Preface
PLEASE READ PRIOR TO INSTALLATION FOR SAFETY
DANGER
Page
Table of Contents
Table of Contents
Chapter 2 Installation and Wiring
Preface
Chapter 5 Troubleshooting
Chapter 3 Keypad and Start Up
Chapter 4 Parameters
Specification for main circuit terminals and control terminals
Chapter 6 Fault Code Information and Maintenance
Appendix A Specifications
Appendix B Accessories
Appendix C How to Select the Right AC Motor Drive
Chapter 1 Introduction
1.1 Receiving and Inspection
1.1.1 Nameplate Information
075F43AG4T5010001
1.1.3 Series Number Explanation
075F43AG4 T 7 01
1.1.4 Drive Frames
1.2 Appearances
50-125HP/37-90kWFrame E, E1
150-215HP/110-160kWFrame G
250-300HP/185-220kWFrame H
Chapter 1 Introduction
1.3 Remove Instructions 1.3.1 Remove Keypad
7.5-20HP/5.5-15kWFrame
25-40HP/18.5-30kWFrame D
50-125HP/37-90kWFrame
1.3.2 Remove Front Cover
250-300HP/185-220kWFrame H
7.5-20HP/5.5-15kWFrame C
25-40HP/18.5-30kWFrame D
50-125HP/37-90kWFrame E, E1
150-215HP/110-160kWFrame G
250-300HP/185-220kWFrame H
Chapter 1 Introduction
1.4 Lifting
For 50-125HP Frame E, E1
Step
Step
For 150-215HP Frame G
Step
Step
Step
For 250-300HP Frame H
Step
Step
Step
1.5 Preparation for Installation and Wiring 1.5.1 Ambient Conditions
1.5.2 Minimum Mounting Clearances
Air Flow
2. Failure to observe these precautions may void the warranty
1.6 Dimensions
Chapter 1 Introduction
Frame
Frame
Chapter 1 Introduction
Frame
Frame
425.016.73
This page intentionally left blank
Chapter 1 Introduction
1-14
Revision July 2008, EG03, SW
Chapter 2 Installation and Wiring
2.1 Wiring
Chapter 2 Installation and Wiring
DANGER
Chapter 2 Installation and Wiring
VFD-G
Revision July 2008, EG03, SW
NOTE*1- 3 are optional
Chapter 2 Installation and Wiring
VFD-G
For 460V series, 25hp and above
Revision July 2008, EG03, SW
SINK Mode
SOURCE Mode
Digital Signal Common
+24V EF FWD REV MI1 MI2 MI3 MI4 DCM +24V EF FWD REV MI1 MI2 MI3 MI4
Excellent Good Not allowed
2.2 External Wiring
Choke
BR Brake resistor
VF DB
2.3 Main Circuit Connection
VFD-G
IM 3~
VFD-G
DC Reactor
DC Reactor
Jumper
Jumper
external brake unit
2.4 Control Terminals
wind each wires 3 times or more around the core
ferrite core
Analog inputs AI1, AI2, AC1, AC2
AI1/AI2 C AC1/AC2
DANGER
General
2.5 Specification for main circuit terminals and control terminals
POWER
25 HP to 40 HP VFD185F43A-G, VFD220F43A-G, VFD300F43A-G
V/T2 W/T3
DC +
Chapter 2 Installation and Wiring
POWER
POWER ALARM
2-16
75 HP to 125 HP VFD550F43A-G, VFD750F43A-G, VFD900F43C-G
CHARGE
Chapter 2 Installation and Wiring
POWER
2-18
Revision July 2008, EG03, SW
Chapter 2 Installation and Wiring
POWER
Revision July 2008, EG03, SW
2-19
2.6 Wiring Explanation for Analog Input Terminal
Chapter 2 Installation and Wiring
2-20
Revision July 2008, EG03, SW
1. When using analog current input 0~1A, please plug into the left two pins See the red mark, and make sure the jumper is connected well See what the following yellow arrows point at
Chapter 2 Installation and Wiring
This page intentionally left blank
2-22
Revision July 2008, EG03, SW
Chapter 3 Keypad and Start Up
3.1 Digital Keypad VFD-PU01 3.1.1 Description of the Digital Keypad
STOP RESET
3.1.2 How to Operate the Digital Keypad VFD-PU01
Setting direction
START
To shift data
3.1.3 VFD-PU01 Dimensions
3.1.4 Reference Table for the LED Display of the Digital Keypad
RUN STOP
3.2 Operation Method
RESET
RUN STOP
3.3 Trial Run
Check if the motor direction of rotation is correct
Check if acceleration and deceleration are smooth
This page intentionally left blank
Chapter 3 Keypad and Start Up
Revision July 2008, EG03, SW
Chapter 4 Parameters
4.1 Summary of Parameter Settings
Settings
Setting
Group 0 User Parameters
Settings
Setting
Parameter
Functions
Parameter
Parameter
Settings
Setting
Parameter
Functions
Settings
Setting
Group 3 Output Function Parameters
Parameter
Settings
Setting
Group 4 Input Function Parameters
Parameter
Settings
Setting
Parameter
Functions
Settings
Setting
Group 5 Multi-step Speed Parameters
Parameter
Parameter
Settings
Setting
Parameter
Functions
Parameter
Parameter
Parameter
Settings
Setting
Parameter
Functions
Settings
Setting
Group 10 PID Control Parameters
Parameter
4.2 Parameter Settings for Applications
VFD-G
VFD-G
Emergency Stop by DC Brake
Output Signal during Running
Output Signal for Base Block
4.3 Description of Parameter Settings
This parameter can be set during operation
Code
Bit 8 Master frequency source via communication interface
00 - 14 PLC Time
Group 1 Basic Parameters
01 - 04 Mid-point Voltage
Output voltage 01-02
01-04
01-06
Output Frequency
JOG Frequency
01-23
Accel/Decel time unit
1 Sec
0.1 Sec
Group 2 Operation Method Parameters
Settings
PWM Carrier Frequency Selections
7.5~10HP 4000~6000Hz
15~30HP 3000~6000Hz
VFD-G
FWD/STOP
REV/STOP
RUN/STOP
02 - 07 Reserved
User Defined Coefficient
Setting
Group 3 Output Function Parameters
Functions
Descriptions
Setting
Frequency 2Hz
Time
Functions
03 - 04 DC Fan Control
03 - 09 Analog Output 2 Selection Factory Setting
Settings
00 0~20mA
01 4~20mA
Setting
Group 4 Input Function Parameters
Functions
Descriptions
Setting
Functions
Descriptions
Minimum AI2 Analog Input
Page
1st Analog Input Frequency Gain
05 - 15 PLC Mode
Group 5 Multi-step Speed Parameters
settings are
Example 2 Pr.05-15 = 2 Continuously executes program cycles
Example 3 Pr.05-15 = 3 Execute one cycle step by step
Weights 0=Forward 1=Reverse
Chapter 4 Parameters
Bit 0 1 0 0 1 1
0 0 1 1 1
Time Duration of 1st Step Speed
Frequency
9 1011 12
Multi-Step Speed via External Terminals
Chapter 4 Parameters
Settings
Factory Setting 150%
Time
Over-current Stall Prevention during Acceleration
Over-current Stall Prevention during Acceleration
Over-current Stall Prevention during Operation
06 - 03 Over-torque Detection Selection
80 100 120 140 160
Operation
5 Timemin
Load
Settings
42 CC,OC hardware error HPF2 43 OC hardware error HPF3
Group 7 AC Drive and Motor Parameters
No-load Current of Motor
Rated Slip Frequency of Motor
This parameter could display running time of the motor
Group 8 Special Parameters
DC Braking Time
Momentary Power Loss Operation
V/f curve setting
Output frequency
Output voltage
08-07 output current
Auto Restart Time after Fault
Settings
00 AVR function enabled
01 AVR function disabled
02 AVR function disabled for deceleration
Settings
Factory Setting
Vibration Compensation Factor
Unit
Group 9 Communication Parameters
09 - 05 Even/Odd Parity and Stopping Parity Setting Factory Setting
1 EV 2 GND 3 SG- 4 SG+ 5 NC 6 1 6 for communication
Character ASCII Code Character ASCII Code
ASCII mode
RTU mode
ASCII mode
RTU mode
ASCII mode
RTU mode
ASCII mode
RTU mode Command message
ASCII mode
RTU mode
ASCII mode
RTU mode
Command message ADR CMD Data starting address Number of data word
3.5 Address list
Content
Content
ASCII mode
RTU mode
The explanation of exception codes
Page
Proportional Gain P
Primary Low Pass Filter Time
V/F Curve Diagram
01-02 Voltage%
Frequency
0 20 40 60 80
This page intentionally left blank
Chapter 4 Parameters
4-90
Revision July 2008, EG03, SW
Chapter 5 Troubleshooting
5.1 Over Current OC
o cd
Ov er-curre nt dur ing ac celeratio n
5.2 Ground Fault
5.3 Over Voltage OV
Ground fault
Remove ground fault
5.4 Low Voltage Lv
Is input power correct? Or power cut, Yes
including momentary power loss
Restart after reset
5.5 Over Heat OH
5.6 Overload
Reduce load or increase the power of AC motor drive
Chapter 5 Troubleshooting
5.8 Phase Loss PHL
5.7 Keypad Display is Abnormal
Abnormal display or no display Yes Cycle power to AC motor drive
Fix connector and eliminate noise No
5.9 Motor cannot Run
Chapter 5 Troubleshooting
Revision July 2008, EG03, SW
5.10 Motor Speed cannot be Changed
Chapter 5 Troubleshooting
Check to see if frequency is
out of range upper/lower
5.11 Motor Stalls during Acceleration
5.12 The Motor does not Run as Expected
Chapter 5 Troubleshooting
settings
5.13 Electromagnetic/Induction Noise
5.14 Environmental Condition
5.15 Affecting Other Machines
serial reactor phase lead capacitor
Chapter 6 Fault Code Information and Maintenance
6.1 Fault Code Information
6.1.1 Common Problems and Solutions
Fault
Fault Descriptions
Chapter 6 Fault Code Information and Maintenance
Corrective Actions
Fault
Fault Descriptions
Corrective Actions
Name
Fault
Fault Descriptions
Corrective Actions
Name
6.1.2 Reset
6.2 Maintenance and Inspections
Daily Inspection
Periodic Inspection
Periodical Maintenance Ambient environment
Maintenance
Maintenance
DANGER
Keypad
Terminals and wiring of main circuit
Transformer and reactor of main circuit
Maintenance
Maintenance
Cooling fan of cooling system
Check Items
Appendix A Specifications
General Specifications
Appendix A Specifications
General Specifications
Environment
Appendix B Accessories
B.1 All Brake Resistors & Brake Units Used in AC Motor Drives
9. Definition for Brake Usage ED%
Appendix B Accessories
VFD Series
B.2 Non-fuse Circuit Breaker Chart
B.3 Fuse Specification Chart
B.4 AC Reactor
B.4.1 AC Input Reactor Recommended Value 460V, 50/60Hz, 3-Phase
460V DC Choke
B.4.2 AC Output Reactor Recommended Value
460V, 50/60Hz, 3-Phase
B.4.3 Applications
Switching spikes will be generated when the
connected to the same power
Correct wiring
power
large-capacity
small-capacity
AC motor drive
B.5 Zero Phase Reactor RF220X00A
Diagram A
Diagram B
B.6 PU06 B.6.1 Description of the Digital Keypad VFD-PU06
B.6.2 Explanation of Display Message
RESET
STOP
B.6.3 PU06 Operation Flow Chart
VFD-PU06 Operation Flow Chart
XX-XX
XXXXX -ERR- -END
Appendix C How to Select the Right AC Motor Drive
Related Specification
C.1 Capacity Formulas
n T I M ⎢
k ⋅ IM ≤ the rated current of AC motor drive A
1.5 the rated current of AC motor drive A
Symbol explanation
C.2 General Precaution
Parameter Settings Note
Selection Note
C.3 How to Choose a Suitable Motor
torque%
25% 40% 60% 100
continuous
To avoid resonances, use the Skip frequencies
Special motors
60 seconds
torque
Frequency Hz
Base freq. 60Hz
Appendix C How to Select the Right AC Motor Drive
This page intentionally left blank