Bryan Boilers 200, Triple-Flex 150, 250 Initial Light OFF, Adjusting Boiler Maximum Input, Iwc

Page 43

WARNING:

During pilot adjustment leave the manual main gas cock (Figure 7 item 4) closed.

NOTE:

Pilot gas pressures in excess of the recommended will lead to the formation of carbon hairs that will ground out the pilot igniter causing a safety shutdown.

2.3.6INITIAL LIGHT OFF

Open the manual main gas cock (Figure 7 item 4). Clear the lockout fault (paragraph 2.2.10) and allow the burner to cycle and attempt to light off. If the main flame fails to light, the low fire displacement of the pressure regulating actuator (Figure 7 item 2) may need to be increased.

WARNING:

Do not adjust the low fire displacement more than 1/4 to 1/2 turn for each main flame-establishing period.

The boiler will light off at approximately 1.5 times the minimum firing rate rpm. The boiler will hold in this position for no less than 5 minutes to establish a stable flame before releasing the boiler to full modulation. Observe combustion readings and make small adjustments to the low fire displacement of the pressure regulating actuator (Figure 7 item 2) when the O2 is not within 6% to 10%. Allow sufficient time for combustion to stabilize after each ¼ to ½ turn of the low fire displacement (Figure 7 item 2).

2.3.7ADJUSTING BOILER MAXIMUM

INPUT

After the flame stabilization period increase the firing rate in 500 rpm increments until the maximum modulation rate (paragraph 2.2.13) is reached. For each 500 rpm increment observe combustion readings and make adjustments to the gas limiting orifice (Figure 7 item 26) if the O2 is not within 6% to 10%. Final adjustments

37

Date: 8-4-2010

Revision: 0

Form: 2396

for NOx, O2, and CO should be made at the maximum firing rate. No further adjustments are required of the gas limiting orifice valve. Return to the minimum low fire rate (paragraph 2.2.13) in increments of 500 rpm. For each increment verify combustion readings. Refer to trouble shooting (paragraph 0) for further help.

NOTE:

Use rpm values that fall between the rpm values used going to high fire. This will give more points to verify on the modulation curve.

2.3.8ADJUSTING BOILER MINIMUM

INPUT

NOTE:

The boiler maximum input must be adjusted before final adjustments can be made for minimum input.

Decrease the boiler firing rate to the minimum modulation rate (paragraph 2.2.13). Adjust the O2 level to obtain Nox levels desired by adjusting the low fire displacement on the gas pressure regulating actuator to obtain appropriate NOx, O2, and CO levels. Allow sufficient time for combustion to stabilize after each ¼ to ½ turn of the low fire displacement (Figure 7 item 2).

WARNING:

O2 levels below 6% will overheat the metal fiber burner and cause the fuel / air mixture to ignite inside the burner. An internal temperature fuse is provided to open when the internal burner temperature reaches 425 oF.

 

 

Boiler Model

 

 

 

 

TF300

TF250

TF200

TF150

 

 

 

 

 

 

Pilot

Gas

3.5 - 4

3.5 - 4

3.5 - 4

3.5 - 4

Pressure

(IWC)

 

 

 

 

 

Light

Off

1800

1800

1200

1200

RPM

 

 

 

 

 

 

High Fire

 

 

 

 

Image 43
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form DIM Boiler FoundationClearances Minimum Clearances to Combustible SurfacesExpansion Tank Connections Safety Relief ValvesBoiler Connections Flow ConnectionCombustion AIR Supply Venting of GAS Train ComponentsElectrical Requirements KW HPLOUVERS, GRILLES, and Screens Combustion AIR OpeningsFlue GAS Venting System Design & InstallationScfm Combustion AIR and Venting Requirements for CanadaBefore Placing Boiler in Operation Marking of GAS VentsTest of GAS Piping Hydrostatic Test of Boilers and SystemStart-Up and Operation Triple-Flex High Efficiency Boilers TRIPLE-FLEX Front View Boiler AssemblyTriple-Flex Rear View TRIPLE-FLEX Rear ViewTRIPLE-FLEX Right Side View TRIPLE-FLEX Left Side ViewTRIPLE-FLEX Behind the Cabinet Door Air Flow Switch TRIPLE-FLEX Left Flue Collector View Pilot Spark Igniter AssemblySola Hydronic Control System POWER-UP ValidationTRIPLE-FLEX Right Flue Collector View HomeKeyboard NavigationStatus Configuration ConfigureSample Configuration Configuration PasswordSafety Verification Configure Verify Change Parameter SettingsSafety Parameter User Confirmation FAULT/ALARM HandlingHome Page Lockout Info BAR Lockouts Clear Lockout OperationAnnunciation Operation Modulation Configuration Configure ModulationFiring Rate Control Operation Firing Rate Field System Time Setup Advanced Setup Date & Time Advanced Setup Setup Advanced SetupCalibrate Touch Screen Setup Advanced Setup Diagnostics Advanced Setup Display Reset Reset / Reboot DisplayOutdoor Reset Configure Configure CH Central Heat Configuration Configure Sensor ConfigurationSafety Verification Configure CH Central Heat Configuration PID Sound Pressure LevelsSound Pressure Readings Alert Codes Modbus CommunicationDHW RPMODR ILK PII SLOA2D HFSRevision Modulation Test SetupPRE Checks and Setup Boiler CommissioningDRY RUN Pilot AdjustmentIWC Adjusting Boiler Maximum InputAdjusting Boiler Minimum Input Initial Light OFFGAS Meter Readings CFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clockedPII Or L TroubleshootingDate PII OFF LCI OFFILK OFF ILK on Weak VsnsrThrough Fault CodesAre OEM Specific Fault Codes OFFOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Do not Flush the System Through the Boiler Draining the SystemBoiler Water Treatment Suggested Maintenance Schedule External FIRE-SIDE CleaningDate Revision Form Lead Lag Lead LAG LL Master General Operation General Description of the Lead LAG ApplicationDrop-stage method Drop-stage detection timing LL / Multi-Boiler Field Wiring System Wiring HookupLEAD-LAG Operation Slave Mode USE FIRST, Equalize RUNTIME, USE Last Slave Operation and SetupSlave Parameters Overall Control LL Master Operation and SetupSlave Status Manager Periodic Data Polling MessagesInvalid Response or no Response AbnormalFaultCounter Used to tolerate momentary abnormalityMaster Heat Demand LL CH Demand Switch DISABLE, STAT, Environcom Remote StatLL Modulation Sensor S5 Master Active ServiceMaster Service Status Modulation SensorDemand and Rate Integrator Compensation Rate AdjustmentImplementation Base Load Common 0-100% Rate AllocationRate Allocation Method Parallel Commonbase Limited Overflow and Underflow Modulating StageStagerstate = Idle Burner DemandStagerstate = Active ADD-STAGE Condition ADD-STAGE Error Threshold DegreesError Threshold ADD-STAGE Rate Offset -100% to +100%DROP-STAGE Condition DROP-STAGE Error Threshold DegreesLL ALL Boilers OFF Threshold Temperature or None DROP-STAGE Rate Offset -100% to +100%LAG Selecton Method Sequence ORDER, Measured RUN Time Lead DROP-STAGE on ErrorForce Lead Rotation Time Hhmm or None Date Revision Form Slave Read Data Sequencer 1 Minute EventForced Lead Rotation Slave Write Data