Chapter 4 Parameters

Group 7: AC Drive and Motor Parameters

07 - 00 Identity Code of AC Drive

Settings Display by model typeFactory Setting: ## This parameter displays the AC drive model code.

This parameter is read-only.

07 - 01 Rated Current of AC Drive

Settings Display by model typeFactory Setting: ## This parameter displays rated output current of the AC drive. The following chart may be used to look up the identity code, current, and hp of your drive.

kW

5.5

7.5

11

15

18.5

22

30

37

45

55

75

90

110

132

160

185

220

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP

7.5

10

15

20

25

30

40

50

60

75

100

125

150

175

215

250

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr.07-00

13

15

17

19

21

23

25

27

29

31

33

35

37

39

41

43

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated Current (A)

13

18

24

32

38

45

60

73

91

110

150

180

220

260

310

370

460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Carried Freq.

6kHz

 

6kHz

 

 

 

6kHz

 

 

 

 

4kHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min. Carried Freq.

4kHz

 

3kHz

 

 

 

2kHz

 

 

 

 

2kHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting

6kHz

 

6kHz

 

 

 

4kHz

 

 

 

 

4kHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This parameter is read-only.

 

 

 

 

07 - 02

Full-load Current of Motor

Unit: 1

 

Settings

30~120%

Factory Setting: 100%

 

 

 

 

This parameter selects the full load current of the motor.

Pr7-02 = (full load motor current / drive rated current)

Example: If the rated current of AC drive is 150A, full-load current of motor is 120A, then Pr.7- 02 should be set to 80%.

This parameter is used with slip compensation Pr.7-04 to Pr.7-05 and electronic thermal relay Pr.6-06 to Pr.6-07. An incorrect setting will cause these functions to not work incorrectly and may damage the motor and drive.

The full-load current of the motor must be equal to or less than (but not less than 50%) the rated current of the AC drive.

4-58

Revision July 2008, EG03, SW V1.06

Page 109
Image 109
Delta Electronics VFD-G manual Group 7 AC Drive and Motor Parameters, 18.5 110 132 160 185 220