Bryan Boilers 250, Triple-Flex 150, & 300, 200 service manual Vsnsr, Weak

Page 49

 

 

 

 

 

Date:

8-4-2010

 

 

 

 

 

Revision:

 

0

 

 

 

 

 

Form:

2396

 

 

 

 

 

 

Code

Description

 

Recommended Troubleshooting of Lockout Codes

 

Code

 

 

 

 

2.

Replace the stack sensor.

 

 

 

 

 

 

3.

If previous steps are correct and fault persists, replace the

 

 

 

 

 

module

 

 

96

Outdoor

sensor

1.

Check wiring and correct any possible errors.

 

H

 

fault

 

 

2.

Replace the outdoor sensor.

 

 

 

 

 

 

3.

If previous steps are correct and fault persists, replace the

 

 

 

 

 

module.

 

 

97

Internal Fault: A2D

Internal Fault.

 

L

 

mismatch.

 

1.

Reset Module.

 

 

98

Internal

Fault:

2.

If fault repeats, replace module.

 

L

 

Exceeded

VSNSR

 

 

 

 

 

voltage tolerance

 

 

 

 

99

Internal

Fault:

 

 

 

L

 

Exceeded

28V

 

 

 

 

 

voltage tolerance

 

 

 

 

100

Pressure

Sensor

1.

Verify the Pressure Sensor is a 4-20ma source.

 

H

 

Fault

 

 

2.

Check wiring and correct any possible errors.

 

 

 

 

 

 

3.

Test Pressure Sensor for correct operation.

 

 

 

 

 

 

4.

Replace the Pressure sensor.

 

 

 

 

 

 

5.

If previous steps are correct and fault persists, replace the

 

 

 

 

 

module.

 

 

 

 

 

 

 

 

101-

RESERVED

 

 

 

 

104

 

 

 

 

 

 

 

105

Flame detected out

1.

Check that flame is not present in the combustion chamber.

H or L

 

of sequence

Correct any errors.

 

 

 

 

 

 

2.

Make sure that the flame detector is wired to the correct

 

 

 

 

 

terminal.

 

 

 

 

 

 

3.

Make sure the F & G wires are protected from stray noise

 

 

 

 

 

pickup.

 

 

 

 

 

 

4.

Reset and sequence the module, if code reappears, replace

 

 

 

 

 

the flame detector.

 

 

 

 

 

 

5.

Reset and sequence the module, if code reappears, replace

 

 

 

 

 

the module.

 

 

106

Flame lost in MFEP

1. Check pilot valve (Main Valve for DSI) wiring and operation -

L

107

Flame

lost

early in

correct any errors.

 

L

 

run

 

 

2.

Check the fuel supply.

 

 

108

Flame lost in run

3.

Check fuel pressure and repeat turndown tests.

 

L

109

Ignition failed

4.

Check ignition transformer electrode, flame detector, flame

L

 

 

 

 

detector setting or flame rod position.

 

 

 

 

 

 

5. If steps 1 through 4 are correct and the fault persists, replace

 

 

 

 

 

the module.

 

 

110

Ignition

failure

Hold time of recycle and hold option. Will not be a lockout fault.

H

 

occurred

 

Hold Only. Internal hardware test. Not a lockout.

 

 

111

Flame

 

current

 

 

 

H

 

lower

than

WEAK

 

 

 

 

 

threshold

 

 

 

 

 

112

Pilot

test

flame

Interrupted Pilot or DSI application and flame lost when system

L

 

timeout

 

in “test” mode.

 

 

 

 

 

 

1.

Reset the module to restart.

 

 

113

Flame

 

circuit

Flame sensed during Initiate or off cycle, hold 240 seconds, if

L

 

timeout

 

present after 240 seconds, lockout.

 

 

114-

RESERVED

 

 

 

 

121

 

 

 

 

 

 

 

 

 

 

 

 

43

 

 

Image 49
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Clearances Boiler FoundationMinimum Clearances to Combustible Surfaces DIMBoiler Connections Safety Relief ValvesFlow Connection Expansion Tank ConnectionsElectrical Requirements Venting of GAS Train ComponentsKW HP Combustion AIR SupplyLOUVERS, GRILLES, and Screens Combustion AIR OpeningsFlue GAS Venting System Design & InstallationScfm Combustion AIR and Venting Requirements for CanadaBefore Placing Boiler in Operation Marking of GAS VentsTest of GAS Piping Hydrostatic Test of Boilers and SystemStart-Up and Operation Triple-Flex High Efficiency Boilers TRIPLE-FLEX Front View Boiler AssemblyTriple-Flex Rear View TRIPLE-FLEX Rear ViewTRIPLE-FLEX Right Side View TRIPLE-FLEX Left Side ViewTRIPLE-FLEX Behind the Cabinet Door Air Flow Switch TRIPLE-FLEX Left Flue Collector View Pilot Spark Igniter AssemblyTRIPLE-FLEX Right Flue Collector View POWER-UP ValidationHome Sola Hydronic Control SystemKeyboard NavigationStatus Configuration ConfigureSample Configuration Configuration PasswordSafety Verification Configure Verify Change Parameter SettingsSafety Parameter User Confirmation FAULT/ALARM HandlingHome Page Lockout Info BAR Lockouts Clear Lockout OperationAnnunciation Operation Modulation Configuration Configure ModulationFiring Rate Control Operation Firing Rate Field System Time Setup Advanced Setup Date & Time Advanced Setup Setup Advanced SetupCalibrate Touch Screen Setup Advanced Setup Diagnostics Advanced Setup Display Reset Reset / Reboot DisplayOutdoor Reset Configure Configure CH Central Heat Configuration Configure Sensor ConfigurationSafety Verification Configure CH Central Heat Configuration PID Sound Pressure LevelsSound Pressure Readings Alert Codes Modbus CommunicationDHW RPMODR ILK A2D SLOHFS PIIRevision PRE Checks and Setup Test SetupBoiler Commissioning ModulationDRY RUN Pilot AdjustmentAdjusting Boiler Minimum Input Adjusting Boiler Maximum InputInitial Light OFF IWCGAS Meter Readings CFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clockedPII Or L TroubleshootingDate PII OFF LCI OFFILK OFF ILK on Weak VsnsrAre OEM Specific Fault Codes Fault CodesOFF ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Do not Flush the System Through the Boiler Draining the SystemBoiler Water Treatment Suggested Maintenance Schedule External FIRE-SIDE CleaningDate Revision Form Lead Lag Lead LAG LL Master General Operation General Description of the Lead LAG ApplicationDrop-stage method Drop-stage detection timing LL / Multi-Boiler Field Wiring System Wiring HookupLEAD-LAG Operation Slave Mode USE FIRST, Equalize RUNTIME, USE Last Slave Operation and SetupSlave Parameters Overall Control LL Master Operation and SetupSlave Status Manager Periodic Data Polling MessagesInvalid Response or no Response AbnormalFaultCounter Used to tolerate momentary abnormalityMaster Heat Demand LL CH Demand Switch DISABLE, STAT, Environcom Remote StatMaster Service Status Master Active ServiceModulation Sensor LL Modulation Sensor S5Demand and Rate Integrator Compensation Rate AdjustmentImplementation Base Load Common 0-100% Rate AllocationRate Allocation Method Parallel Commonbase Limited Overflow and Underflow Modulating StageStagerstate = Idle Burner DemandStagerstate = Active Error Threshold ADD-STAGE Error Threshold DegreesADD-STAGE Rate Offset -100% to +100% ADD-STAGE ConditionLL ALL Boilers OFF Threshold Temperature or None DROP-STAGE Error Threshold DegreesDROP-STAGE Rate Offset -100% to +100% DROP-STAGE ConditionLAG Selecton Method Sequence ORDER, Measured RUN Time Lead DROP-STAGE on ErrorForce Lead Rotation Time Hhmm or None Date Revision Form Forced Lead Rotation Sequencer 1 Minute EventSlave Write Data Slave Read Data