Chapter 4 Parameters

 

Setting

 

Functions

 

Descriptions

 

 

17

 

PID feedback error

 

The corresponding output will be closed when the PID

 

 

 

 

indication

 

 

feedback signal has an error.

 

 

18

 

Auto Running Command

 

The Output will be closed when PLC Program is running.

 

 

 

 

 

 

 

 

 

19

 

1-Step Running

 

The Output will be closed for 0.5 sec when each multi-step

 

 

Completed

 

 

speed is attained.

 

 

 

 

 

 

 

 

 

20

 

Auto Running Completed

 

The output will be closed for 0.5 sec when the PLC

 

 

 

program cycle has completed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

Auto Running Paused

 

The output will be closed when PLC operation is paused.

 

 

Standard relay specifications = 10A/250VAC or 12A/24VDC.

 

 

 

Relay delay time is 5~10 msec.

 

 

 

 

 

 

 

 

 

 

 

 

 

03 - 01

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03 - 02

Master Frequency Attained 1

 

 

Unit: 0.01

 

 

 

 

 

 

 

 

 

 

 

 

03 - 03

Master Frequency Attained 2

 

 

Unit: 0.01

 

 

 

Settings

0.00~160.00 Hz

Factory Setting: 0.00

 

 

 

 

 

 

 

 

 

 

 

An output relay may be programmed to activate when the output frequency exceeds the desired attained frequency setting of these two parameters.

There is a ± 2Hz window of operation. If the master frequency attained is 20Hz and the output frequency exceeds 20Hz, the corresponding output relay will be “closed”. When the output frequency is less than 18Hz, the corresponding output relay will be “opened” as the following diagram shows.

Frequency 2Hz

 

 

2Hz

 

Master

2Hz

 

4Hz

frequency 1

 

Frequency

 

 

command

 

 

Master

 

 

frequency 2

 

 

Time

 

Output frequency

Master frequency 2 attained

Master frequency 1 attained

Master frequency attained

4-38

Revision July 2008, EG03, SW V1.06

Page 89