Chapter 4 Parameters

3.5Address list:

The contents of available addresses are shown as below:

Content

Address

 

Function

 

 

 

 

AC drive

GGnnH

GG means parameter group, nn means parameter number,

Parameters

 

for example, the address of Pr 04-01 is 0401H. Refer to

 

 

chapter 5 for the function of each parameter. When reading

 

 

parameter by command code 03H, only one parameter can

 

 

be read for one time.

Command

2000H

Bit 0-1

00B: Disabled

Write only

 

 

01B: Stop

 

 

 

10B: Run

 

 

 

11B: Jog + Run

 

 

 

 

 

 

Bit 2-3

Reserved

 

 

Bit 4-5

00B: Disabled

 

 

 

01B: FWD command

 

 

 

10B: REV command

 

 

 

11B: Direction change command

 

 

 

 

 

 

Bit 6-7

00B: 1st step acce/decel speed

 

 

 

01B: 2nd step acce/decel speed

 

 

 

10B: 3rd step acce/decel speed

 

 

 

11B: 4th step acce/decel speed

 

 

 

 

 

 

Bit 8-11

0000B: Master speed

 

 

 

0001B: 1st step speed

 

 

 

0010B: 2nd step speed

 

 

 

0011B: 3rd step speed

 

 

 

0100B: 4th step speed

 

 

 

0101B: 5th step speed

 

 

 

0110B: 6th step speed

 

 

 

0111B: 7th step speed

 

 

 

1000B: 8th step speed

 

 

 

1001B: 9th step speed

 

 

 

1010B: 10th step speed

 

 

 

1011B: 11th step speed

 

 

 

1100B: 12th step speed

 

 

 

1101B: 13th step speed

 

 

 

1110B: 14th step speed

 

 

 

1111B: 15th step speed

 

 

Bit 12

Select Bit6~11 function

 

 

Bit 13-15

Reserved

 

2001H

Freq. command

 

2002H

Bit 0

1: EF (external fault) on

 

 

Bit 1

1: Reset

 

 

Bit 2

0: BB OFF

 

 

 

1: BB ON

Revision July 2008, EG03, SW V1.06

4-81

Page 132
Image 132
Delta Electronics VFD-G manual Bb Off