Chapter 4 Parameters

Group 4: Input Function Parameters

04 - 00 Multi-function Input terminal 1

04 - 01

04 - 02

04 - 03

Factory Setting: 01

Multi-function Input terminal 2

Factory Setting: 02

Multi-function Input terminal 3

Factory Setting: 03

Multi-function Input terminal 4

Settings

00~31

Factory Setting: 04

 

Setting

Functions

Descriptions

00

Disabled

All unused terminals should be set to 00, to assure they

 

 

 

have no effect on drive operation.

 

01

Multi-Speed terminal 1

Allows selection of the 15 multi-step speeds. Please refer

 

02

Multi-Speed terminal 2

to 05-00 to 05-14 to program the 15 step speeds.

 

 

03

Multi-Speed terminal 3

 

 

04

Multi-Speed terminal 4

 

05

Reset (NO)

Clears (Reset) a fault and returns the AC drive to normal

 

 

 

operation.

06

Reset (NC)

 

07

Jog operation (JOG)

Enables the JOG command. Works identical to the JOG

 

 

 

key on the digital keypad.

08

Accel/Decel disable

Stops the acceleration or deceleration of the AC drive. AC

 

 

 

drive then maintains a constant speed.

09

1st and 2nd Accel/Decel

A corresponding terminal set to value 09 and closed

 

 

selection

selects Accel/Decel time 2. A corresponding terminal set

10

3rd and 4th Accel/Decel

to value 10 and closed selects Accel/Decel time 3.

Accel/Decel time 4 is selected when both terminals are

 

 

selection

 

 

 

closed.

 

11

B.B. (NO) input

Enables the base block (pause) function.

 

12

B.B. (NC) input

Please refer to Pr.08-08, for base block functions.

13

Increase Frequency

Enables the external terminals to increase or decrease the

 

 

 

Master Frequency command each time an input is

14

Decrease Frequency

received. Terminals are not active during a stop

 

 

 

 

 

 

command.

15

Emergency stop (NO)

Generates an external fault (EF1). The function is identical

 

 

 

to the external terminal (EF).

16

Emergency stop (NC)

 

17

KEYPAD(open),

External selection of the Operation Command Source.

 

 

EXT(close)

(Keypad = terminal open) or (External terminals = terminal

 

 

 

closed). This setting is valid when Pr.02-01 is set to 00.

 

 

 

Otherwise, the Operation Command Source will follow the

 

 

 

setting in Pr.02-01.

Revision July 2008, EG03, SW V1.06

4-41

Page 92
Image 92
Delta Electronics VFD-G manual Group 4 Input Function Parameters, Setting Functions Descriptions