Chapter 4 Parameters

 

 

 

 

 

 

10 - 07

Primary Low Pass Filter Time

Unit: 0.1

 

Settings

0.0~2.5 Sec

Factory Setting: 0.0

 

 

 

 

 

This parameter determines primary Low Pass filter time.

Output frequency of PID controller will filter by primary low pass function. This function could decrease change of output frequency. A long primary low pass time means filter degree is high and vice versa.

Unsuitable primary low pass filter time setting may cause system oscillation.

10 - 08

PID Feedback Signal Range

Unit: 0.01

 

Settings

0.01~160.00Hz

Factory Setting: 600.00

 

 

 

 

This parameter setting could allow the maximum of PID deviation.

If PID function is normally, it should control the detective value to target value accurately in the certain time. If AC drive can’t control deviation in the 10-08 setting range during 10-07 setting time, it means PID feedback control is abnormal. The treatment is set as 10-10.

10 - 09

PID Feedback Signal Fault Treatment Time

Unit: 0.1

 

Settings

0.0~3600.0 Sec

Factory Setting: 0.0

 

This parameter is to set the detection time of abnormal PID derivative. If PID deviation

detection time is set to 0.0, the function is disabled.

 

 

 

 

10 - 10

PID Feedback Signal Fault Treatment

 

 

 

 

Factory Setting: 01

 

Settings

00: Warn and RAMP stop

 

 

 

01: Warn and COAST stop

 

 

 

02: Warn and keep operating

 

 

 

 

 

This parameter is to set treatment of the abnormal PID deviation.

10 - 11 V/F Curve Selection

Factory Setting: 00

Settings

00: Determined by group 1

 

01: 1.5 power curve

 

02: 1.7 power curve

 

03: 2 power curve

 

04: 3 power curve

 

 

4-88