Bryan Boilers 250, Triple-Flex 150, & 300, 200 service manual Odr

Page 37

129

Slow start ramp setting of zero will

result in no modulation rate change

 

130

RESERVED

 

131

CH demand source was invalid

132

CH P-gain was invalid

 

133

CH I-gain was invalid

 

134

CH D-gain was invalid

 

135

CH OFF hysteresis was invalid

 

136

CH ON hysteresis was invalid

 

137

CH sensor type was invalid

 

138

CH hysteresis step time was invalid

139

CH remote control parameter was

invalid

 

 

 

140

CH ODR not allowed with

remote

control

 

 

 

141-

RESERVED

 

145

 

 

 

146

CH control was suspended

due to

fault

 

 

 

147

CH header temperature was invalid

148

CH outlet temperature was invalid

149

CH steam pressure was invalid

150-

RESERVED

 

156

 

 

 

157

DHW demand source was invalid

158

DHW P-gain was invalid

 

159

DHW I-gain was invalid

 

160

DHW D-gain was invalid

 

161

DHW OFF hysteresis was invalid

162

DHW ON hysteresis was invalid

163

DHW hysteresis step time was invalid

164

DHW sensor type was invalid

 

165

Inlet sensor type was invalid for DHW

166

Outlet sensor type was invalid for

DHW

 

 

 

167-

RESERVED

 

170

 

 

 

171

DHW control was suspended due to

fault

 

 

 

172

DHW temperature was invalid

 

173

DHW inlet temperature was invalid

174

DHW outlet temperature was invalid

175-

RESERVED

 

182

 

 

 

183

Lead Lag P-gain was invalid

 

184

Lead Lag I-gain was invalid

 

185

Lead Lag D-gain was invalid

 

186

Lead Lag OFF hysteresis was invalid

187

Lead Lag ON hysteresis was invalid

188

Lead Lag slave enable was invalid

189

Lead Lag hysteresis step time was

invalid

 

 

 

190-

RESERVED

 

203

 

 

 

 

 

 

 

Date:

8-4-2010

 

 

 

 

Revision:

0

 

 

 

 

Form:

 

2396

 

 

204

Lead Lag master was suspended due

to fault

 

 

 

 

 

 

 

 

 

205

Lead Lag slave was suspended due

to fault

 

 

 

 

 

 

 

 

 

206

Lead

Lag header

temperature was

invalid

 

 

 

 

 

 

 

 

 

 

 

207

Lead Lag was suspended due to no

enabled Program Module installed

 

208

Lead Lag slave session has timed out

209-

RESERVED

 

 

 

 

221

 

 

 

 

 

 

 

 

 

 

 

222

CH frost protection temperature was

invalid

 

 

 

 

 

 

 

 

 

 

 

223

CH frost protection inlet temperature

was invalid

 

 

 

 

 

 

 

 

 

224

DHW

frost

protection

temperature

was invalid

 

 

 

 

 

 

 

 

 

225-

RESERVED

 

 

 

 

230

 

 

 

 

 

 

 

 

 

 

 

231

LL setpoint was invalid

 

 

232

LL time of day setpoint was invalid

233

LL outdoor temperature was invalid

234

LL

ODR time of

day

setpoint was

invalid

 

 

 

 

 

 

 

 

 

 

 

235

LL

ODR

time

of

day

setpoint

exceeded normal setpoint

 

 

 

236

LL max outdoor setpoint was invalid

237

LL min outdoor setpoint was invalid

238

LL min water setpoint was invalid

239

LL

outdoor

temperature range was

too small (minimum 12 C / 22 F)

 

240

LL water temperature range was too

small (minimum 12 C / 22 F)

 

 

 

241-

RESERVED

 

 

 

 

245

 

 

 

 

 

 

 

 

 

 

 

246

CH setpoint was invalid

 

 

247

CH time of day setpoint was invalid

248

CH outdoor temperature was invalid

249

CH

ODR time of

day

setpoint was

invalid

 

 

 

 

 

 

 

 

 

 

 

250

CH

ODR

time

of

day

setpoint

exceeds normal setpoint

 

 

 

251

CH max outdoor setpoint was invalid

252

CH min outdoor setpoint was invalid

253

CH min water setpoint was invalid

254

CH outdoor temperature range was

too small (minimum 12 C / 22 F)

 

255

CH water temperature range was too

small (minimum 12 C / 22 F)

 

 

 

256-

RESERVED

 

 

 

 

260

 

 

 

 

 

 

 

261

DHW setpoint was invalid

 

262

DHW time of day setpoint was invalid

31

Image 37
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Clearances Boiler FoundationMinimum Clearances to Combustible Surfaces DIMBoiler Connections Safety Relief ValvesFlow Connection Expansion Tank ConnectionsElectrical Requirements Venting of GAS Train ComponentsKW HP Combustion AIR SupplyLOUVERS, GRILLES, and Screens Combustion AIR OpeningsFlue GAS Venting System Design & InstallationScfm Combustion AIR and Venting Requirements for CanadaBefore Placing Boiler in Operation Marking of GAS VentsTest of GAS Piping Hydrostatic Test of Boilers and SystemStart-Up and Operation Triple-Flex High Efficiency Boilers TRIPLE-FLEX Front View Boiler AssemblyTriple-Flex Rear View TRIPLE-FLEX Rear ViewTRIPLE-FLEX Right Side View TRIPLE-FLEX Left Side ViewTRIPLE-FLEX Behind the Cabinet Door Air Flow Switch TRIPLE-FLEX Left Flue Collector View Pilot Spark Igniter AssemblyTRIPLE-FLEX Right Flue Collector View POWER-UP ValidationHome Sola Hydronic Control SystemKeyboard NavigationStatus Configuration ConfigureSample Configuration Configuration PasswordSafety Verification Configure Verify Change Parameter SettingsSafety Parameter User Confirmation FAULT/ALARM HandlingHome Page Lockout Info BAR Lockouts Clear Lockout OperationAnnunciation Operation Modulation Configuration Configure ModulationFiring Rate Control Operation Firing Rate Field System Time Setup Advanced Setup Date & Time Advanced Setup Setup Advanced SetupCalibrate Touch Screen Setup Advanced Setup Diagnostics Advanced Setup Display Reset Reset / Reboot DisplayOutdoor Reset Configure Configure CH Central Heat Configuration Configure Sensor ConfigurationSafety Verification Configure CH Central Heat Configuration PID Sound Pressure LevelsSound Pressure Readings Alert Codes Modbus CommunicationDHW RPMODR ILK A2D SLOHFS PIIRevision PRE Checks and Setup Test SetupBoiler Commissioning ModulationDRY RUN Pilot AdjustmentAdjusting Boiler Minimum Input Adjusting Boiler Maximum InputInitial Light OFF IWCGAS Meter Readings CFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clockedPII Or L TroubleshootingDate PII OFF LCI OFFILK OFF ILK on Weak VsnsrAre OEM Specific Fault Codes Fault CodesOFF ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Do not Flush the System Through the Boiler Draining the SystemBoiler Water Treatment Suggested Maintenance Schedule External FIRE-SIDE CleaningDate Revision Form Lead Lag Lead LAG LL Master General Operation General Description of the Lead LAG ApplicationDrop-stage method Drop-stage detection timing LL / Multi-Boiler Field Wiring System Wiring HookupLEAD-LAG Operation Slave Mode USE FIRST, Equalize RUNTIME, USE Last Slave Operation and SetupSlave Parameters Overall Control LL Master Operation and SetupSlave Status Manager Periodic Data Polling MessagesInvalid Response or no Response AbnormalFaultCounter Used to tolerate momentary abnormalityMaster Heat Demand LL CH Demand Switch DISABLE, STAT, Environcom Remote StatMaster Service Status Master Active ServiceModulation Sensor LL Modulation Sensor S5Demand and Rate Integrator Compensation Rate AdjustmentImplementation Base Load Common 0-100% Rate AllocationRate Allocation Method Parallel Commonbase Limited Overflow and Underflow Modulating StageStagerstate = Idle Burner DemandStagerstate = Active Error Threshold ADD-STAGE Error Threshold DegreesADD-STAGE Rate Offset -100% to +100% ADD-STAGE ConditionLL ALL Boilers OFF Threshold Temperature or None DROP-STAGE Error Threshold DegreesDROP-STAGE Rate Offset -100% to +100% DROP-STAGE ConditionLAG Selecton Method Sequence ORDER, Measured RUN Time Lead DROP-STAGE on ErrorForce Lead Rotation Time Hhmm or None Date Revision Form Forced Lead Rotation Sequencer 1 Minute EventSlave Write Data Slave Read Data