Chapter 4 Parameters |
|
|
| |
|
|
| ||
02 - 10 | User Defined Coefficient | Unit: 0.01 | ||
| Settings | 0.01~160.00 | Factory Setting: 1.00 | |
|
|
|
|
|
When this parameter is set, the “H “display value = actual output frequency of AC drive x 02- 10.
If output frequency of AC drive is 90Hz, set
02 - 11 | Flying Start |
| |
|
|
| Factory Setting: 00 |
| Settings | 00: Disabled | |
|
|
| 01: Enabled (DC braking disabled) |
|
|
|
|
When the AC drive starts into a running motor (Flying Start), it may cause an over current on the drive and may damage the motor. Using speed search upon
If the Flying Start feature is enabled upon
02 - 12 | Flying Start Frequency |
| |
|
|
| Factory Setting: 00 |
| Settings | 00: Begin search from Master Frequency Command | |
|
| 01: Begin search from Maximum Frequency | |
|
|
|
|
|
|
|
|
02 - 13 | Master Frequency Memory Setting | ||
|
|
| Factory Setting: 01 |
| Settings | 00: Do not remember the last known frequency | |
|
| 01: Remember the last known frequency |
If this parameter is set to 00: The AC drive will not store the last known master frequency command, after power is removed.
If this parameter is set to 01: The AC drive will memorize the last known master frequency command after power off. Upon power up the last known frequency is displayed.
After a fault, the AC drive will always remember the last know master frequency command. This feature is only enabled when Pr.