Delta Electronics VFD-G manual B.4 AC Reactor, 460V DC Choke

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 169
Image 169
B.4 AC Reactor

Appendix B AccessoriesB.4.1 AC Input Reactor Recommended Value 460V, 50/60Hz, 3-Phase460V DC ChokeManual backgroundManual backgroundManual background

B.4 AC Reactor

B.4.1 AC Input Reactor Recommended Value 460V, 50/60Hz, 3-Phase

kW

HP

Fundamental

Max. continuous

Inductance (mh)

Amps

Amps

3% impedance

5% impedance

 

 

5.5

7.5

12

18

2.5

4.2

7.5

10

18

27

1.5

2.5

11

15

25

37.5

1.2

2

15

20

35

52.5

0.8

1.2

18.5

25

35

52.5

0.8

1.2

22

30

45

67.5

0.7

1.2

30

40

55

82.5

0.5

0.85

37

50

80

120

0.4

0.7

45

60

80

120

0.4

0.7

55

75

100

150

0.3

0.45

75

100

130

195

0.2

0.3

90

125

160

240

0.15

0.23

110

150

200

300

0.11

0.185

132

175

250

375

0.09

0.15

160

215

320

480

0.075

0.125

185

250

400

560

0.06

0.105

220

300

500

700

0.05

0.085

460V DC Choke

Input Voltage

kW

HP

DC Amps

 

5.5

7.5

18

 

7.5

10

25

 

11

15

32

 

15

20

50

18.5kW~132kW(25HP~175HP): Built-in DC Reactor

160kW~220kW(215HP~300HP): Built-in AC Reactor

Inductance (mh)

3.75

4.00

2.68

2.00

B-6

Revision July 2008, EG03, SW V1.06