Auto Restart Time after Fault

Chapter 4 Parameters

 

 

 

 

 

 

08 - 10

Auto Restart Time after Fault

Unit: 1

 

Settings

00 to 60000 sec

Factory Setting: 600

 

 

 

 

 

This parameter determines auto restart time after fault. After fault occurs and restart, there is no fault occurs during 08-10 setting time, AC drive will reset fault occurred record to zero.

08 - 11

Operation Frequency Inhibition 1 UP

Unit: 0.01

 

 

 

08 - 12

Operation Frequency Inhibition 1 DOWN

Unit: 0.01

 

 

 

08 - 13

Operation Frequency Inhibition 2 UP

Unit: 0.01

08 - 14

Operation Frequency Inhibition 2 DOWN

Unit: 0.01

08 - 15

Operation Frequency Inhibition 3 UP

Unit: 0.01

08 - 16

Operation Frequency Inhibition 3 DOWN

Unit: 0.01

 

Settings

0.00~160.00 Hz

Factory Setting: 0.00

 

 

 

 

These parameters determine the inhibition operation frequency range. This function will let AC drive not run continuous in the resonance frequency of the motor or loading system, or inhibition operation frequency.

The settings of these parameters should follow as 08-1108-1208-1308-1408-1508- 16.

Master frequency command can be set in inhibition operation frequency range. Now the output frequency will be limited in the lower bound of inhibition operation frequency.

When AC drive accelerates or decelerates, output frequency will pass through inhibition operation frequency range.

08 - 17 Automatic Energy-saving

 

Factory Setting: 00

Settings

00: Energy-saving operation disabled

 

01: Energy-saving operation enabled

 

 

This parameter determines automatic energy-saving function.

4-66