Chapter 4 Parameters |
|
|
| |
|
|
| ||
01 - 19 | JOG Frequency | Unit: 0.1sec | ||
| Settings | 0.0 Hz~160.00 Hz | Factory Setting: 6.00 | |
|
|
|
|
|
When the JOG function is to be utilized, users need to use the
The accel/decel time of the JOG operation is determined by the JOG accel/decel speed
When the drive is in operation, the JOG command is disabled.
01 - 20 S Curve Delay Time in Accel
01 - 21 S Curve Delay Time in Decel
Settings 0.00~2.50secFactory Setting: 0.00 These parameters enable the S curve. The longer the S curve time period the smoother the transition between speeds.
01 - 22 | Modulation Index | Unit: 0.1 | |
| Settings | 0.90~1.20 | Factory Setting: 1.00 |
|
|
|
|
This parameter sets the ratio of the Maximum Output Voltage to the input voltage.
The Maximum Output Voltage
A Modulation Index of 1, defines the Maximum Output Voltage (Pr.
A Modulation index of 1.2, defines the Maximum Output Voltage (Pr.
01 - 23 Accel/Decel Time Unit
|
| Factory Setting: 01 |
Settings | 00: Unit is 1 Sec | |
| 01: Unit is 0.1 Sec | |
| 02: Unit is 0.01 Sec | |
|
|
|
This parameter sets the resolution of accel/decel time
Revision July 2008, EG03, SW V1.06 |