Chapter 4 Parameters

 

 

 

 

 

 

 

 

 

 

 

 

Group 3: Output Function Parameters

 

 

 

 

 

 

 

 

 

03 - 00

Multi-function Output terminal 1 (Relay)

 

 

Settings

00-21

 

Factory Setting: 01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

Functions

Descriptions

 

 

00

 

Disabled

 

 

 

 

 

 

01

 

Indication during

The corresponding output will be closed during operation

 

 

 

operation

 

(including DC braking time).

 

02

 

Master frequency

The corresponding output will be closed when output

 

 

 

attained

 

frequency reaches master frequency command.

 

03

 

Zero Speed (including

The corresponding output will be closed when the AC drive

 

 

 

shutdown)

 

has no output voltage signal.

 

04

 

Over-torque

 

The corresponding output relay will be closed when the AC

 

 

 

 

 

drives output current exceeds the over-torque detection

 

 

 

 

 

level 06-04.

 

05

 

External Fault

The corresponding output will be closed when the EF is

 

 

 

 

 

enabled. (Pr. 04-00 to 04-03)

 

06

 

Low voltage detection

The corresponding output will be closed when the DC Bus

 

 

 

 

 

voltage drops below our threshold. The keypad will display

 

 

 

 

 

“Lu”.

 

07

 

Operation Mode

The corresponding output will be closed when the AC

 

 

 

indication

 

drives “Operation Command” is controlled by the external

 

 

 

 

 

terminals.

 

08

 

Fault Indication

The corresponding output will be closed when AC drive

 

 

 

 

 

has experienced a fault.

 

09

 

Master Frequency

The corresponding output will be closed when the AC

 

 

 

Attained 1

 

drives output frequency exceeds (Pr.03-08) Master

 

 

 

 

 

Frequency Attained 1.

 

10

 

Master Frequency

The corresponding output will be closed when the AC

 

 

 

Attained 2

 

drives output frequency exceeds (Pr.03-09) Master

 

 

 

 

 

Frequency Attained 2.

 

11

 

Over Temperature

The corresponding output will be closed when the AC drive

 

 

 

indication

 

temperature exceeds its rating.

 

12

 

Drive Ready

The corresponding output will be closed the when the AC

 

 

 

 

 

drive is ready and has no faults.

 

13

 

External Emergency Stop

The corresponding output will be closed when multi-

 

 

 

(EF1)

 

function input terminals (Pr.04-00 to 04-03) are set to

 

 

 

 

 

emergency stop and then activated.

 

14

 

Software braking output

The corresponding output will be closed when the AC

 

 

 

 

 

drives DC bus voltage exceeds (Pr.08-19) the braking

 

 

 

 

 

level.

 

15

 

OL or OL1 overload

The corresponding output will be closed upon an overload

 

 

 

warning

 

(OL or OL1) fault.

 

16

 

Low current indication

The corresponding output will be closed when the AC

 

 

 

 

 

drives output current is lower than the Low Current setting

 

 

 

 

 

(Pr.06-08).

 