button turns red (Figure 22). On all other pages and when the user is looking at a different boiler, a notification dialog box displays indicating which boiler just locked out.
Figure 21 Home Page Lockout
Figure 22 Status Page Lockout
Selecting the info bar will display the history dialog. If none of the buttons are selected the dialog box closes after 30 seconds.
Date: 8-4-2010
Revision: 0
Form: 2396
Figure 23 History Dialog
The lockout history can be displayed for each boiler. The state information about each lockout is displayed along with the date/time that the lockout occurred.
Figure 24 Lockout History Page
Use the following to clear a lockout and reset the boiler.
►
► INFO BAR ► LOCKOUTS ►
CLEAR LOCKOUT
2.2.11OPERATION PAGE
►
►OPERATION
Figure 25 Operation Page
The operation page displays the boiler running operation, including set point and firing rate values expressed in rpm. From this page the user can change set points, manually control the boiler’s firing rate, manually turn pumps on, view
22