Delta Electronics VFD-G manual Parameter

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 65
Image 65
Manual background

Chapter 4 ParametersManual backgroundManual backgroundManual backgroundManual backgroundManual background

 

Parameter

Functions

Settings

Factory

Customer

 

 

Setting

 

 

 

 

 

 

 

07-08

Calculate Total

00 to 1439 Min

00

 

 

 

 

Running Time of the

 

 

 

 

 

 

Motor (Min)

 

 

 

 

 

 

 

 

 

 

07-09

Calculate Total

00 to 65535 Day

00

 

 

 

 

Running Time of the

 

 

 

 

 

 

Motor (Day)

 

 

 

 

 

 

 

 

 

 

07-10

Electric Bill for One

Read Only

Read

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

07-11

Accumulated Electric

Read Only

Read

 

 

 

 

Bill (per currency unit)

 

 

 

 

 

 

 

 

 

07-12

Accumulated Electric

Read Only

 

 

 

 

 

Bill (per 104 currency

 

Read

 

 

 

 

unit)

 

 

 

 

07-13

Electric Rate (per

0.01 to 655.35

0.6

 

 

 

 

currency unit)

 

 

 

 

Group 8 Special Parameters

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

Functions

Settings

Factory

Customer

 

 

Setting

 

 

 

 

 

 

 

08-00

DC Braking Current

00~100%

00

 

 

 

 

Level

 

 

 

 

08-01

DC Braking Time

0.0~60.0 Sec

0.0

 

 

 

 

during Start-up

 

 

 

 

08-02

DC Braking Time

0.00~60.00 Hz

0.0

 

 

 

 

during Stopping

 

 

 

 

08-03

Start-point for DC

0.00~160.00 Hz

0.00

 

 

 

 

Braking

 

 

 

 

08-04

Momentary Power

00: Disable

00

 

 

 

 

Loss Operation

01: Trace from top downward

 

 

 

 

 

Selection

02: Trace from bottom upward

 

 

 

 

 

 

 

 

 

08-05

Maximum Allowable

0.1~5.0 Sec

2.0

 

 

 

 

Power Loss Time

 

 

 

 

08-06

Speed Search Time

0.1~5.0 Sec

0.5

 

 

08-07

Maximum Speed

30~150%

110

 

 

 

 

Search Current

 

 

 

 

08-08

BB speed search

00: Trace from top downward

00

 

 

 

 

method

01: Trace from bottom upward

 

 

 

08-09

Auto Restart Times

00~10

00

 

 

 

 

after Fault

 

 

 

 

 

08-10

Auto Restart Time after

00 to 60000 sec

600

 

 

 

 

Fault

 

 

 

 

4-14

Revision July 2008, EG03, SW V1.06

Page 65
Image 65
Delta Electronics VFD-G manual Parameter