Group 9: Communication Parameters

09 - 00 Communication Address

Factory Setting: 01

Settings 01-254

00: Disabled

If the AC drive is controlled by RS-485 serial communication, the communication address for

this drive must be set via this parameter.

09 - 01 Transmission Speed (Baud Rate)

Factory Setting: 01

Settings

00: Baud rate 4800

 

01: Baud rate 9600

 

02: Baud rate 19200

 

03: Baud rate 38400

This parameter determines transmission speed of AC drive communication.

09 - 02 Transmission Fault Treatment

Factory Setting: 03

Settings

00: Warn and keep operating

 

01: Warn and RAMP to stop

 

02: Warn and COAST to stop

 

03: No warning and no display

 

 

This parameter is set to detect if an error occurs and take actions.

09 - 03 Time-out Detection during Transmission

Factory Setting: 00

Settings

00: Disabled

 

01: Enabled

 

 

This parameter is used for ASCII mode. When this parameter is set to 01, indicates that the

time-out detection is enable, the time slot between each character can’t exceed 500 ms.

09 - 04 Communication Format

Factory Setting: 00

Settings

00: 7-bit for ASCII

 

01:

8-bit for ASCII

 

02:

8-bit for RTU

 

 

 