Chapter 4 Parameters
Group 9: Communication Parameters
09 - 00 Communication Address
Factory Setting: 01
Settings
00: Disabled
If the AC drive is controlled by
this drive must be set via this parameter.
09 - 01 Transmission Speed (Baud Rate)
Factory Setting: 01
Settings | 00: Baud rate 4800 |
| 01: Baud rate 9600 |
| 02: Baud rate 19200 |
| 03: Baud rate 38400 |
This parameter determines transmission speed of AC drive communication.
09 - 02 Transmission Fault Treatment
Factory Setting: 03
Settings | 00: Warn and keep operating |
| 01: Warn and RAMP to stop |
| 02: Warn and COAST to stop |
| 03: No warning and no display |
|
|
This parameter is set to detect if an error occurs and take actions.
09 - 03
Factory Setting: 00
Settings | 00: Disabled |
| 01: Enabled |
|
|
This parameter is used for ASCII mode. When this parameter is set to 01, indicates that the
09 - 04 Communication Format
Factory Setting: 00
Settings | 00: | |
| 01: | |
| 02: | |
|
|
|
Revision July 2008, EG03, SW V1.06 |