Group 10 PID Control Parameters

Chapter 4 ParametersManual backgroundManual backgroundManual backgroundManual backgroundManual background

Group 10 PID Control Parameters

 

Parameter

Functions

Settings

Factory

Customer

 

 

Setting

 

 

 

 

 

 

 

10-00

Input Terminal for PID

00: Disabled

00

 

 

 

 

Feedback

01: Input via AI1

 

 

 

 

 

 

02: Input via AI2

 

 

 

 

 

 

03: Input via External Reference

 

 

 

10-01

PID Control Detection

1.0-6550.0

1000.0

 

 

 

 

Signal Reference

 

 

 

 

10-02

PID Feedback Control

00: Normal (Err=SP-FB)

00

 

 

 

 

Method

01: Inverse (Err=FB-SP)

 

 

 

10-03

Proportional Gain (P)

0.0~10.0

1.0

 

 

10-04

Integral Time (I)

0.00~100.00 Sec

1.00

 

 

10-05

Differential Time (D)

0.00~1.00 Sec

0.00

 

 

10-06

Upper Bound for

00~200%

100

 

 

 

 

Integral Control

 

 

 

 

10-07

Primary Low Pass

0.0~2.5 Sec

0.0

 

 

 

 

Filter Time

 

 

 

 

10-08

PID Feedback Signal

0.01 to 10-01

600.0

 

 

 

 

Range

 

 

 

 

10-09

PID Feedback Signal

0. 0~3600.0 Sec

0.0

 

 

 

 

Fault Treatment Time

0.0: Disabled

 

 

 

10-10

PID Feedback Signal

00: Warn and RAMP stop

01

 

 

 

 

Fault Treatment

01: Warn and COAST stop

 

 

 

 

 

 

02: Warn and keep operating

 

 

 

10-11

V/F Curve Selection

00: Determined by group 01

00

 

 

 

 

 

01: 1.5 power curve

 

 

 

 

 

 

02: 1.7 power curve

 

 

 

 

 

 

03: 2 power curve

 

 

 

 

 

 

04: 3 power curve

 

 

 