Chapter 4 Parameters

02 - 04 Forward/Reverse Enabled

Factory Setting: 00

Settings

00: Forward/Reverse enabled

 

01: Reverse disabled

 

02: Forward disabled

 

 

This parameter enables the direction of the AC drive.

02 - 05 2-wire/3-wire Operation Control Modes

Factory Setting: 00

Settings

00: 2-wire (#1), FWD / STOP, REV / STOP

 

01:

2-wire (#2), RUN/STOP, FWD/REV

 

02:

3-wire operation

 

 

 

This parameter sets the operation mode when operating by external terminals.

Please refer to 02-01.

 

02-05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWD:("OPEN":STOP)

 

00 (2-wire #1)

FWD/STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

("CLOSE":FWD)

 

FWD / STOP

REV/STOP

 

 

 

 

 

 

 

 

 

REV: ("OPEN":STOP)

 

 

 

 

 

 

 

 

 

 

 

REV / STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCM ("CLOSE":REV)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWD:("OPEN":STOP)

 

01 (2-wire #2)

RUN/STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

("CLOSE":RUN)

 

REV / FWD

FWD/REV

 

 

 

 

 

 

 

 

 

 

REV :("OPEN":FWD)

 

 

 

 

 

 

 

 

 

 

 

 

RUN / STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCM ("CLOSE":REV)

 

 

 

 

 

STOP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUN FWD ("CLOSE ":RUN)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02 3-wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EF

("OPEN":S TOP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REV ("OPEN ":FW D)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWD/REV

 

 

 

 

 

 

 

 

 

 

 

 

 

DCM

("CLOSE ":R EV)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFD-G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02 - 06

Line Start Lockout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Setting: 01

 

 

Settings

00: Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01: Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When enabled, the AC drive will not start when powered up with a run command applied. The

AC drive must see the run command transition from stop to run after power up. When Line

Start Lockout is disabled (also known as Auto-Start), the AC drive will start when powered-up

with run commands applied.

4-34

Revision July 2008, EG03, SW V1.06

Page 85
Image 85
Delta Electronics VFD-G manual Vfd-G