Chapter 4 Parameters

RTU mode:

Command message:

ADR

01H

CMD

06H

 

 

data

01H

 

 

Starting address

00H

data

17H

 

00H

 

 

CRC CHK LOW

87H

CRC CHK HIGH

C6H

 

 

Response message:

ADR

01H

CMD 1

06H

 

 

data

01H

 

 

Starting address

00H

data

17H

 

70H

 

 

CRC CHK LOW

87H

CRC CHK HIGH

C6H

 

 

Error response message

ADR

01H

CMD 1

86H

 

 

Error code

02

 

 

CRC CHK LOW

C3H

CRC CHK HIGH

A1H

Command code: 08H, loop detection

This command is used to test the communication condition between master control

equipment (usually is PC or PLC) and AC drive. AC drive will deliver the data that received

from AC drive to master control equipment.

For example:

ASCII mode:

Command message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘0’

CMD 0

‘8’

 

 

data

‘0’

Starting

‘0’

address

‘0’

 

‘0’

data

‘1’

 

‘7’

 

 

 

‘7’

 

‘0’

LRC CHK 1

‘7’

LRC CHK 0

‘0’

END 1

CR

END 0

LF

 

 

Response message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘0’

CMD 0

‘8’

 

 

data

‘0’

Starting

‘0’

 

‘0’

 

‘0’

data

‘1’

 

‘7’

 

 

 

‘7’

 

‘0’

LRC CHK 1

‘7’

LRC CHK 0

‘0’

END 1

CR

END 0

LF

 

 

Error response message

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘8’

CMD 0

‘8’

 

 

Error

‘0’

code

‘2’

LRC CHK 0

‘6’

LRC CHK 1

‘D’

END 1

CR

END 0

LF

 

 

4-76

Revision July 2008, EG03, SW V1.06

Page 127
Image 127
Delta Electronics VFD-G manual C6H