08-11

Operation Frequency

0.00~160.00 Hz

0.00

 

 

 

 

Inhibition 1 UP

 

 

 

 

08-12

Operation Frequency

0.00~160.00 Hz

0.00

 

 

 

 

Inhibition 1 DOWN

 

 

 

 

08-13

Operation Frequency

0.00~160.00 Hz

0.00

 

 

 

 

Inhibition 2 UP

 

 

 

 

08-14

Operation Frequency

0.00~160.00 Hz

0.00

 

 

 

 

Inhibition 2 DOWN

 

 

 

 

08-15

Operation Frequency

0.00~160.00 Hz

0.00

 

 

 

 

Inhibition 3 UP

 

 

 

 

08-16

Operation Frequency

0.00~160.00 Hz

0.00

 

 

 

 

Inhibition 3 DOWN

 

 

 

 

08-17

Automatic Energy-

00: Energy-saving operation disabled

00

 

 

 

 

saving

01: Energy-saving operation enabled

 

 

 

08-18

Automatic Voltage

00: AVR function enabled

00

 

 

 

 

Regulation (AVR)

01: AVR function disabled

 

 

 

 

 

 

 

02: AVR function disabled for deceleration

 

 

 

08-19

Software Setting of the

740V~820VDC

760

 

 

 

 

Braking Level (the

00:Disabled

 

 

 

 

 

action level of the

 

 

 

 

 

 

braking resistor)

 

 

 

 

08-20

Vibration

00~1000

00

 

 

 

 

Compensation Factor

 

 

 

 

Group 9 Communication Parameters

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

Functions

Settings

Factory

Customer

 

 

 

 

 

 

Setting

 

 

09-00

Communication

01-254

01

 

 

 

 

 

Address

00:Disabled

 

 

 

09-01

Transmission Speed

00: Baud rate 4800

01

 

 

 

 

 

(Baud Rate)

01: Baud rate 9600

 

 

 

 

 

 

 

02: Baud rate 19200

 

 

 

 

 

 

 

03: Baud rate 38400

 

 

 

09-02

 

Transmission Fault

00: Warn and keep operating

03

 

 

 

 

 

Treatment

01: Warn and RAMP to stop

 

 

 

 

 

 

 

02: Warn and COAST to stop

 

 

 

 

 

 

 

03: No warning and no display

 

 

 

09-03

 

Over Time Detection

00: Disabled

00

 

 

 

 

 

during Transmission

01: Enabled

 

 

 

09-04

Communication

00: 7-bit for ASCII

00

 

 

 

 

 

Format

01: 8-bit for ASCII

 

 

 

 

 

 

 

02: 8-bit for RTU

 

 

 