| L | |||
| feedback incorrect |
|
|
|
| |||||
175 | Safety relay open |
|
|
|
| L | ||||
176 | Main | relay | ON | at |
|
|
| L | ||
| safe start check |
|
|
|
|
| ||||
177 | Pilot | relay | ON | at |
|
|
| L | ||
| safe start check |
|
|
|
|
| ||||
178 | Safety relay ON at |
|
|
| L | |||||
| safe start check |
|
|
|
|
| ||||
179- | RESERVED |
|
|
|
|
|
|
| ||
183 |
|
|
|
|
|
|
|
|
|
|
184 | Invalid | BLOWER | / | 1. Return to Configuration mode and recheck selected |
| L | ||||
| HSI output setting |
| parameters, reverify and reset module. |
|
|
| ||||
185 | Invalid Delta T limit | 2. If fault repeats, verify electrical grounding. |
|
| L | |||||
| enable setting |
|
| 3. If fault repeats, replace module. |
|
|
| |||
186 | Invalid Delta T limit |
|
|
| L | |||||
| response setting |
|
|
|
|
| ||||
187 | Invalid | DHW | high |
|
|
| L | |||
| limit enable setting |
|
|
|
| |||||
188 | Invalid | DHW | high |
|
|
| L | |||
| limit |
| response |
|
|
|
| |||
| setting |
|
|
|
|
|
|
| ||
189 | Invalid |
| Flame |
|
|
| L | |||
| sensor type setting |
|
|
|
| |||||
190 | Invalid | interrupted |
|
|
| L | ||||
| air | switch | enable |
|
|
|
| |||
| setting |
|
|
|
|
|
|
| ||
191 | Invalid | interrupted |
|
|
| L | ||||
| air | switch |
| start |
|
|
|
| ||
| check |
| enable |
|
|
|
| |||
| setting |
|
|
|
|
|
|
| ||
192 | Invalid | igniter | on |
|
|
| L | |||
| during setting |
|
|
|
|
|
| |||
193 | Invalid ignite failure |
|
|
| L | |||||
| delay setting |
|
|
|
|
|
|
| ||
194 | Invalid ignite failure |
|
|
| L | |||||
| response setting |
|
|
|
|
| ||||
195 | Invalid ignite failure |
|
|
| L | |||||
| retries setting |
|
|
|
|
|
| |||
|
|
|
|
|
|
| 46 |
|
|
|