Bryan Boilers 250, & 300, 200 Sequencer 1 Minute Event, Forced Lead Rotation, Slave Write Data

Page 81

StagingOrder numbers of all Firing boilers. If only one Firing boiler is found, or none are found, then this selection function returns a value that indicates no boiler may be dropped. Otherwise it returns an identifier for the boiler having the highest StagingOrder number.

SEQUENCER 1 MINUTE EVENT

Part of the sequencer is called by the timing service at a 1 minute rate to implement lead rotation.

The 1 minute event checks the boiler identified by Lead- BoilerSeqNum. If it is Firing then the LeadBoilerRunTime is incremented.

FORCED LEAD ROTATION:

When the boiler identified by LeadBoilerSeqNum is firing and also LeadBoilerRunTime reaches the Force lead rotation time parameter time then:

1.The current lead boiler is noted.

2.Lead rotation occurs as described above under Voluntary Lead Rotation (this changes the designation, but does not change the actual firing status).

SLAVE WRITE: DATA

This allows the slave to accept command messages from a Sola master

SLAVE READ: DATA

This provides the slave status message to be read by a Sola Master. It includes all of the data that is read from a slave.

SLAVE MODE: USE FIRST, EQUALIZE RUNTIME, USE LAST

If set to Use First, then this slave Sola will be used prior to using other slave Solas with other values.

If this parameter is set to Equalize Runtime, then this slave Sola will be staged according to a run time equalization. (Any Solas set to Use First will precede any that are set to Equalize Runtime.)

If this parameter is set to Use Last, then this slave Sola will be used only after

all Use First and Equalize Runtime Solas have been brought online.

SLAVE PRIORITY SEQUENCE ORDER: 0-255 Slave sequence order is used to determine the order in which the slave Solas will be used (staged on) for those Solas with the same Slave mode setting. Numbers may be skipped, that is

75

Date: 8-4-2010

Revision: 0

Form: 2396

3 will be first if there is no 1 or 2.

NOTE: For Equalize Runtime purposes, 1 does not mean the Sola will be used first every time; that will vary over time based on the master's run time equalization scheme. In this case the sequence number determines the relative order in which Sola controls will be used in a round- robin scheme.

If the slave sequence number value is zero, then the slave Sola's ModBus address will be used instead.

If two Solas are set the same mode and both have the same sequence number then an alert will occur and the order in which they are used will be arbitrary and is not guaranteed to be repeatable.

Image 81
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Clearances Boiler FoundationMinimum Clearances to Combustible Surfaces DIMBoiler Connections Safety Relief ValvesFlow Connection Expansion Tank ConnectionsElectrical Requirements Venting of GAS Train ComponentsKW HP Combustion AIR SupplyLOUVERS, GRILLES, and Screens Combustion AIR OpeningsFlue GAS Venting System Design & InstallationScfm Combustion AIR and Venting Requirements for CanadaBefore Placing Boiler in Operation Marking of GAS VentsTest of GAS Piping Hydrostatic Test of Boilers and SystemStart-Up and Operation Triple-Flex High Efficiency Boilers TRIPLE-FLEX Front View Boiler AssemblyTriple-Flex Rear View TRIPLE-FLEX Rear ViewTRIPLE-FLEX Left Side View TRIPLE-FLEX Right Side ViewTRIPLE-FLEX Behind the Cabinet Door Air Flow Switch TRIPLE-FLEX Left Flue Collector View Pilot Spark Igniter AssemblyTRIPLE-FLEX Right Flue Collector View POWER-UP ValidationHome Sola Hydronic Control SystemKeyboard NavigationStatus Configuration ConfigureSample Configuration Configuration PasswordSafety Verification Configure Verify Change Parameter SettingsSafety Parameter User Confirmation FAULT/ALARM HandlingHome Page Lockout Info BAR Lockouts Clear Lockout OperationModulation Configuration Configure Modulation Annunciation OperationFiring Rate Control Operation Firing Rate Field Advanced Setup Setup Advanced Setup System Time Setup Advanced Setup Date & TimeCalibrate Touch Screen Setup Advanced Setup Diagnostics Reset / Reboot Display Advanced Setup Display ResetOutdoor Reset Configure Configure Sensor Configuration Configure CH Central Heat ConfigurationSafety Verification Configure CH Central Heat Configuration PID Sound Pressure LevelsSound Pressure Readings Alert Codes Modbus CommunicationDHW RPMODR ILK A2D SLOHFS PIIRevision PRE Checks and Setup Test SetupBoiler Commissioning ModulationDRY RUN Pilot AdjustmentAdjusting Boiler Minimum Input Adjusting Boiler Maximum InputInitial Light OFF IWCGAS Meter Readings CFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clockedPII Or L TroubleshootingDate LCI OFF PII OFFILK OFF ILK on Weak VsnsrAre OEM Specific Fault Codes Fault CodesOFF ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Draining the System Do not Flush the System Through the BoilerBoiler Water Treatment Suggested Maintenance Schedule External FIRE-SIDE CleaningDate Revision Form Lead Lag Lead LAG LL Master General Operation General Description of the Lead LAG ApplicationDrop-stage method Drop-stage detection timing LL / Multi-Boiler Field Wiring System Wiring HookupLEAD-LAG Operation Slave Operation and Setup Slave Mode USE FIRST, Equalize RUNTIME, USE LastSlave Parameters Overall Control LL Master Operation and SetupSlave Status Manager Periodic Data Polling MessagesInvalid Response or no Response AbnormalFaultCounter Used to tolerate momentary abnormalityMaster Heat Demand LL CH Demand Switch DISABLE, STAT, Environcom Remote StatMaster Service Status Master Active ServiceModulation Sensor LL Modulation Sensor S5Demand and Rate Rate Adjustment Integrator CompensationImplementation Rate Allocation Base Load Common 0-100%Rate Allocation Method Parallel Commonbase Limited Overflow and Underflow Modulating StageBurner Demand Stagerstate = IdleStagerstate = Active Error Threshold ADD-STAGE Error Threshold DegreesADD-STAGE Rate Offset -100% to +100% ADD-STAGE ConditionLL ALL Boilers OFF Threshold Temperature or None DROP-STAGE Error Threshold DegreesDROP-STAGE Rate Offset -100% to +100% DROP-STAGE ConditionLead DROP-STAGE on Error LAG Selecton Method Sequence ORDER, Measured RUN TimeForce Lead Rotation Time Hhmm or None Date Revision Form Forced Lead Rotation Sequencer 1 Minute EventSlave Write Data Slave Read Data