Chapter 4 Parameters
| Parameter | Functions | Settings | Factory | Customer |
|
| Setting |
| ||||
|
|
|
|
|
| |
JOG Acceleration | 0.1~3600.0 Sec | 10.0/ |
|
| ||
|
| Time |
| 60.0 |
|
|
JOG Deceleration | 0.1~3600.0 Sec | 10.0/ |
|
| ||
|
| Time |
| 60.0 |
|
|
JOG Frequency | 0.0 Hz~160.00 Hz | 6.00 |
|
| ||
S Curve Delay Time | 0.00~2.50sec | 0.00 |
|
| ||
|
| in Accel |
|
|
|
|
S Curve Delay Time | 0.00~2.50sec | 0.00 |
|
| ||
|
| in Decel |
|
|
|
|
Modulation Index | 0.90~1.20 | 1.00 |
|
| ||
Accel/Decel Time Unit | 00: Unit is 1 Sec | 01 |
|
| ||
|
|
| 01: Unit is 0.1 Sec |
|
|
|
|
|
| 02: Unit is 0.01 Sec |
|
|
|
Group 2 Operation Method Parameters
Parameter | Functions | Settings | Factory | Customer |
|
|
| Setting |
|
Source of Frequency | 00: via keypad | 00 |
| |
| Command | 01: via analog input AI1 |
|
|
|
| 02: via analog input AI2 |
|
|
|
| 03: via RS485 serial communication |
|
|
|
| 04: via External Reference |
|
|
Source of Operation | 00: Controlled by the digital keypad | 00 |
| |
| Command | 01: Controlled by the external terminals, |
|
|
|
| keypad STOP enabled. |
|
|
|
| 02: Controlled by external terminals, keypad |
|
|
|
| STOP disabled. |
|
|
|
| 03: Controlled by the |
|
|
|
| interface, keypad STOP enabled. |
|
|
|
| 04: Controlled by the |
|
|
|
| interface, keypad STOP disabled. |
|
|
Stop Method | 00: Stop = ramp to stop, E.F. (External Fault) | 00 |
| |
|
| = coast to stop |
|
|
|
| 01: Stop = coast to stop, E.F. = coast to stop |
|
|
|
| 02: Stop = ramp to stop, E.F. = ramp to stop |
|
|
|
| 03: Stop = coast to stop, E.F. = ramp to stop |
|
|
PWM Carrier | 7.5~10HP: 4000~6000Hz | 6000 |
| |
| Frequency Selections | 15~30HP: 3000~6000Hz | 6000 |
|
|
| 40~125HP: 2000~6000Hz | 4000 |
|
|
| 150~300HP: 2000~4000Hz | 4000 |
|
Revision July 2008, EG03, SW V1.06 |