Delta Electronics VFD-G manual Output voltage 01-02, 01-04, 01-06, Output Frequency, 01-07

Models: VFD-G

1 183
Download 183 pages 30.97 Kb
Page 80
Image 80
Output voltage

Chapter 4 Parameters01-04

Output voltage

01-02 01-06Output Frequency01-05 01-08 01-03 01-01 01-0001-07Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

 

01-04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01-06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01-05 01-08 01-03 01-01 01-00

01-07

 

 

 

 

 

 

 

 

 

 

 

01 - 09

Acceleration Time 1

 

 

 

 

Unit: 0.1sec

01 - 10

Deceleration Time 1

 

 

 

 

Unit: 0.1sec

01 - 11

Acceleration Time 2

 

 

 

 

Unit: 0.1sec

01 - 12

Deceleration Time 2

 

 

 

 

Unit: 0.1sec

01 - 13

Acceleration Time 3

 

 

 

 

Unit: 0.1sec

01 - 14

Deceleration Time 3

 

 

 

 

Unit: 0.1sec

01 - 15

Acceleration Time 4

 

 

 

 

Unit: 0.1sec

 

 

 

 

 

 

 

01 - 16

Deceleration Time 4

 

 

 

 

Unit: 0.1sec

01 - 17

JOG Acceleration Time

 

 

 

 

Unit: 0.1sec

01 - 18

JOG Deceleration Time

 

 

 

 

Unit: 0.1sec

 

Settings

 

 

 

 

 

0.1~3600.0 Sec

 

 

 

 

Factory Setting: 10.0/60.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory setting for 30HP and higher models is 60.0 seconds.

Acceleration time is the time required for the AC drive to ramp from 0 Hz to its Maximum Output Frequency (Pr.1-00). Deceleration time is the time required for the AC drive to decelerate from Maximum Output Frequency (Pr.1-00) down to 0 Hz.

An Acceleration or Deceleration time that is too quickly, may cause the AC drives protection features to enable (over-current stall prevention during Accel 06-01 or over-voltage stall prevention 06-00). If this occurs, the actual Accel/Decel time will be longer than this setting. Warning: An acceleration or deceleration that is too quickly, may cause excess loads on the AC drive and may permanently damage the drive.

If you want to decelerate the AC drive in short time period, we recommend adding an external braking module and braking resistor.

You can set 1st to 4th Accel/Decel time via multi-function input terminals 04-00 to 04-03.

Revision July 2008, EG03, SW V1.06

4-29

Page 80
Image 80