Delta Electronics VFD-G manual Parameter

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 62
Image 62
Manual background

Chapter 4 ParametersManual backgroundManual backgroundManual backgroundManual backgroundManual background

 

Parameter

 

 

Functions

Settings

Factory

Customer

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

05 - 20

Time Duration Step 4

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 21

Time Duration Step 5

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 22

Time Duration Step 6

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 23

Time Duration Step 7

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 24

Time Duration Step 8

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 25

Time Duration Step 9

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 26

Time Duration Step 10

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 27

Time Duration Step 11

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 28

Time Duration Step 12

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 29

Time Duration Step 13

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 30

Time Duration Step 14

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

 

 

05 - 31

Time Duration Step 15

0.0 to 65500 Sec / 0.0~6550.0 Sec

0.0

 

 

05-32

 

 

Time Unit Settings

00: 1 Sec

00

 

 

 

 

 

 

 

01: 0.1 Sec

 

 

 

Group 6 Protection Function Parameters

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

Functions

Settings

Factory

Customer

 

 

 

 

 

 

 

Setting

 

 

06-00

 

Over-voltage Stall

660.0V~820.0VDC

780.0

 

 

 

 

 

Prevention

00: Disabled

 

 

 

06-01

 

Over-current Stall

20~250%

150%

 

 

 

 

 

Prevention during

00: Disabled

 

 

 

 

 

 

Acceleration

 

 

 

 

06-02

 

Over-current Stall

20~250%

150%

 

 

 

 

 

Prevention during

00: Disabled

 

 

 

 

 

 

operation

 

 

 

 

06-03

 

Over-torque Detection

00: Over-torque detection disabled.

00

 

 

 

 

 

Selection

01: Over-torque detection enabled during

 

 

 

 

 

 

 

 

constant speed operation (OL2), and

 

 

 

 

 

 

 

 

operation continues.

 

 

 

 

 

 

 

 

02: Over-torque detection enabled during

 

 

 

 

 

 

 

 

constant speed operation (OL2), and

 

 

 

 

 

 

 

 

operation halted.

 

 

 

 

 

 

 

 

03: Over-torque detection enabled during

 

 

 

 

 

 

 

 

operation (OL2), and operation

 

 

 

 

 

 

 

 

continues.

 

 

 

 

 

 

 

 

04: Over-torque detection enabled during

 

 

 

 

 

 

 

 

operation (OL2), and operation halted.

 

 

 

06-04

 

Over-torque Detection

30~150%

110

 

 

 

 

 

Level

 

 

 

 

06-05

 

Over-torque Detection

0.1~60.0 Sec

0.1

 

 

 

 

 

Time

 

 

 

 

Revision July 2008, EG03, SW V1.06

4-11

Page 62
Image 62
Delta Electronics VFD-G manual Parameter