Chapter 4 Parameters |
|
|
| |
|
|
| ||
08 - 10 | Auto Restart Time after Fault | Unit: 1 | ||
| Settings | 00 to 60000 sec | Factory Setting: 600 | |
|
|
|
|
|
This parameter determines auto restart time after fault. After fault occurs and restart, there is no fault occurs during
08 - 11 | Operation Frequency Inhibition 1 UP | Unit: 0.01 | |
|
|
| |
08 - 12 | Operation Frequency Inhibition 1 DOWN | Unit: 0.01 | |
|
|
| |
08 - 13 | Operation Frequency Inhibition 2 UP | Unit: 0.01 | |
08 - 14 | Operation Frequency Inhibition 2 DOWN | Unit: 0.01 | |
08 - 15 | Operation Frequency Inhibition 3 UP | Unit: 0.01 | |
08 - 16 | Operation Frequency Inhibition 3 DOWN | Unit: 0.01 | |
| Settings | 0.00~160.00 Hz | Factory Setting: 0.00 |
|
|
|
|
These parameters determine the inhibition operation frequency range. This function will let AC drive not run continuous in the resonance frequency of the motor or loading system, or inhibition operation frequency.
The settings of these parameters should follow as
Master frequency command can be set in inhibition operation frequency range. Now the output frequency will be limited in the lower bound of inhibition operation frequency.
When AC drive accelerates or decelerates, output frequency will pass through inhibition operation frequency range.
08 - 17 Automatic
| Factory Setting: 00 |
Settings | 00: |
| 01: |
|
|
This parameter determines automatic
Revision July 2008, EG03, SW V1.06 |