Code | Description |
| Recommended Troubleshooting of Lockout Codes |
| Code | ||
|
|
|
| 2. | Replace the stack sensor. |
|
|
|
|
|
| 3. | If previous steps are correct and fault persists, replace the |
| |
|
|
|
| module |
|
| |
96 | Outdoor | sensor | 1. | Check wiring and correct any possible errors. |
| H | |
| fault |
|
| 2. | Replace the outdoor sensor. |
|
|
|
|
|
| 3. | If previous steps are correct and fault persists, replace the |
| |
|
|
|
| module. |
|
| |
97 | Internal Fault: A2D | Internal Fault. |
| L | |||
| mismatch. |
| 1. | Reset Module. |
|
| |
98 | Internal | Fault: | 2. | If fault repeats, replace module. |
| L | |
| Exceeded | VSNSR |
|
|
|
| |
| voltage tolerance |
|
|
|
| ||
99 | Internal | Fault: |
|
|
| L | |
| Exceeded | 28V |
|
|
|
| |
| voltage tolerance |
|
|
|
| ||
100 | Pressure | Sensor | 1. | Verify the Pressure Sensor is a |
| H | |
| Fault |
|
| 2. | Check wiring and correct any possible errors. |
|
|
|
|
|
| 3. | Test Pressure Sensor for correct operation. |
|
|
|
|
|
| 4. | Replace the Pressure sensor. |
|
|
|
|
|
| 5. | If previous steps are correct and fault persists, replace the |
| |
|
|
|
| module. |
|
| |
|
|
|
|
|
| ||
101- | RESERVED |
|
|
|
| ||
104 |
|
|
|
|
|
|
|
105 | Flame detected out | 1. | Check that flame is not present in the combustion chamber. | H or L | |||
| of sequence | Correct any errors. |
|
| |||
|
|
|
| 2. | Make sure that the flame detector is wired to the correct |
| |
|
|
|
| terminal. |
|
| |
|
|
|
| 3. | Make sure the F & G wires are protected from stray noise |
| |
|
|
|
| pickup. |
|
| |
|
|
|
| 4. | Reset and sequence the module, if code reappears, replace |
| |
|
|
|
| the flame detector. |
|
| |
|
|
|
| 5. | Reset and sequence the module, if code reappears, replace |
| |
|
|
|
| the module. |
|
| |
106 | Flame lost in MFEP | 1. Check pilot valve (Main Valve for DSI) wiring and operation - | L | ||||
107 | Flame | lost | early in | correct any errors. |
| L | |
| run |
|
| 2. | Check the fuel supply. |
|
|
108 | Flame lost in run | 3. | Check fuel pressure and repeat turndown tests. |
| L | ||
109 | Ignition failed | 4. | Check ignition transformer electrode, flame detector, flame | L | |||
|
|
|
| detector setting or flame rod position. |
|
| |
|
|
|
| 5. If steps 1 through 4 are correct and the fault persists, replace |
| ||
|
|
|
| the module. |
|
| |
110 | Ignition | failure | Hold time of recycle and hold option. Will not be a lockout fault. | H | |||
| occurred |
| Hold Only. Internal hardware test. Not a lockout. |
|
| ||
111 | Flame |
| current |
|
|
| H |
| lower | than | WEAK |
|
|
|
|
| threshold |
|
|
|
|
| |
112 | Pilot | test | flame | Interrupted Pilot or DSI application and flame lost when system | L | ||
| timeout |
| in “test” mode. |
|
| ||
|
|
|
| 1. | Reset the module to restart. |
|
|
113 | Flame |
| circuit | Flame sensed during Initiate or off cycle, hold 240 seconds, if | L | ||
| timeout |
| present after 240 seconds, lockout. |
|
| ||
114- | RESERVED |
|
|
|
| ||
121 |
|
|
|
|
|
|
|
|
|
|
|