Bryan Boilers & 300, Triple-Flex 150, 250, 200 service manual Dry Run, Pilot Adjustment

Page 42

WARNING:

Do not open the manual main gas cock (Figure 7 item 4) before all pre checks, setups, and dry runs have been successfully completed.

With a voltmeter check for the proper incoming main voltage and the proper control voltage from the control circuit transformer. Refer to the electrical wiring diagram and boiler-rating label for proper voltages.

Make sure the boiler is full of water and proper flow has been established.

Power up the boiler see (paragraph 2.2.1).

Navigate to the ‘Operation Screen’ (paragraph 2.2.11). Select the burner switch to toggle the burner to the off state.

Navigate to the ‘Firing Rate Control Page’ (paragraph 2.2.14). Select the ‘Manual in Run” option and enter the light off RPM from (Table 9 Approximate Boiler Settings) in the Manual Firing Rate box. This will prevent the burner from ramping up to high fire after the flame stabilization period.

Navigate to the ‘Annunciation Page” (paragraph 2.2.12). All load control inputs and interlocks should be in the on state with the exception of the air flow switch. The air flow switch will close when the burner is commanded to start. Correct any problem indicated. Refer to trouble shooting (paragraph 0) for further help.

Navigate to the ‘Operation Screen’ (paragraph 2.2.11). The boiler is now prepared to be placed in the on state by toggling the burner switch to on.

2.3.4DRY RUN

Navigate to the ‘Operation Screen’ (paragraph 2.2.11). Toggle the burner switch to on.

Navigate to the ‘Status Page’ (paragraph 2.2.5). If there is demand for hot water the burner state will display driving to purge. When the fan speed is within +/- 3% of the firing rate for 3

Date: 8-4-2010

Revision: 0

Form: 2396

seconds the purge timer will start and count to

30.After 30 seconds the fan speed is reduced to the light off rate. When the fan speed is with in +/- 3% of the firing rate for 3 seconds the ignition transformer and the pilot valve are energized. The pilot will light and can be observed from the observation port (Figure 5 item 4). After a duration of 5 seconds the ignition transformer will de-energize. The pilot valve will stay energized for another 5 seconds before the main gas valves are energized. During this 10 second period the pilot should be adjusted according to paragraph 2.3.5.

The main gas valves will energize for 10 seconds. After this 10 second duration the pilot valve is de-energized. The control will lockout with a code of 106, Flame lost in Main Flame Establishing Period.

WARNING:

During the first 10 seconds of this process the automatic gas valves should not have opened or been energized. If any of the automatic gas valves are energized or open at this point correct the problem immediately.

2.3.5PILOT ADJUSTMENT

Adjust the pilot gas pressure between 3.5 iwc and 4 iwc. The pilot flame signal can be observed from the status page (paragraph 2.2.5). The minimum flame signal is .8 volts. The flame signal can vary between 4 volts and 15 volts. A flame signal closer to 15 volts is preferred. Observe the pilot flame through the flame observation port (Figure 5 item 4). The pilot should appear stable. A stable pilot will not flicker on and off. Recycle the boiler as many times as needed to establish a good pilot. If the pilot fails to light refer to trouble shooting (paragraph 1.1.1) for further help.

36

Image 42
Contents Triple-Flex High Efficiency Boilers Triple-Flex 150, 200, 250 High Efficiency Boilers Table of Contents Lead Drop-Stage On Error Ldse Figures Date Date Revision Form Minimum Clearances to Combustible Surfaces Boiler FoundationClearances DIMFlow Connection Safety Relief ValvesBoiler Connections Expansion Tank ConnectionsKW HP Venting of GAS Train ComponentsElectrical Requirements Combustion AIR SupplyCombustion AIR Openings LOUVERS, GRILLES, and ScreensDesign & Installation Flue GAS Venting SystemCombustion AIR and Venting Requirements for Canada ScfmMarking of GAS Vents Before Placing Boiler in OperationHydrostatic Test of Boilers and System Test of GAS PipingStart-Up and Operation Triple-Flex High Efficiency Boilers Boiler Assembly TRIPLE-FLEX Front ViewTRIPLE-FLEX Rear View Triple-Flex Rear ViewTRIPLE-FLEX Left Side View TRIPLE-FLEX Right Side ViewTRIPLE-FLEX Behind the Cabinet Door Air Flow Switch Pilot Spark Igniter Assembly TRIPLE-FLEX Left Flue Collector ViewHome POWER-UP ValidationTRIPLE-FLEX Right Flue Collector View Sola Hydronic Control SystemNavigation KeyboardConfiguration Configure StatusConfiguration Password Sample ConfigurationChange Parameter Settings Safety Verification Configure VerifyFAULT/ALARM Handling Safety Parameter User ConfirmationInfo BAR Lockouts Clear Lockout Operation Home Page LockoutModulation Configuration Configure Modulation Annunciation OperationFiring Rate Control Operation Firing Rate Field Advanced Setup Setup Advanced Setup System Time Setup Advanced Setup Date & TimeCalibrate Touch Screen Setup Advanced Setup Diagnostics Reset / Reboot Display Advanced Setup Display ResetOutdoor Reset Configure Configure Sensor Configuration Configure CH Central Heat ConfigurationSafety Verification Configure CH Central Heat Configuration Sound Pressure Levels PIDSound Pressure Readings Modbus Communication Alert CodesRPM DHWODR ILK HFS SLOA2D PIIRevision Boiler Commissioning Test SetupPRE Checks and Setup ModulationPilot Adjustment DRY RUNInitial Light OFF Adjusting Boiler Maximum InputAdjusting Boiler Minimum Input IWCCFH = 3600Vc gc CFH = ft 3 hr −1 of gas Vc = ft clocked GAS Meter ReadingsTroubleshooting PII Or LDate LCI OFF PII OFFILK OFF ILK on Vsnsr WeakOFF Fault CodesAre OEM Specific Fault Codes ThroughOFF Blower LCI High Limit setpoint setting 228 Invalid Reserved Care and Maintenance Boil OUT Procedure Draining the System Do not Flush the System Through the BoilerBoiler Water Treatment External FIRE-SIDE Cleaning Suggested Maintenance ScheduleDate Revision Form Lead Lag General Description of the Lead LAG Application Lead LAG LL Master General OperationDrop-stage method Drop-stage detection timing System Wiring Hookup LL / Multi-Boiler Field WiringLEAD-LAG Operation Slave Operation and Setup Slave Mode USE FIRST, Equalize RUNTIME, USE LastSlave Parameters LL Master Operation and Setup Overall ControlPeriodic Data Polling Messages Slave Status ManagerAbnormalFaultCounter Used to tolerate momentary abnormality Invalid Response or no ResponseLL CH Demand Switch DISABLE, STAT, Environcom Remote Stat Master Heat DemandModulation Sensor Master Active ServiceMaster Service Status LL Modulation Sensor S5Demand and Rate Rate Adjustment Integrator CompensationImplementation Rate Allocation Base Load Common 0-100%Rate Allocation Method Parallel Commonbase Limited Modulating Stage Overflow and UnderflowBurner Demand Stagerstate = IdleStagerstate = Active ADD-STAGE Rate Offset -100% to +100% ADD-STAGE Error Threshold DegreesError Threshold ADD-STAGE ConditionDROP-STAGE Rate Offset -100% to +100% DROP-STAGE Error Threshold DegreesLL ALL Boilers OFF Threshold Temperature or None DROP-STAGE ConditionLead DROP-STAGE on Error LAG Selecton Method Sequence ORDER, Measured RUN TimeForce Lead Rotation Time Hhmm or None Date Revision Form Slave Write Data Sequencer 1 Minute EventForced Lead Rotation Slave Read Data