Delta Electronics VFD-G manual 06 - 03 Over-torque Detection Selection

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 105
Image 105
06 - 03 Over-torque Detection Selection

Chapter 4 ParametersManual background

06 - 03 Over-torque Detection Selection

 

Factory Setting: 00

Settings

00: Over-torque detection disabled.

 

01: Over-torque detection enabled during constant speed operation (OL2),

 

and operation continues.

 

02: Over-torque detection enabled during constant speed operation (OL2),

 

and operation halted.

 

03: Over-torque detection enabled during operation (OL2), and operation

 

continues.

 

04: Over-torque detection enabled during constant speed operation (OL2),

 

and operation halted.

This parameter selects the Over-torque Detection operation.

If this parameter is set to 01 or 02, over-torque detection will not occur during acceleration.

 

06 - 04

 

Over-torque Detection Level

Unit: 1

 

 

 

Settings

30~150%

Factory Setting: 110

 

 

 

 

 

 

This parameter sets the Over-torque Detection level based on the AC drive rated current.

 

06 - 05

 

Over-torque Detection Time

Unit: 0.1

 

 

 

Settings

0.1~60.0 Sec

Factory Setting: 0.1

This parameter selects the allowable time of Over-torque Detection before the AC drive faults

with an OL2.

When the output current exceeds Pr.06-04 for the time set in Pr06-05, AC drive will fault and

display “OL2” on the keypad.

06 - 06 Electronic Thermal Relay Selection

 

Factory Setting: 02

Settings

00: Operation disabled.

 

01: Operation with a standard motor (shaft mounted fan cooled).

02:Operation with a vector motor (non-fan cooled or self powered fan) This parameter provides electronic thermal protection for the motor. When the output current exceeds Pr.07-02 for the time set in Pr.06-07, the drive will fault with an OL1.

06 - 07

Electronic Thermal Characteristic

Unit: 1

 

Settings

30~600 Sec

Factory Setting: 60

 

 

 

 

This parameter selects the time required for the electronic thermal protection function to

activate.

4-54

Revision July 2008, EG03, SW V1.06

Page 105
Image 105
Delta Electronics VFD-G manual 06 - 03 Over-torque Detection Selection