Delta Electronics VFD-G manual Preparation for Installation and Wiring 1.5.1 Ambient Conditions

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 19
Image 19
1.5 Preparation for Installation and Wiring

Chapter 1 Introduction1.5.2 Minimum Mounting Clearances

1.5 Preparation for Installation and Wiring

1.5.1 Ambient Conditions

Install the AC motor drive in an environment with the following conditions:

 

 

Air Temperature:

 

-10 ~ +40°C (14 ~ 104°F)

 

 

 

Relative Humidity:

<90%, no condensation allowed

 

 

 

 

 

 

Operation

Atmosphere

 

86 ~ 106 kPa

 

 

pressure:

 

 

 

 

 

 

 

Installation Site

<1000m

 

 

Altitude:

 

 

 

 

 

 

Vibration:

 

<20Hz: 9.80 m/s2 (1G) max

 

 

 

 

20 ~ 50Hz: 5.88 m/s2 (0.6G) max

 

 

 

 

 

 

Temperature:

-20°C ~ +60°C (-4°F ~ 140°F)

 

 

 

 

 

Storage

Relative Humidity:

 

<90%, no condensation allowed

 

 

Transportation

Atmosphere

86 ~ 106 kPa

 

 

pressure:

 

 

 

 

 

 

Vibration:

 

<20Hz: 9.80 m/s2 (1G) max

 

 

 

20 ~ 50Hz: 5.88 m/s2 (0.6G) max

 

 

 

 

Pollution Degree

2: good for a factory type environment.

 

 

 

 

 

 

1.5.2 Minimum Mounting Clearances

H

Air Flow

 

FWD

 

REV

 

W

W

H

 

HP

W

mm (inch)

 

1-5HP

50 (2)

7.5-20HP

75 (3)

25-75HP

75 (3)

100HP and above

75 (3)

H

mm(inch)

150 (6)

175 (7)

200 (8)

250 (10)

1-10

Revision July 2008, EG03, SW V1.06