Chapter 6 Fault Code Information and Maintenance

 

 

 

 

 

 

 

 

Fault

Fault Descriptions

 

Corrective Actions

 

 

Name

 

 

 

 

 

 

 

 

 

 

Over-current during

 

 

 

 

 

 

deceleration:

1.

Check for possible poor insulation at the output

 

1. Short-circuit at motor

 

 

line.

 

output.

 

 

2.

Increase the deceleration time.

 

2. Deceleration time too

 

3.

Replace with the AC drive with one that has a

 

short.

 

 

higher output capacity (next HP size).

 

3. AC drive output capacity

 

 

 

 

 

 

 

 

is too small.

 

 

 

 

 

 

Over-current during steady

 

 

 

 

 

 

state operation:

1.

Check for possible poor insulation at the output

 

1. Short-circuit at motor

 

 

line.

 

output.

 

 

2.

Check for possible motor stall.

 

2. Sudden increase in motor

 

3.

Replace with the AC drive with one that has a

 

loading.

 

 

higher output capacity (next HP size).

 

3. AC drive output capacity

 

 

 

 

 

 

 

 

is too small.

 

 

 

 

 

 

 

 

 

 

 

The external terminal EF-

1.

When external terminal EF-GND is closed, the

 

 

output will be turned off. (Under N.O. E.F.)

 

GND goes from OFF to ON.

 

 

2.

Press RESET after fault has been cleared.

 

 

 

 

 

 

 

 

 

 

Emergency stop.

 

 

 

 

 

 

When the multi-function input

Press RESET after fault has been cleared.

 

terminals (MI1 to MI4) stop,

 

 

 

 

 

 

 

AC drive stops any output.

 

 

 

 

 

 

 

 

 

 

Software protection failure

Return to the factory.

 

 

 

 

 

 

 

 

Ground fault:

 

 

 

 

 

 

The AC drive output is

 

 

 

 

 

 

abnormal. When the output

 

 

 

 

 

 

terminal is grounded (short

Ground fault:

 

circuit current is 50% more

1.

Check whether the IGBT power module is

 

than the AC drive rated

 

 

damaged.

 

current), the AC drive power

 

 

2.

Check for possible poor insulation at the output

 

module may be damaged.

 

 

line.

 

The short circuit protection is

 

 

 

 

 

 

 

 

provided for AC drive

 

 

 

 

 

 

protection, not user

 

 

 

 

 

 

protection.

 

 

 

 

 

 

External Base Block.

1.

When the external input terminal (B.B) is active,

 

 

the AC drive output will be turned off.

 

AC drive output is turned off.

 

 

2.

Disable this connection and the AC drive will

 

(Refer to Pr. 08-08)

 

 

begin to work again.

 

 

 

 

 

 

 

 

 

Low Current

1.

Check Load current

 

2.

Check Pr.06-08 to Pr.06-10 setting

 

 

 

 

 

 

 

Phase Loss

Check Power Source Input

 

 

 

 

 

 

 

Revision July 2008, EG03, SW V1.06