RTU mode: Command message:
ADR  | 01H  | 
CMD  | 08H  | 
  | 
  | 
data  | 00H  | 
  | 
  | 
Starting address  | 00H  | 
data  | 17H  | 
  | 70H  | 
  | 
  | 
CRC CHK LOW  | EEH  | 
CRC CHK HIGH  | EFH  | 
  | 
  | 
Response message:  | 
  | |
ADR  | 
  | 01H  | 
CMD 1  | 
  | 08H  | 
  | 
  | 
  | 
data  | 
  | 00H  | 
Starting address  | 
  | 00H  | 
data  | 
  | 17H  | 
  | 
  | 70H  | 
  | 
  | 
  | 
CRC CHK LOW  | 
  | EEH  | 
CRC CHK HIGH  | 
  | EFH  | 
  | 
  | 
  | 
Chapter 4 Parameters
Error response message
ADR  | 01H  | 
CMD 1  | 88H  | 
  | 
  | 
Error code  | 02  | 
  | 
  | 
CRC CHK LOW  | E0H  | 
CRC CHK  | 6DH  | 
HIGH | 
  | 
  | 
  | 
●Command code: 10H, write continuous words
For example, modify 
ASCII mode:
Command message:
STX  | ‘:’  | 
ADR 1  | ‘0’  | 
ADR 0  | ‘1’  | 
CMD 1  | ‘1’  | 
CMD 0  | ‘0’  | 
Data  | ‘0’  | 
Starting  | ‘5’  | 
address  | ‘0’  | 
  | ‘0’  | 
Number  | ‘0’  | 
Of  | ‘0’  | 
data  | ‘0’  | 
(Word)  | ‘2’  | 
Number of  | ‘0’  | 
data (Byte)  | ‘4’  | 
The first  | ‘1’  | 
data  | ‘3’  | 
  | ‘8’  | 
  | ‘8’  | 
The second  | ‘0’  | 
data  | ‘F’  | 
  | ‘A’  | 
  | ‘0’  | 
Response message:
STX  | ‘:’  | 
ADR 1  | ‘0’  | 
ADR 0  | ‘1’  | 
CMD 1  | ‘1’  | 
CMD 0  | ‘0’  | 
Data  | ‘0’  | 
address  | ‘5’  | 
  | ‘0’  | 
  | ‘0’  | 
Number  | ‘0’  | 
Of  | ‘0’  | 
data  | ‘0’  | 
(Word)  | ‘2’  | 
LRC CHK 1  | ‘E’  | 
LRCCHK 0  | ‘8’  | 
END 1  | CR  | 
END 0  | LF  | 
Error response message
STX  | ‘:’  | 
ADR 1  | ‘0’  | 
ADR 0  | ‘1’  | 
CMD 1  | ‘9’  | 
CMD 0  | ‘0’  | 
Error  | ‘0’  | 
code  | ‘2’  | 
LRC CHK 0  | ‘6’  | 
LRC CHK 1  | ‘D’  | 
END 1  | CR  | 
END 0  | LF  | 
Revision July 2008, EG03, SW V1.06  |