Bryan Boilers Triple-Flex 150, 250, & 300, 200 service manual Air Flow Switch

Page 20

NOTE:

The low fire displacement final adjustment should be made at low fire only.

3.Main gas pressure regulating and shutoff valve actuator. The pressure regulating actuator provides slow opening fast closing safety shutoff and air/gas ratio control. The actuator controls the pressure difference across the gas limiting orifice valve (Figure 7 item 26) as a function of the pressure difference across the furnace section so that the air to gas ratio remains constant irrespective of air volume changes. There is no need for an upstream constant pressure regulator when the supply gas pressure does not exceed 56 inches of water column. A minimum of 14 inches of water column must be supplied at the gas inlet connection (Figure 6 item 1). The supply pressure can be measured at the test port (Figure 7 item 28).

NOTE:

The supply pressure is not static. The supply pressure is at the maximum full flow of gas through the burner.

4.Manual main gas shutoff valve.

5.Pilot ignition transformer.

6.Manual pilot gas shutoff valve.

7.Pilot gas pressure regulator. This regulator provides a constant gas pressure to the pilot when the solenoid valve is energized. The pressure can be adjusted by removing the cap and adjusting the slotted screw clockwise to increase the pressure and counter-clockwise to decrease the pressure. The pilot gas supply is taken upstream of the main gas cock so the pilot may be lighted and adjusted with the main gas cock closed.

8.Low pilot gas pressure switch (Manual Reset)

9.Pilot spark igniter assembly. For further detail see Figure 9.

10.Pilot gas solenoid valve.

11.Flame scanner.

12.Main gas manifold pressure test port (1/4” NPT).

13.Main high gas pressure switch (Manual Reset). This switch should be set 1” of water column above the maximum gas manifold pressure.

14.Pilot gas pressure test port (1/4” NPT). This

14

Date: 8-4-2010

Revision: 0

Form: 2396

port is also used to record the furnace pressure.

15.Boiler water flow switch. The boiler water flow switch is adjustable within the parameters listed in the table.

Settings

Mode Of Operation

Switch

Switch

 

Closed

Open

Minimum

30 gpm

12 gpm

Maximum

52.1

46.1

 

gpm

gpm

Table 4 Water Flow Switch Settings

16.Low Water Cutoff (Manual Reset Probe Type).

17.Combustion air-flow switch. An airflow switch is provided to prove that air is being provided to the burners before main flame can be established. The airflow switch can be adjusted by turning the screw (Figure 8 item A) clockwise to increase the pressure setting and counter-clockwise to decrease the pressure setting. The switch will open on pressure drop. When the blower is running there should be continuity between the common and the normally open contacts (Figure 8 item B and C). When the blower is interrupted the switch should open and cause a safety shutdown.

A

B

C

Figure 8 Air Flow Switch

18.High burner air pressure switch manual reset. This switch will trip when the air pressure in the burner rises above the set- point, indicating that the burner has become plugged with dust or other foreign matter.

19.Gas and air mixer assembly.

20.Main 3-phase power connection and fuse

Image 20
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Boiler Foundation ClearancesMinimum Clearances to Combustible Surfaces DIMSafety Relief Valves Boiler ConnectionsFlow Connection Expansion Tank ConnectionsVenting of GAS Train Components Electrical RequirementsKW HP Combustion AIR SupplyCombustion AIR Openings LOUVERS, GRILLES, and ScreensDesign & Installation Flue GAS Venting SystemCombustion AIR and Venting Requirements for Canada ScfmMarking of GAS Vents Before Placing Boiler in OperationHydrostatic Test of Boilers and System Test of GAS PipingStart-Up and Operation Triple-Flex High Efficiency Boilers Boiler Assembly TRIPLE-FLEX Front ViewTRIPLE-FLEX Rear View Triple-Flex Rear ViewTRIPLE-FLEX Behind the Cabinet Door TRIPLE-FLEX Left Side ViewTRIPLE-FLEX Right Side View Air Flow Switch Pilot Spark Igniter Assembly TRIPLE-FLEX Left Flue Collector ViewPOWER-UP Validation TRIPLE-FLEX Right Flue Collector ViewHome Sola Hydronic Control SystemNavigation KeyboardConfiguration Configure StatusConfiguration Password Sample ConfigurationChange Parameter Settings Safety Verification Configure VerifyFAULT/ALARM Handling Safety Parameter User ConfirmationInfo BAR Lockouts Clear Lockout Operation Home Page LockoutFiring Rate Control Operation Firing Rate Field Modulation Configuration Configure ModulationAnnunciation Operation Calibrate Touch Screen Setup Advanced Setup Diagnostics Advanced Setup Setup Advanced SetupSystem Time Setup Advanced Setup Date & Time Outdoor Reset Configure Reset / Reboot DisplayAdvanced Setup Display Reset Safety Verification Configure CH Central Heat Configuration Configure Sensor ConfigurationConfigure CH Central Heat Configuration Sound Pressure Levels PIDSound Pressure Readings Modbus Communication Alert CodesRPM DHWODR ILK SLO A2DHFS PIIRevision Test Setup PRE Checks and SetupBoiler Commissioning ModulationPilot Adjustment DRY RUNAdjusting Boiler Maximum Input Adjusting Boiler Minimum InputInitial Light OFF IWCCFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clocked GAS Meter ReadingsTroubleshooting PII Or LDate ILK OFF LCI OFFPII OFF ILK on Vsnsr WeakFault Codes Are OEM Specific Fault CodesOFF ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Boiler Water Treatment Draining the SystemDo not Flush the System Through the Boiler External FIRE-SIDE Cleaning Suggested Maintenance ScheduleDate Revision Form Lead Lag General Description of the Lead LAG Application Lead LAG LL Master General OperationDrop-stage method Drop-stage detection timing System Wiring Hookup LL / Multi-Boiler Field WiringLEAD-LAG Operation Slave Parameters Slave Operation and SetupSlave Mode USE FIRST, Equalize RUNTIME, USE Last LL Master Operation and Setup Overall ControlPeriodic Data Polling Messages Slave Status ManagerAbnormalFaultCounter Used to tolerate momentary abnormality Invalid Response or no ResponseLL CH Demand Switch DISABLE, STAT, Environcom Remote Stat Master Heat DemandMaster Active Service Master Service StatusModulation Sensor LL Modulation Sensor S5Demand and Rate Implementation Rate AdjustmentIntegrator Compensation Rate Allocation Method Parallel Commonbase Limited Rate AllocationBase Load Common 0-100% Modulating Stage Overflow and UnderflowStagerstate = Active Burner DemandStagerstate = Idle ADD-STAGE Error Threshold Degrees Error ThresholdADD-STAGE Rate Offset -100% to +100% ADD-STAGE ConditionDROP-STAGE Error Threshold Degrees LL ALL Boilers OFF Threshold Temperature or NoneDROP-STAGE Rate Offset -100% to +100% DROP-STAGE ConditionForce Lead Rotation Time Hhmm or None Lead DROP-STAGE on ErrorLAG Selecton Method Sequence ORDER, Measured RUN Time Date Revision Form Sequencer 1 Minute Event Forced Lead RotationSlave Write Data Slave Read Data