Chapter 4 Parameters

When the over-current stall prevention is activated, the acceleration time of the AC drive will be longer than the time set in Pr. 01-09.

Over-current Stall

 

 

Prevention during

 

Current

acceleration

 

 

 

06-01

 

 

 

 

Output

 

 

frequency

 

Over-current stall

 

prevention during

 

acceleration,

 

frequency held

 

Time

Over-current Stall Prevention during Acceleration

06 - 02

Over-current Stall Prevention during operation

Unit: 1

 

Settings

20~250%

Factory Setting: 150%

 

 

 

 

This parameter selects the percentage of allowable over-current during operation before the stall prevention function is enabled.

If the output current exceeds the value specified in Pr.06-02 when the drive is operating at steady state speed, the drive will decrease its output frequency to prevent the drive from faulting with an OC. Once the current falls below the value specified in Pr.06-02, the drive will then accelerate to catch up with the command frequency.

Over-current Stall Prevention during operation 06-02

Current

Over-current Stall Prevention during operation, output frequency decrease

Output frequency

Time

Over-current Stall Prevention during Operation

Revision July 2008, EG03, SW V1.06

4-53

Page 104
Image 104
Delta Electronics VFD-G manual 06-01