Delta Electronics VFD-G manual Parameter, Functions, Settings, Factory, Customer

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 67
Image 67
Manual background

Chapter 4 ParametersManual backgroundManual backgroundManual backgroundManual backgroundManual background

 

Parameter

Functions

Settings

Factory

Customer

 

 

Setting

 

 

 

 

 

 

 

09-05

Even/Odd Parity and

00: None parity + 2 stop bit

00

 

 

 

 

Stopping Parity Setting

01: Even parity + 2 stop bit

 

 

 

 

 

 

02: Odd parity + 2 stop bit

 

 

 

 

 

 

03: None parity + 1 stop bit

 

 

 

 

 

 

04: Even parity + 1 stop bit

 

 

 

 

 

 

05: Odd parity + 1 stop bit

 

 

 

09-06

Communication

Bit0~1: 00: Disable

00

 

 

 

 

Operation Command 1

01: Stop

 

 

 

 

 

 

10: Start-up

 

 

 

 

 

 

11: JOG start-up

 

 

 

 

 

 

Bit2~3: Reserved

 

 

 

 

 

 

Bit4~5: 00: No function

 

 

 

 

 

 

01: FWD command

 

 

 

 

 

 

10: REV command

 

 

 

 

 

 

11: Change direction command

 

 

 

 

 

 

Bit6~7: 00: 1st step accel/decel speed

 

 

 

 

 

 

01: 2nd step accel/decel speed

 

 

 

 

 

 

10: 3rd step accel/decel speed

 

 

 

 

 

 

11: 4th step accel/decel speed

 

 

 

 

 

 

Bit8~11:

 

 

 

 

 

 

0000: Master speed

 

 

 

 

 

 

0001: 1st step speed

 

 

 

 

 

 

0010: 2nd step speed

 

 

 

 

 

 

0011: 3rd step speed

 

 

 

 

 

 

0100: 4th step speed

 

 

 

 

 

 

0101: 5th step speed

 

 

 

 

 

 

0110: 6th step speed

 

 

 

 

 

 

0111: 7th step speed

 

 

 

 

 

 

1000: 8th step speed

 

 

 

 

 

 

1001: 9th step speed

 

 

 

 

 

 

1010: 10th step speed

 

 

 

 

 

 

1011: 11th step speed

 

 

 

 

 

 

1100: 12th step speed

 

 

 

 

 

 

1101: 13th step speed

 

 

 

 

 

 

1110: 14th step speed

 

 

 

 

 

 

1111: 15th step speed

 

 

 

 

 

 

Bit12: Select Bit6~11 function

 

 

 

 

 

 

Bit13~15 Reserved

 

 

 

09-07

Communication

0~160.00Hz

60.00

 

 

 

 

Frequency Setting

 

 

 

 

09-08

Communication

Bit0: 1: EF ON

00

 

 

 

 

Operation Command 2

Bit1: 1: Reset

 

 

 

 

 

 

Bit2: 0: BB OFF, 1: BB ON

 

 

 

 

 

 

Bit3~15: Reserved

 

 

 

4-16